Replace the Air Filter on UPS for Internal Batteries

  1. Open the front door.
  2. Loosen the screws and remove the metal brackets and the manual compartment.

    Rear View of the Front Door for 10-20 kVA UPS

    Rear View of the Front Door for 30-40 kVA UPS

  3. Replace the air filter.

    Rear View of the Front Door for 10-20 kVA UPS

    Rear View of the Front Door for 30-40 kVA UPS

  4. Reinstall the metal brackets and the manual compartment.

    Rear View of the Front Door for 10-20 kVA UPS

    Rear View of the Front Door for 30-40 kVA UPS

  5. Close the front door.
  6. Restart the air filter counter, see Configure the Air Filter Reminder.