Communications setup
Setting the primary address
SND_UD code |
Data format |
Primary VIF |
Range/Options |
Description |
---|---|---|---|---|
00 |
01 |
7A |
0 – 250 |
Primary address |
Setting the baud rate
To change the baud rate via communications, send a telegram to the meter with the appropriate value in the CI-field:
Baud rate |
Hex value for CI-field |
---|---|
300 |
B8 |
600 |
B9 |
1200 |
BA |
2400 |
BB |
4800 |
BC |
9600 |
BD |