TeSys™ VLS Accessories
Refer to Catalog 9400CT1601
Fourth Pole Add-on
General Specifications—Fourth Pole Add-on
IEC ampere ratings |
16–125 A |
Available versions |
DIN rail mounting Door mounting Simultaneous closing with switch poles Early-make closing with respect to switch poles |
Size |
Compact and modular |
Selection—Fourth Pole Add-on
Catalog number |
IEC conventional free air thermal
current Ith (A) |
IEC rated
operational current Ie (A) |
---|---|---|
Simultaneous closing operation with respect to switch poles |
||
DIN Rail Mounting (VLS3P•••R•) |
||
40 |
40 |
|
63 |
45 |
|
63 |
63 |
|
Door Mounting (VLS3P•••D•) |
||
40 |
40 |
|
63 |
63 |
|
Early-make closing operation with respect to switch poles |
||
DIN Rail Mounting (VLS3P•••R•) |
||
125 |
125 |
|
Door Mounting (VLS3P•••D•) |
||
125 |
125 |
note
Certifications and Compliance for Fourth Pole Add-on Blocks (● = certification obtained)
Catalog number |
Certification Standard |
||
---|---|---|---|
cULus per UL 60947-4-1 / CSA C22.2 n° 60947-4-1-14 / |
cULus per UL 98 / CSA C22.2 n° 4 / |
IEC/EN 60947-1, IEC/EN 60947-3 |
|
● |
— |
Compliant |
|
● |
— |
||
● |
— |
||
— |
● |
||
— |
● |
||
— |
● |
Add-on Blocks
Operational Specifications
Auxiliary contacts |
||
---|---|---|
IEC conventional free air thermal current (Ith) |
10 A |
|
UL/CSA and IEC/EN 60947-5-1 designation |
A600-Q600 |
|
Tightening torque |
0.8 N•m (7.1 lb-in.) |
Other devices |
||
---|---|---|
Tightening torque |
VLS1NR1 |
1.8–2 N•m (16–18 lb-in) |
VLS8C2, VLS8M1/M2 |
mounting: 0.5 N•m (4.4 lb-in) extension with handle: 0.8 N•m (7.1 lb-in) |
Selection—Add-on Blocks
Catalog number |
Specifications |
---|---|
Auxiliary contacts, simultaneous operation with respect to switch poles |
|
1NO+1NC for VLS3P•••R• and VLS3P063R1 |
|
1NO+1NC for VLS3P•••D• |
|
Auxiliary contacts, early-break operation with respect to switch poles |
|
1EB (NO) for VLS3P016R1–VLS3P040R1, VLS3P063R1 |
|
1EB (NO) for VLS3P063R2–VLS3P125R2 |
|
Neutral terminal |
|
For VLS3P016R1–VLS3P040R1, VLS3P063R1 |
|
Mechanical interlock for line changeover (I-0-II) |
|
For VLS3P063R2–VLS3P125R2 and VLSH2S5BC: □ 5 mm (0.2 in.) [6] |
|
Mechanical coupling system for 6-8 pole disconnect switches |
|
For VLS3P016R1–VLS3P040R1 and VLS3P063R1: □ 5 mm (0.2 in.) [6] |
|
For VLS3P063R2–VLS3P125R2: □ 7 mm (0.3 in.) [7] |
Sequence and Maximum Combination of Add-on Blocks
DIN Rail Mounting Disconnect Switches
VLS3P016R1–VLS3P040R1 (DIN Rail Mounting)
VLS3P063R1 (DIN Rail Mounting)
Door Mounting Disconnect Switches
Mechanical Coupling and Mechanical Interlock for Line Changeover
VLS3P016R1–VLS3P040R1, VLS8C1–VLS8M1 (Rear Mounting)
VLS3P063R1 + VLS8C1–VLS8M1 (Rear Mounting)
VLS8C1–VLS8M1 |
||||||||
1 |
1 |
— |
1 |
VLS3P063R1 + VLS3P063R1 |
1 |
— |
1 |
1 |
1 |
1 |
— |
1 |
— |
— |
2 |
1 |
|
1 |
2 |
— |
— |
1 |
— |
1 |
1 |
|
1 |
1 |
— |
1 |
— |
1 |
1 |
1 |
|
1 |
1 |
1 |
— |
1 |
— |
1 |
1 |
|
1 |
1 |
1 |
— |
— |
— |
2 |
1 |
|
1 |
2 |
— |
— |
— |
1 |
1 |
1 |
|
1 |
2 |
— |
— |
— |
— |
2 |
1 |
|
1 |
— |
— |
1 |
1 |
— |
— |
1 |
|
1 |
— |
— |
— |
— |
— |
— |
1 |
VLS3P063R2–VLS3P125R2 + VLS8C2–VLS8M2 (Rear Mounting)
Rotary Handles
Selection—Rotary Handles (NEMA 1, 12, 3R, 4, and 4X. IEC IP65 unless otherwise specified)
Catalog number |
Specifications |
---|---|
Door Mounting and Rear Mounting Handles, Padlock-ready[8] |
|
Red/yellow, rotating |
|
For VLS3P•••R• and VLS3P•••D•. Screw mounting. Recessed selector. □ 5 mm (0.2 in.) [9]. |
|
For VLS3P•••R• and VLS3P•••D•. Screw mounting. Protruding selector. □ 5 mm (0.2 in.). [9] |
|
For VLS3P•••R•
and VLS3P016D1–VLS3P040D1. Ring mounting. Protruding selector. |
|
For VLS3P•••R•.
Ring mounting. Protruding selector with release, defeatable per UL60947-4-1; |
|
For VLS3P•••R•, VLS3P063R1, VLS3P016D1–VLS3P040D1. Ring mounting. Low-profile protruding selector, □ 5 mm (0.2 in.). |
|
For VLS3P063R2–VLS3P125R2, and VLS8M2. Screw mounting. Pistol grip with release, defeatable per 60947-4-1; □ 7 mm (0.3 in.). IEC IP66. [11] |
|
For For VLS3P•••R•
and VLS3P•••D•. Screw mounting. Protruding
selector. 48 mm square. |
|
Black, rotating |
|
For VLS3P•••R• and VLS3P•••D•. Screw mounting. Recessed selector. □ 5 mm (0.2 in.). [9] |
|
For VLS3P•••R• and VLS3P•••D•. Screw mounting. Protruding selector. □ 5 mm (0.2 in.). [9] |
|
For VLS3P•••R•,
VLS3P063R1, VLS3P016D1–VLS3P040D1. Ring mounting. Protruding
selector. |
|
For VLS3P•••R•.
Ring mounting. Protruding selector with release, defeatable per 60947-4-1. |
|
For VLS3P•••R•, VLS3P063R1, VLS3P016D1–VLS3P040D1. Ring mounting. Low profile protruding selector, □ 5 mm (0.2 in.). |
|
For VLS3P•••R•, VLS3P063R1, VLS3P016D1–VLS3P040D1. Ring mounting. Lock On protruding selector, □ 5 mm (0.2 in.). |
|
For VLS3P063R2–VLS3P125R2, and VLS8M2. Screw mounting. Pistol grip with release, defeatable per UL60947-4-1; □ 7 mm (0.3 in.). [11] |
|
For VLS8C• mechanical interlock mechanism (I-O-II). □ 5 mm (0.2 in.). [9] |
|
For For VLS3P•••R• and VLS3P•••D•. Screw mounting. Protruding selector. □ 5 mm (0.2 in.). [9] |
|
Accessories for Rear Mounting Control For VLSH3S7RD and VLSH3S7BD handles. |
|
Adapter, □ 7 mm (0.3 in.) for VLS3P063R2-–VLS3P125R2. |
Certifications and Compliance (● = certification obtained)
Catalog number |
cULus per UL60947-4-1 / CSA C22.2 n° 60947-4-1-14 UL Listed (File E487906) |
cULus per UL98 / CSA C22.2 n° 4 UL Listed (File E487907) |
---|---|---|
UL Listed, cULus File E478582 CSA C22.2 n° 14-10 |
— |
|
— |
||
— |
||
● |
— |
|
● |
— |
|
● |
— |
|
— |
● |
|
VLSH1S5R |
● |
● |
● |
● |
|
● |
● |
|
● |
● |
|
● |
● |
|
● |
— |
|
● |
● |
|
● |
● |
|
— |
● |
|
● |
● |
|
VLSHA7 |
— |
● |
Compliant with standards: IEC/EN 60947-1, IEC/EN 60947-3, IEC/EN 60947-5-1, UL 60947-4-1, UL 98, CSA C22.2. |
Operating Specifications
Handle mounting |
ring or screw |
|
Mounting handle interaxis (compatible with the pre-existing drillings of the most common types in the marketplace) |
36 x 36 mm (1.4 x 1.4 in.) or 48 x 48 mm (1.9 x 1.9 in.) |
|
36 x 36 mm (1.4 x1.4 in.) |
||
Padlocks |
1–3 for all handles Ø4–8 mm (Ø0.2–0.3 in.) |
|
Tightening torque |
Mounting ring types |
2.3 N•m (20.4 lb-in) |
0.8 N•m (7 lb-in) |
||
1.5 N•m (13.3 lb-in) |
||
All others |
1 N•m (9 lb-in) |
|
Degree of protection |
IEC / EN: IP65 for all except VLSH3S7RD/BD, which are IP66. UL / CSA: VLSH1S5R/B and VLSH3S7RD/BD are Type 1, 12, 3R, 4, and 4X outdoor use with all VLS switch models. VLSH2S5R/B, VLSH2H5R/B, VLSH2H5RD/BD and VLSH2S5BC are Types 1, 12, 3R, 4, and 4X outdoor use with VLS3P016R1/D1–VLS3P040R1/D1 and VLS3P063R1 models, otherwise Type 1 only. |
Certifications and Compliance: See Certifications and Compliance (● = certification obtained) for details. |
Shaft Extensions, Terminal Covers, Fuse Holders, and Fuse Blocks
Selection—Shaft Extensions, Terminal Covers, Fuse Holders, and Fuse Blocks
Catalog number |
Specifications |
Qty per package |
Weight,kg (lb) |
---|---|---|---|
Shaft extension for rear-mounting handles VLSH1S5R–VLSH2H5RD, VLSH1S5B–VLSH2H5BD, VLSH2S5BC; interlocking changeover type VLS8C1, VLS8C2; and mechanical disconnect switch system VLS8M1 |
|||
150 mm long; □ 5 mm (0.2 in.) |
1 |
0.032 (0.07) |
|
300 mm long; □ 5 mm (0.2 in.) |
1 |
0.068 (0.15) |
|
500 mm long; □ 5 mm (0.2 in.) |
1 |
0.090 (0.20) |
|
Shaft extension for rear-mounting handles VLSH3S7RD/BD, and mechanical coupling system VLS8M2 |
|||
150 mm long; □ 7 mm (0.3 in.) |
1 |
0.090 (0.20) |
|
300 mm long; □ 7 mm (0.3 in.) |
1 |
0.160 (0.35) |
|
500 mm long; □ 7 mm (0.3 in,) |
1 |
0.250 (0.55) |
|
Support for □ 7 mm shaft |
1 |
0.160 (0.35) |
|
Set of 2 three-pole terminal covers |
|||
For VLS3P016R1–VLS3P040R1, VLS3P063R1, VLS3P016D1–VLS3P040D1 |
1 |
0.018 (0.04) |
|
For VLS3P063R2–VLS3P125R2, VLS3P063D2–VLS3P125D2 |
1 |
0.030 (0.07) |
|
Fuse holder/block for disconnect switches |
|||
For VLS3P016R1–VLS3P032R1 (suitable for Class CC fuses) |
1 |
0.135 (0.30) |
Operational Specifications of Fuse Holder
IEC rated insulation voltage, Ui |
1000 V |
IEC rated impulse withstand voltage, Uimp |
8 kV |
|
Certifications and Compliance (● = certification obtained)
Catalog number |
cULus per UL60947-4-1 / CSA C22.2
n° 60947-4-1-14 |
cULus per
UL98 / CSA C22.2 n° 4 |
---|---|---|
VLSS1505, VLSS3005, VLSS5005 |
● |
— |
VLSS1507, VLSS3007 |
● |
— |
VLSC3P1 |
— |
— |
VLSC3P2 |
— |
— |
VLSFH1UL |
● |
— |
Compliant with standards: IEC/EN 60947-1, IEC/EN 60947-3, UL60947-4-1, UL98, CSA C22.2. |