Recommended Upstream Protection for Easy UPS 3S
Easy UPS 3S – 3:1 UPS System
UPS rating | 3+0 parallel capacity | 2+0
parallel capacity 2+1 parallel redundant |
||||||
---|---|---|---|---|---|---|---|---|
Breaker type | Io | Ir | Isd | Breaker type | Io | Ir | Isd | |
10 kVA |
Compact NSX160F 160A TM160D (C16F3TM160) |
Fixed |
Fixed/100 |
/ |
C120H-C-100A/NSX100F 100A TMD (C10F3TM100) |
Fixed |
Fixed/100 |
/ |
15 kVA |
Compact NSX250F TM250D (C25F3TM250) |
5~10*In |
225 |
/ |
Compact NSX160F 160A TM160D (C16F3TM160) |
Fixed |
Fixed/160 |
/ |
20 kVA |
NSX400N mic2.3 (C40N32D400) |
280 |
280 |
1.5-10 |
Compact NSX250F TM200D (C25F3TM200) |
5~10*In |
200 |
/ |
30 kVA |
NSX630N mic2.3 (C63N32D630) |
450 |
441 |
1.5-10 |
NSX400N mic2.3 (C40N32D400) |
280 |
280 |
1.5-10 |
Easy UPS 3S – 3:1 UPS System
UPS rating | 1+0 single 1+1 parallel redundant |
|||
---|---|---|---|---|
Breaker type | Io | Ir | Isd | |
10 kVA |
iC65H-C-50A/C60H-C-50A |
Fixed |
Fixed |
/ |
15 kVA |
C120H-C-80A/NSX100F 80A TM100D (C10F3TM080) |
Fixed |
Fixed/80 |
/ |
20 kVA |
C120H-C-100A/NSX100F 100A TM100D (C10F3TM100) |
Fixed |
Fixed/100 |
/ |
30 kVA |
Compact NSX160F 160A TM160D (C16F3TM160) |
Fixed |
144 |
/ |
Easy UPS 3S – 3:3 UPS System
UPS rating | 3+0 parallel capacity | 2+0
parallel capacity 2+1 parallel redundant |
||||||
---|---|---|---|---|---|---|---|---|
Breaker type | Io | Ir | Isd | Breaker type | Io | Ir | Isd | |
10 kVA |
iC65H-C-63A / C60H-C-63A /C120H-C-63A |
Fixed |
Fixed |
Fixed |
iC65H-C-40A/C60H-C-40A |
Fixed |
Fixed |
Fixed |
15 kVA |
C120H-C-100A / NSX100F TM100D 100A (C10F3TM100) |
Fixed/100 |
Fixed/100 |
Fixed |
iC65H-C-63A/C60H-C-63A /C120H-C-63A |
Fixed |
Fixed |
Fixed |
20 kVA |
Compact NSX160F TM125D (C16F3TM125) |
Fixed |
125 |
Fixed |
C120H-C-80A/NSX100F TM80D 80A (C10F3TM080) |
Fixed |
Fixed/80 |
Fixed |
30 kVA |
NSX250N mic2.2 (C25N32D250) |
200 |
200 |
1.5-10 |
Compact NSX160F TM125D (C16F3TM125) |
Fixed |
125 |
Fixed |
40 kVA |
NSX250N mic2.2 (C25N32D250) |
250 |
225 |
1.5-10 |
Compact NSX160F TM160D (C16F3TM160) |
Fixed |
160 |
Fixed |
Easy UPS 3S – 3:3 UPS System
UPS rating | 1+0 single 1+1 parallel redundant |
|||
---|---|---|---|---|
Breaker type | Io | Ir | Isd | |
10 kVA |
iC65H-C-20A/C60H-C-20A |
Fixed |
Fixed |
Fixed |
15 kVA |
iC65H-C-32A/C60H-C-32A |
Fixed |
Fixed |
Fixed |
20 kVA |
iC65H-C-40A/C60H-C-40A |
Fixed |
Fixed |
Fixed |
30 kVA |
iC65H-C-63A/C60H-C-63A/C120H-C-63A |
Fixed |
Fixed |
Fixed |
40 kVA |
C120H-C-80A/NSX100F TM80D (C10F3TM080) |
Fixed |
Fixed/80 |
Fixed |