990-5783J-001

Inverter Short–Circuit Capabilities (Bypass not Available)

IK1 – Short-Circuit between a Phase and Neutral

400 V IK1

S [kVA] Ik10ms [A] Normal operation /Battery operation Ik30ms [A] Normal operation /Battery operation Ik100ms [A] Normal operation /Battery operation Ik500ms [A] Normal operation /Battery operation Ik1s [A] Normal operation /Battery operation Ik5s [A] Normal operation /Battery operation I2 t total [A2s] Normal operation /Battery operation

250

840

/840

820

/840

610

/640

550

/550

550

/550

550

/360

1539100 /874180

500

1680 /1680

1640 /1680

1220 /1280

1100 /1100

1100 /1100

1100

/720

6156400 /3496720

750

2520 /2520

2460 /2520

1830 /1920

1650 /1650

1650 /1650

1650 /1080

13851900 /7867620

1000

3360 /3360

3280 /3360

2440 /2560

2200 /2200

2200 /2200

2200 /1440

24625600 /13986880

1250

4200 /4200

4100 /4200

3050 /3200

2750 /2750

2750 /2750

2750 /1800

38477500 /21854500

1500

5040 /5040

4920 /5040

3660 /3840

3300 /3300

3300 /3300

3300 /2160

55407600 /31470480

480 V IK1

S [kVA] Ik10ms [A] Normal operation /Battery operation Ik30ms [A] Normal operation /Battery operation Ik100ms [A] Normal operation /Battery operation Ik500ms [A] Normal operation /Battery operation Ik1s [A] Normal operation /Battery operation Ik5s [A] Normal operation /Battery operation I2 t total [A2s] Normal operation /Battery operation

250

/810

/810

/570

/290

/290

/290

/493600

500

/1620

/1620

/1140

/580

/580

/580

/1974400

750

/2430

/2430

/1710

/870

/870

/870

/4442400

1000

/3240

/3240

/2280

/1160

/1160

/1160

/7897600

1250

/4050

/4050

/2850

/1450

/1450

/1450

/12340000

1500

/4860

/4860

/3420

/1740

/1740

/1740

/17769600

IK2 – Short-Circuit between Two Phases

400 V IK2

S [kVA] Ik10ms [A] Normal operation /Battery operation Ik30ms [A] Normal operation /Battery operation Ik100ms [A] Normal operation /Battery operation Ik500ms [A] Normal operation /Battery operation Ik1s [A] Normal operation /Battery operation Ik5s [A] Normal operation /Battery operation I2 t total [A2s] Normal operation /Battery operation

250

780

/780

780

/780

600

/600

510

/510

510

/510

510

/330

1312100 /740520

500

1560 /1560

1560 /1560

1200 /1200

1020 /1020

1020 /1020

1020

/660

5248400 /2962080

750

2340 /2340

2340 /2340

1800 /1800

1530 /1530

1530 /1530

1530

/990

11808900 /6664680

1000

3120 /3120

3120 /3120

2400 /2400

2040 /2040

2040 /2040

2040 /1320

20993600 /11848320

1250

3900 /3900

3900 /3900

3000 /3000

2550 /2550

2550 /2550

2550 /1650

32802500 /18513000

1500

4680 /4680

4680 /4680

3600 /3600

3060 /3060

3060 /3060

3060 /1980

47235600 /26658720

480 V IK2

S [kVA] Ik10ms [A] Normal operation /Battery operation Ik30ms [A] Normal operation /Battery operation Ik100ms [A] Normal operation /Battery operation Ik500ms [A] Normal operation /Battery operation Ik1s [A] Normal operation /Battery operation Ik5s [A] Normal operation /Battery operation I2 t total [A2s] Normal operation /Battery operation

250

790

/790

770

/770

550

/550

430

/280

430

/280

280

/280

606450 /460820

500

1580 /1580

1540 /1540

1100 /1100

860

/560

860

/560

560

/560

2425800 /1843280

750

2370 /2370

2310 /2310

1650 /1650

1290

/840

1290

/840

840

/840

5458050 /4147380

1000

3160 /3160

3080 /3080

2200 /2200

1720 /1120

1720 /1120

1120 /1120

9703200 /7373120

1250

3950 /3950

3850 /3850

2750 /2750

2150 /1400

2150 /1400

1400 /1400

15161250 /11520500

1500

4740 /4740

4620 /4620

3300 /3300

2580 /1680

2580 /1680

1680 /1680

21832200 /16589520

IK3 – Short-Circuit between All Three Phases

400 V IK3

S [kVA] Ik10ms [A] Normal operation /Battery operation Ik30ms [A] Normal operation /Battery operation Ik100ms [A] Normal operation /Battery operation Ik500ms [A] Normal operation /Battery operation Ik1s [A] Normal operation /Battery operation Ik5s [A] Normal operation /Battery operation I2 t total [A2s] Normal operation /Battery operation

250

720

/720

720

/720

670

/640

540

/360

540

/360

540

/360

1507600 /711360

500

1440 /1440

1440 /1440

1340 /1280

1080

/720

1080

/720

1080

/720

6030400 /2845440

750

2160 /2160

2160 /2160

2010 /1920

1620 /1080

1620 /1080

1620 /1080

13568400 /6402240

1000

2880 /2880

2880 /2880

2680 /2560

2160 /1440

2160 /1440

2160 /1440

24121600 /11381760

1250

3600 /3600

3600 /3600

3350 /3200

2700 /1800

2700 /1800

2700 /1800

37690000 /17784000

1500

4320 /4320

4320 /4320

4020 /3840

3240 /2160

3240 /2160

3240 /2160

54273600 /25608960

480 V IK3

S [kVA] Ik10ms [A] Normal operation /Battery operation Ik30ms [A] Normal operation /Battery operation Ik100ms [A] Normal operation /Battery operation Ik500ms [A] Normal operation /Battery operation Ik1s [A] Normal operation /Battery operation Ik5s [A] Normal operation /Battery operation I2 t total [A2s] Normal operation /Battery operation

250

670

/660

670

/660

610

/610

440

/440

360

/440

300

/300

580600 /589380

500

1340 /1320

1340 /1320

1220 /1220

880

/880

720

/880

600

/600

2322400 /2357520

650

1742 /1716

1742 /1716

1586 /1586

1144 /1144

936

/1144

780

/780

3924856 /3984209

1000

2680 /2640

2680 /2640

2440 /2440

1760 /1760

1440 /1760

1200 /1200

9289600 /9430080

1250

3350 /3300

3350 /3300

3050 /3050

2200 /2200

1800 /2200

1500 /1500

14515000 /14734500

1500

4020 /3960

4020 /3960

3660 /3660

2640 /2640

2160 /2640

1800 /1800

20901600 /21217680

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?