Example configuration telegram
hex |
Description |
68 |
Start character |
07 |
L-field |
07 |
L-field repetition |
68 |
Start character |
53 |
C-field (control field) SND_UD = Send user data to slave |
04 |
A-field (address field) Slave address of the meter you want to reset |
51 |
CI-field (control information field) Data send to slave |
00 |
Indicates no data is sent (because this is a reset) |
FF |
VIF indicating the next field is manufacturer specific |
8D |
Manufacturer-specific VIFE: Reset partial energy |
07 |
Action = Reset |
xx |
Automatically generated Checksum |
16 |
Stop character |