Inverter Short–Circuit Capabilities (Bypass not Available)
IK1 – Short-Circuit between a Phase and Neutral

400 V IK1
S [kVA] | Ik10ms [A] Normal operation /Battery operation | Ik30ms [A] Normal operation /Battery operation | Ik100ms [A] Normal operation /Battery operation | Ik500ms [A] Normal operation /Battery operation | Ik1s [A] Normal operation /Battery operation | Ik5s [A] Normal operation /Battery operation | I2 t total [A2s] Normal operation /Battery operation |
---|---|---|---|---|---|---|---|
250 |
840 /840 |
820 /840 |
610 /640 |
550 /550 |
550 /550 |
550 /360 |
1539100 /874180 |
500 |
1680 /1680 |
1640 /1680 |
1220 /1280 |
1100 /1100 |
1100 /1100 |
1100 /720 |
6156400 /3496720 |
750 |
2520 /2520 |
2460 /2520 |
1830 /1920 |
1650 /1650 |
1650 /1650 |
1650 /1080 |
13851900 /7867620 |
1000 |
3360 /3360 |
3280 /3360 |
2440 /2560 |
2200 /2200 |
2200 /2200 |
2200 /1440 |
24625600 /13986880 |
1250 |
4200 /4200 |
4100 /4200 |
3050 /3200 |
2750 /2750 |
2750 /2750 |
2750 /1800 |
38477500 /21854500 |
1500 |
5040 /5040 |
4920 /5040 |
3660 /3840 |
3300 /3300 |
3300 /3300 |
3300 /2160 |
55407600 /31470480 |
IK2 – Short-Circuit between Two Phases

400 V IK2
S [kVA] | Ik10ms [A] Normal operation /Battery operation | Ik30ms [A] Normal operation /Battery operation | Ik100ms [A] Normal operation /Battery operation | Ik500ms [A] Normal operation /Battery operation | Ik1s [A] Normal operation /Battery operation | Ik5s [A] Normal operation /Battery operation | I2 t total [A2s] Normal operation /Battery operation |
---|---|---|---|---|---|---|---|
250 |
780 /780 |
780 /780 |
600 /600 |
510 /510 |
510 /510 |
510 /330 |
1312100 /740520 |
500 |
1560 /1560 |
1560 /1560 |
1200 /1200 |
1020 /1020 |
1020 /1020 |
1020 /660 |
5248400 /2962080 |
750 |
2340 /2340 |
2340 /2340 |
1800 /1800 |
1530 /1530 |
1530 /1530 |
1530 /990 |
11808900 /6664680 |
1000 |
3120 /3120 |
3120 /3120 |
2400 /2400 |
2040 /2040 |
2040 /2040 |
2040 /1320 |
20993600 /11848320 |
1250 |
3900 /3900 |
3900 /3900 |
3000 /3000 |
2550 /2550 |
2550 /2550 |
2550 /1650 |
32802500 /18513000 |
1500 |
4680 /4680 |
4680 /4680 |
3600 /3600 |
3060 /3060 |
3060 /3060 |
3060 /1980 |
47235600 /26658720 |
IK3 – Short-Circuit between All Three Phases

400 V IK3
S [kVA] | Ik10ms [A] Normal operation /Battery operation | Ik30ms [A] Normal operation /Battery operation | Ik100ms [A] Normal operation /Battery operation | Ik500ms [A] Normal operation /Battery operation | Ik1s [A] Normal operation /Battery operation | Ik5s [A] Normal operation /Battery operation | I2 t total [A2s] Normal operation /Battery operation |
---|---|---|---|---|---|---|---|
250 |
720 /720 |
720 /720 |
670 /640 |
540 /360 |
540 /360 |
540 /360 |
1507600 /711360 |
500 |
1440 /1440 |
1440 /1440 |
1340 /1280 |
1080 /720 |
1080 /720 |
1080 /720 |
6030400 /2845440 |
750 |
2160 /2160 |
2160 /2160 |
2010 /1920 |
1620 /1080 |
1620 /1080 |
1620 /1080 |
13568400 /6402240 |
1000 |
2880 /2880 |
2880 /2880 |
2680 /2560 |
2160 /1440 |
2160 /1440 |
2160 /1440 |
24121600 /11381760 |
1250 |
3600 /3600 |
3600 /3600 |
3350 /3200 |
2700 /1800 |
2700 /1800 |
2700 /1800 |
37690000 /17784000 |
1500 |
4320 /4320 |
4320 /4320 |
4020 /3840 |
3240 /2160 |
3240 /2160 |
3240 /2160 |
54273600 /25608960 |