990-5850L-001

Inverter Short–Circuit Capabilities (Bypass not Available)

IK1 – Short-Circuit between a Phase and Neutral

400 V IK1

S [kVA] Ik10ms [A] Normal operation /Battery operation Ik30ms [A] Normal operation /Battery operation Ik100ms [A] Normal operation /Battery operation Ik500ms [A] Normal operation /Battery operation Ik1s [A] Normal operation /Battery operation Ik5s [A] Normal operation /Battery operation I2 t total [A2s] Normal operation /Battery operation

250

840

/840

820

/840

610

/640

550

/550

550

/550

550

/360

1539100 /874180

500

1680 /1680

1640 /1680

1220 /1280

1100 /1100

1100 /1100

1100

/720

6156400 /3496720

750

2520 /2520

2460 /2520

1830 /1920

1650 /1650

1650 /1650

1650 /1080

13851900 /7867620

1000

3360 /3360

3280 /3360

2440 /2560

2200 /2200

2200 /2200

2200 /1440

24625600 /13986880

1250

4200 /4200

4100 /4200

3050 /3200

2750 /2750

2750 /2750

2750 /1800

38477500 /21854500

1500

5040 /5040

4920 /5040

3660 /3840

3300 /3300

3300 /3300

3300 /2160

55407600 /31470480

IK2 – Short-Circuit between Two Phases

400 V IK2

S [kVA] Ik10ms [A] Normal operation /Battery operation Ik30ms [A] Normal operation /Battery operation Ik100ms [A] Normal operation /Battery operation Ik500ms [A] Normal operation /Battery operation Ik1s [A] Normal operation /Battery operation Ik5s [A] Normal operation /Battery operation I2 t total [A2s] Normal operation /Battery operation

250

780

/780

780

/780

600

/600

510

/510

510

/510

510

/330

1312100 /740520

500

1560 /1560

1560 /1560

1200 /1200

1020 /1020

1020 /1020

1020

/660

5248400 /2962080

750

2340 /2340

2340 /2340

1800 /1800

1530 /1530

1530 /1530

1530

/990

11808900 /6664680

1000

3120 /3120

3120 /3120

2400 /2400

2040 /2040

2040 /2040

2040 /1320

20993600 /11848320

1250

3900 /3900

3900 /3900

3000 /3000

2550 /2550

2550 /2550

2550 /1650

32802500 /18513000

1500

4680 /4680

4680 /4680

3600 /3600

3060 /3060

3060 /3060

3060 /1980

47235600 /26658720

IK3 – Short-Circuit between All Three Phases

400 V IK3

S [kVA] Ik10ms [A] Normal operation /Battery operation Ik30ms [A] Normal operation /Battery operation Ik100ms [A] Normal operation /Battery operation Ik500ms [A] Normal operation /Battery operation Ik1s [A] Normal operation /Battery operation Ik5s [A] Normal operation /Battery operation I2 t total [A2s] Normal operation /Battery operation

250

720

/720

720

/720

670

/640

540

/360

540

/360

540

/360

1507600 /711360

500

1440 /1440

1440 /1440

1340 /1280

1080

/720

1080

/720

1080

/720

6030400 /2845440

750

2160 /2160

2160 /2160

2010 /1920

1620 /1080

1620 /1080

1620 /1080

13568400 /6402240

1000

2880 /2880

2880 /2880

2680 /2560

2160 /1440

2160 /1440

2160 /1440

24121600 /11381760

1250

3600 /3600

3600 /3600

3350 /3200

2700 /1800

2700 /1800

2700 /1800

37690000 /17784000

1500

4320 /4320

4320 /4320

4020 /3840

3240 /2160

3240 /2160

3240 /2160

54273600 /25608960

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.