990-6392D-001

Specifications for Easy UPS 3S

In Easy UPS 3S systems E3MBP60K400H can be used as a single maintenance bypass panel or as a parallel maintenance bypass panel..

Overview of Easy UPS 3S System with Parallel Maintenance Bypass Panel

UIB Unit input switch
SSIB Static switch input switch
UOB Unit output switch
MBB Maintenance bypass switch in UPS
SIB System isolation switch
Ext. MBB External maintenance bypass switch
NOTE: In parallel systems with an external maintenance bypass switch (Ext. MBB), the maintenance bypass switches (MBB) in the UPSs must be padlocked in the open position.

Easy UPS 3S Single Mains System

Easy UPS 3S Dual Mains System

Recommended Cable Sizes for Easy UPS 3S

DANGER
hazard of electric shock, explosion, or arc flash
All wiring must comply with all applicable national and/or electrical codes. The maximum allowable cable size is 185 mm².
Failure to follow these instructions will result in death or serious injury.
NOTE: Overcurrent protection must be provided by others.

Cable sizes in this manual are based on:

  • Single core cables type U1000 R02V

  • Specific to AC cables: Maximum length 70 m with a line voltage drop <3% installed on perforated cable trays, XLPE-type insulation, single layer trefoil formation, THDI between 15% and 33%, 35 °C at 208 V grouped in four touching cables

  • Specific to DC cables: Maximum length 15 m with a line voltage drop <1%

NOTE: If neutral conductor is expected to carry a high current, due to line-neutral non-linear load, the circuit breaker must be rated according to expected neutral current.

Easy UPS 3S – 3:1 UPS System

UPS rating   3+0 Parallel Capacity 2+0 Parallel Capacity
2+1 Parallel Redundant
1+0 Single
1+1 Parallel Redundant
    Per phase (mm2) Neutral (mm2) PE (mm2) Per phase (mm²) Neutral (mm2) PE (mm²) Per phase (mm²) Neutral (mm2) PE (mm²)
10 kVA Load

50

50

25

35

35

16

16

16

16

Input (single mains)/
bypass (dual mains)

50

50

25

35

35

16

16

16

16

UPS output

16

16

16

16

16

10

16

16

16

15 kVA Load

2X50

2X50

50

50

50

25

25

25

16

Input (single mains)/
bypass (dual mains)

2X50

2X50

50

50

50

25

25

25

16

UPS output

25

25

16

25

25

16

25

25

16

20 kVA Load

2X70

2X70

70

2X35

2X35

35

35

35

16

Input (single mains)/
bypass (dual mains)

2X70

2X70

70

2X35

2X35

35

35

35

16

UPS output

35

35

16

35

35

16

35

35

16

30 kVA Load

3X70

3X70

2X70

2X70

2X70

70

50

50

25

Input (single mains)/
bypass (dual mains)

3X70

3X70

2X70

2X70

2X70

70

50

50

25

UPS output

50

50

25

50

50

25

50

50

25

Easy UPS 3S – 3:3 UPS System

UPS rating   3+0 Parallel Capacity 2+0 Parallel Capacity
2+1 Parallel Redundant
1+0 Single
1+1 Parallel Redundant
    Per phase (mm²) Neutral (mm2) PE (mm²) Per phase (mm²) Neutral (mm2) PE (mm²) Per phase (mm²) Neutral (mm2) PE (mm²)
10 kVA Load

16

2x16

16

10

2x10

10

6

2x6

6

Input (single mains)/
bypass (dual mains)

16

2x16

16

10

2x10

10

6

2x6

6

UPS output

6

2x6

6

6

2x6

6

6

2x6

6

15 kVA Load

16

2X16

16

16

2x16

16

6

2x6

6

Input (single mains)/
bypass (dual mains)

25

2X16

16

16

2x16

16

6

2x6

6

UPS output

6

2x6

6

6

2x6

6

6

2x6

6

20 kVA UPS output

35

2X25

16

25

2x25

16

10

2x10

10

Input (single mains)/
bypass (dual mains)

35

2X25

16

25

2x25

16

10

2x10

10

Load

10

2x10

10

10

2x10

10

10

2x10

10

30 kVA Load

70

2X70

35

25

2X25

16

16

2x16

16

Input (single mains)/
bypass (dual mains)

70

2X70

35

35

2X25

16

16

2x16

16

UPS output

16

2x16

16

16

2x16

16

16

2x16

16

40 kVA Load

95

3X95

50

50

2X50

25

25

2x25

16

Input (single mains)/
bypass (dual mains)

95

3X95

50

50

2X50

25

25

2x25

16

UPS output

25

2x25

16

25

2x25

16

25

2x25

16

Recommended Upstream Protection for Easy UPS 3S

Easy UPS 3S – 3:1 UPS System

UPS rating 3+0 parallel capacity 2+0 parallel capacity
2+1 parallel redundant
  Breaker type Io Ir Isd Breaker type Io Ir Isd
10 kVA

Compact NSX160F 160A TM160D (C16F3TM160)

Fixed

Fixed/100

/

C120H-C-100A/NSX100F 100A TMD (C10F3TM100)

Fixed

Fixed/100

/

15 kVA

Compact NSX250F TM250D (C25F3TM250)

5~10*In

225

/

Compact NSX160F 160A TM160D (C16F3TM160)

Fixed

Fixed/160

/

20 kVA

NSX400N mic2.3 (C40N32D400)

280

280

1.5-10

Compact NSX250F TM200D (C25F3TM200)

5~10*In

200

/

30 kVA

 NSX630N mic2.3  (C63N32D630)

450

441

1.5-10

NSX400N mic2.3 (C40N32D400)

280

280

1.5-10

Easy UPS 3S – 3:1 UPS System

UPS rating 1+0 single
1+1 parallel redundant
  Breaker type Io Ir Isd
10 kVA

iC65H-C-50A/C60H-C-50A

Fixed

Fixed

/

15 kVA

C120H-C-80A/NSX100F 80A TM100D (C10F3TM080)

Fixed

Fixed/80

/

20 kVA

C120H-C-100A/NSX100F 100A TM100D (C10F3TM100)

Fixed

Fixed/100

/

30 kVA

Compact NSX160F 160A TM160D (C16F3TM160)

Fixed

144

/

Easy UPS 3S – 3:3 UPS System

UPS rating 3+0 parallel capacity 2+0 parallel capacity
2+1 parallel redundant
  Breaker type Io Ir Isd Breaker type Io Ir Isd
10 kVA

 iC65H-C-63A / C60H-C-63A /C120H-C-63A

Fixed

Fixed

Fixed

iC65H-C-40A/C60H-C-40A

Fixed

Fixed

Fixed

15 kVA

C120H-C-100A / NSX100F TM100D 100A (C10F3TM100)

Fixed/100

Fixed/100

Fixed

iC65H-C-63A/C60H-C-63A /C120H-C-63A

Fixed

Fixed

Fixed

20 kVA

Compact NSX160F  TM125D (C16F3TM125)

Fixed

125

Fixed

C120H-C-80A/NSX100F TM80D 80A (C10F3TM080)

Fixed

Fixed/80

Fixed

30 kVA

NSX250N mic2.2 (C25N32D250)

200

200

1.5-10

Compact NSX160F TM125D (C16F3TM125)

Fixed

125

Fixed

40 kVA

NSX250N mic2.2 (C25N32D250)

250

225

1.5-10

Compact NSX160F TM160D (C16F3TM160)

Fixed

160

Fixed

Easy UPS 3S – 3:3 UPS System

UPS rating 1+0 single
1+1 parallel redundant
  Breaker type Io Ir Isd
10 kVA

iC65H-C-20A/C60H-C-20A

Fixed

Fixed

Fixed

15 kVA

iC65H-C-32A/C60H-C-32A

Fixed

Fixed

Fixed

20 kVA

iC65H-C-40A/C60H-C-40A

Fixed

Fixed

Fixed

30 kVA

iC65H-C-63A/C60H-C-63A/C120H-C-63A

Fixed

Fixed

Fixed

40 kVA

C120H-C-80A/NSX100F TM80D (C10F3TM080)

Fixed

Fixed/80

Fixed