Installing the MCC
This section explains how to locate, install, and join Model 6 MCC enclosures, and how to splice power and the ground bus. Refer to MCC front elevation drawings supplied by Schneider Electric for location/placement of shipping splits/sections within each MCC line-up. For information related to removing and installing existing and new units, see Expansion, or the information included with the shipment of the new device.
Locating the MCC
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
MCCs are designed for use in non-hazardous locations. Choose a location for installation that is well ventilated and free from excess humidity, dust, and dirt. The temperature of the area must be no less than 0°C (32°F) and no greater than 40°C (104°F). Protect the MCC from the entrance of water or any moisture. If necessary, protect the MCC from condensation by ordering internal space heaters.
Space Requirements
Install MCCs in an area with a minimum of 3 ft. (0.9 m) of free space in front of front-of-board construction. An additional 3 ft. (0.9 m) is necessary in the rear of back-to-back construction. This free space provides adequate room to remove and install units. (More space may be required for some applications; refer to applicable local and national installation codes.) Provide at least 0.5 in. (13 mm) of space between the back of front-of-board MCCs and a wall. For damp locations, provide at least 6 in. (152 mm).
When selecting a location for the installation of an MCC, carefully consider accessibility, overhead clearances, and future expansions. Considering these factors minimizes many difficulties during this and future MCC installations.
DANGER |
|---|
|
Burn hazard from HOT GASES
Failure to follow these instructions will result in death or serious injury.
|
The shaded area (see Required Obstruction-Free Area) above the arc-rated MCC must be free from obstructions.
Aligning the MCC
Provide a smooth, level surface for installation. An uneven foundation may cause misalignment of shipping blocks, units, and doors. The surface under an MCC must be of a non-combustible material unless bottom plates are installed in each vertical section.
Joining Type 1, Type 1 Gasketed, and Type 12 Sections
Before positioning the MCC sections (see Motor Control Center Views), check for damaged bus bars and insulators. If the bus is bent or insulators are broken, do not install the MCC. Report any damage to the carrier.
-
A joining hardware kit is bagged and tied to the right front corner channel of each shipping split. Captive splice bars are preassembled on the horizontal bus on the left side of each shipping split.
-
For gasket installation instructions, see Splice Gaskets for Type 1 Gasketed, Type 1 Sprinkler-resistant, and Type 12 Enclosures before joining sections.
Positioning the MCC
To mount and splice a new MCC section to an existing Model 6 section, or to join factory shipping splits:
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Remove the upper and lower horizontal wireway covers in all sections, providing access to each section’s front splicing bolts (see Motor Control Center Views, View B).
-
Gain access to each section’s bus splicing provisions buy sliding the panels of the two-piece bus barriers (see Motor Control Center Views, View C) in the sections adjacent to a splice connection (the left and right sections).
-
Make provisions for fastening the structure(s) to the floor and wall. See Securing Structures to the Floor, Seismic Certification of Model 6 MCCs, Responsibility for Mitigation of Seismic Damage, Securing Structures to Floor—Seismic Hazard Designated Locations, and Securing Structures to Wall—Seismic Hazard Designated Locations for fastener locations.
-
Supporting the MCC by its base channels and/or lifting angles, lift it into place. The front edges of the base channels must align to form a continuous front in a straight line. Use a chalk line, string, or other method to align the front base channels in a straight line.
-
Using the notches in the base channels, carefully move the sections in to alignment with a crowbar (see Base Channel Notches).
NOTE: Follow all manufacturer-specified instructions and precautions when moving heavy equipment. See Handling the MCC before moving the MCC.
Joining Corner Channels
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
The hardware kit for joining sections (see Hardware Kit) is bagged and tied to the right front corner channel of each shipping split.
-
Locate the four half-circle shaped notches on the inside surface of the corner channels (see Bolting Sections Together: Joining Corner Channels, View A).
-
Using four of the 3/4 in. x 1/4-20 hex head thread-forming screws supplied in the hardware kit, join the front vertical corner channels by inserting the screws through the clearance holes located within the half-circle shaped notches and into the mating thread-forming hole (see Bolting Sections Together: Joining Corner Channels, View B).
NOTE: Insert the screws from whichever side provides the easiest access to the holes; either side allows proper joining of the channels. -
Tighten the screws (see Bolting Sections Together: Joining Corner Channels, View C).
-
Repeat steps 3–5 to connect the rear corner channels.
Joining Section Side Channels
-
Locate two clearance holes for 1/4-20 hardware on the inside surface of the bottom section side channels (see Bolting Sections Together: Joining Corner Channels, Views A and B). These are accessible after removal of the bottom wireway cover.
-
Use two of the four 1-1/4 in. x 1/4-20 hex head thread-forming screws supplied in the hardware kit to join the bottom section side channels. The screw installed at the front is installed from the right-hand section (see Bolting Sections Together: Joining Corner Channels, View A).
-
The screw installed at the rear is installed from the left-hand section (see Bolting Sections Together: Joining Corner Channels, View B).
-
Locate two clearance holes for 1/4-20 hardware on the inside surface of the top section side channels. The front clearance hole is in the left section and is accessible after removal of the top wireway cover (see Bolting Sections Together: Joining Corner Channels, View C).
-
The rear clearance hole is in the right section. In most cases, it is necessary to remove the section back plate or the top plate to gain access to the rear clearance hole and install the screw (see Bolting Sections Together: Joining Corner Channels, View D).
Securing Structures to the Floor
Non-seismic Applications
Fasten each section to the floor (see Standard Base Channel Mounting) using 1/2 in. or 3/4 in., grade 5 or higher, bolts, and flat washers (furnished by customer).
0.88 in. (22 mm) diameter base channel mounting holes provide clearance for bolt expansion anchors for 1/2 in. bolts.
| A | Structure anchoring locations (typical of four) |
Seismic Certification of Model 6 MCCs
Introduction
Model 6 Motor Control Centers that are seismically certified have been certified to the seismic requirements of the listed regional building codes and/or seismic design standards per the manufacturer’s certificate of compliance (CoC). Equipment labels and CoCs are provided with all seismically certified Model 6 Motor Control Centers. Refer to the equipment CoC for certification details and applicable seismic parameters. To maintain the validity of this certification, the installation instructions provided in this section must be followed.
Responsibility for Mitigation of Seismic Damage
Model 6 MCCs are considered nonstructural building components, as defined by regional building codes and seismic design standards. Equipment capacity was determined from tri-axial seismic shake table test results in accordance with the International Code Counsel Evaluation Service (ICC ES) Acceptance Criteria for Seismic Certification by Shake-TableTesting of Nonstructural Components (AC156).
An equipment importance factor, Ip, that is greater than one (Ip > 1.0) is assumed and indicates that equipment functionality is required after a seismic event and after seismic simulation testing. This importance factor is applicable for designated seismic systems, for example, special certification, servicing critical infrastructure where post- earthquake equipment functionality is a requirement.
Incoming and outgoing bus, cable, and conduit must also be considered as related, but independent, systems. These distribution systems must be designed and restrained to withstand the forces generated by the seismic event without increasing the load transferred to the equipment. For applications where seismic hazard exists, it is preferable for bus, cable, and conduit to enter and exit the bottom of the equipment enclosure.
Seismic qualification of nonstructural components and equipment by Schneider Electric is just one link in the total chain of responsibility required to maximize the probability that the equipment is intact and functional after a seismic event. During a seismic event, the equipment must be able to transfer the inertial loads that are created and reacted through the equipment’s force resisting system and anchorage to the load-bearing path of the building structural system or foundation.
Anchorage of equipment, for example, nonstructural supports and attachments, to the primary building structure or foundation is required to validate seismic conformance. The construction site structural engineer or registered design professional or engineer of record (EOR) is responsible for detailing the equipment anchorage requirements for the given installation. The installer and manufacturers of the anchorage system are responsible for assuring the mounting requirements are met. Schneider Electric is not responsible for the specification and performance of anchorage systems.
Tie-Down Points for Rigid, Floor-Mounted Equipment
The equipment enclosure provides anchorage tie-down points to accept anchor attachments to the building structure or foundation. Model 6 MCC indoor enclosures provide enclosure base frame clearance holes for bolted anchorage attachments, as shown in Type 1, Type 1 Gasketed, Type 1 Sprinkler Resistant, and Type 12 Seismic Tie Down Locations and Seismic Tie-Down Locations for 18-Pulse AC Drive MCC Sections. Model 6 MCC outdoor enclosures provide enclosure base frame clearance holes for bolted anchorage attachments, as shown in Type 3R Seismic Tie-Down Locations.
MCC sections must be anchored using all enclosure tie-down points, as shown in the previous referenced topics, for indoor and outdoor applications.
Anchorage Assembly Instructions
The bolted anchor assembly view depicted in Bolted Anchor Assembly illustrates the equipment’s as-tested attachment to a seismic shake-table test fixture. The equipment seismic capacity, as stated on the Schneider Electric CoC, was achieved with the identified size and grade attachment hardware. For bolted attachments, the use of factory-supplied Belleville conical spring washers at specified locations is required to maintain seismic conformance. Field installed equipment attachment and support detailing must be in accordance with the anchorage system requirements as defined by the construction site structural engineer, registered design professional, or engineer of record.
Welded Anchorage
Equipment installations using welded supports and attachments in lieu of bolted supports and attachments must ensure the weld locations are distributed similarly to the locations of enclosure anchorage clearance holes. Welded supports and attachments must be properly sized to ensure the weldment withstand capacity exceeds the earthquake demand at the equipment installation location. Precautions must be taken to properly vent and shield the equipment enclosure during the field welding process. Paint must be removed from the equipment weld locations before welding, and then replaced after welding is complete to inhibit corrosion.
Securing Structures to Floor-Seismic Hazard* Designated Locations
Each section must be anchored per detail supplied by engineer of record to the load bearing path of the building structural system. For floor mounting locations, see Type 1, Type 1 Gasketed, Type 1 Sprinkler Resistant, and Type 12 Seismic Tie Down Locations or Seismic Tie-Down Locations for 18-Pulse AC Drive MCC Sections. Use anchorage designed by and supplied by others. Seismic test units were anchored with 1/2-13 SAE Grade 5 hardware and Belleville conical washers. 1/2 in. and 3/4 in. Belleville washers are supplied with equipment for use with the seismic anchorage.
Seismic Tie-down Access for ArcBlok 1200 with Bottom-feed, Line-side, Isolation Cable Vault
The front cover and rear panel assembly of each ArcBlok bottomfeed cable vault are removable to allow access to seismic tie-down points. Refer to Front Cover and Rear Panel of Cable Vault, Type 1, Type 1 Gasketed, Type 1 Sprinkler Resistant, and Type 12 Seismic Tie Down Locations, Seismic Tie-Down Locations for 18-Pulse AC Drive MCC Sections, and Type 3R Seismic Tie-Down Locations.
| A | Structure anchoring locations (typical of 4) |
|
15 (381) Section Dimensions in. (mm)
|
20 (508) Section Dimensions in. (mm)
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
NOTE: The dimensions shown are tie-down
locations within individual MCC sections. Refer to factory supplied
drawings to determine appropriate anchor locations for the equipment
pad.
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
-
Remove and retain the 3/8-16 Keps™ nuts securing the cable vault front cover.
-
Remove the cable vault front cover.
-
Remove and retain the 3/8-16 Keps nuts securing the cable vault rear panel.
-
Remove the rear panel from the inside of the cable vault.
-
Install the seismic hardware.
-
Reinstall the rear panel and front cover using the 3/8-16 Keps nuts retained in steps 1 and 3.
Seismic Tie-Down Access for ArcBlok 2500 with Bottom-feed, Line-side, Isolation Cable Vault
Anchor Point Access for ArcBlok 2500 with Bottom-Feed, Line-Side, Isolation Cable Vault
The front cover and rear access panel of each ArcBlok bottom-feed cable vault are removable to allow access to section anchor points.
-
Unplug the terminal block of ArcBlok Event Indicator and put it on the right side of the cable vault. Do not unplug any wires of the terminal block.
-
Remove and retain the 1/4-20 hardware securing the cable vault front cover.
-
Remove and retain the cable vault front cover.
-
Remove and retain the 1/4-20 hardware securing the cable vault rear access panel.
-
Remove and retain the rear access panel from the inside of the cable vault.
DANGERhazard of electric shock, explosion, or arc flash- Replace this cover after section is anchored.
- Do not turn on power if this cover is uninstalled.
- Torque cover hardware to 95–105 lb-in. (10.7–11.9 N•m).
Failure to follow these instructions will result in death or serious injury. -
Install the anchor hardware.
-
Reinstall the rear access panel using 1/4-20 hardware retained in step 4. Torque hardware to 95–105 lb-in. (10.7–11.9 N•m).
-
Reinstall the cable vault front cover using 1/4-20 hardware retained in step 2 and 3.
-
Re-plug the terminal block of ArcBlok Event Indicator removed in step 1.
Securing Structures to Wall—Seismic Hazard* Designated Locations
When specified or required for the application (all seismic hazard areas with Ss in excess of 2.67g), each section must be laterally braced at the top (bracing supplied by others) and connected to the load-bearing path of the building system per detail supplied by engineer of record. Refer to the current International Building Code or NFPA 5000 for location specific values of Ss.
DANGER |
|---|
|
Hazard of electric shock, explosion, or arc flash
Failure to follow these instructions will result in death or serious injury.
|
Remove the lifting angle and fasten each section to the lateral restraint system (supplied by others) using the same attachment points used to secure the lifting angle. Re-use bolts and lock washer supplied with the lifting angle or hardware supplied by others as appropriate. Pay particular attention to the limitation on the depth the bolt can penetrate below the surface of the top plate. The bolts must not penetrate the top plate of the enclosure by more than 0.50 in.
Each section must also be anchored at the base. See the instruction label located on the inside of the bottom horizontal wireway cover.
|
15 (381) Section Dimensions
|
20 (508) Section Dimensions
|
|||||||||||||||||||||||||||||||||||||||||||||||||||
Splice Gaskets for Type 1 Gasketed, Type 1 Sprinkler-resistant, and Type 12 Enclosures
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
Model 6 MCC, Type 12 sections manufactured between 1992 and 2005 included "P" shaped gaskets. When splicing to an existing MCC, refer to P Gasketing. If a P gasket is:
-
Not installed, follow the instructions in Splicing Without P Gasketing.
-
Installed, follow the instructions in Splicing With P Gasketing.
Splicing Without P Gasketing
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
If splicing to an existing MCC, remove the end plate and any gasketing from the existing MCC.
-
Remove the white paper backing from the new gaskets (supplied by Schneider Electric) to expose the adhesive. This adhesive temporarily holds the gaskets in place while the sections are being positioned.
-
Apply flat gaskets to the outside of the front and rear vertical corner channels. The gaskets must not extend above the top of the corner channels.
-
Apply flat gaskets to the outside of the top and bottom tie channels. The gaskets must not extend above the top of the tie channels.
-
Applying thumb pressure, firmly press the gaskets in place from top to bottom. Verify that the gaskets are flat along the entire length.
-
Join sections together following the appropriate steps in Joining Type 1, Type 1 Gasketed, and Type 12 Sections or Joining Type 1 Sprinkler-resistant Sections.
Splicing With P Gasketing
Determine the location of the existing P gasket before splicing. If the P gasket is on the left (see P Gasketing), follow the instructions Splice to Existing Left. If the P gasket is on the right (see P Gasketing), follow the instructions Splice to Existing Right.
Splice to Existing Left
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Remove the end plate and all flat gaskets from the existing MCC. Leave the P gasket on the existing front corner channel in place.
-
Remove the factory installed flat gasket from the front corner channel of the new vertical section.
-
Join sections together following the appropriate steps in Joining Type 1, Type 1 Gasketed, and Type 12 Sections or Joining Type 1 Sprinkler-resistant Sections.
Splice to Existing Right
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Remove the end plate and all flat gaskets from the existing MCC. Leave the P gasket on the existing front corner channel in place.
-
Remove the white paper backing from the new gaskets (supplied by Schneider Electric) to expose the adhesive. This adhesive temporarily holds the gasket in place while the sections are being positioned.
-
Apply a flat gasket to the outside of the rear vertical corner channel of the existing section. The gasket must not extend above the top of the corner channel.
-
Apply flat gaskets to the outside of the top and bottom side channels. The gaskets must not extend above the top of the side channels.
-
Applying thumb pressure, firmly press the gasket in place from top to bottom. The gasket must be flat along the entire length.
-
Join sections together following the appropriate steps in Joining Type 1, Type 1 Gasketed, and Type 12 Sections or Joining Type 1 Sprinkler-resistant Sections.
Joining New Style Type 3R Enclosures to Old Style Type 3R Enclosures
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
This section provides instructions for joining new style Type 3R enclosures manufactured after February 1998 to old style Type 3R enclosures manufactured before February 1998 (the new MCC enclosure is 3 in. (76 mm) shorter than the existing MCC). Instructions for joining to the left or right of an existing MCC enclosure (as viewed from the front) are provided.
For all MCCs in Type 3R enclosures, the parts required for joining the enclosures are included in a kit. This kit is shipped with the MCC order and contains all the parts necessary to join the enclosures.
Joining to the Left Side of an Existing Type 3R MCC Enclosure
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
Remove the end deflector (see Removing the End Deflector) from the leftmost section of the existing MCC and the end deflector, if supplied, from the rightmost section of the MCC being added. Discard both end deflectors. Retain the hardware for installation of new parts.
-
Remove the back plate from the leftmost section of the existing MCC and from the rightmost section of the MCC being added. Retain the back plates and mounting hardware for re-installation.
-
Remove the end plate (see Removing the End Deflector) from the leftmost section of the existing MCC and the end plate, if supplied, from the rightmost section of the MCC being added. Discard both end plates. Retain the hardware for installation of new parts.
-
Remove the insulating barrier (see Removing the Insulating Barrier) from the leftmost section of the existing MCC by punching out the rivets that are holding the barrier in place. Repeat this procedure for the barrier, if supplied, in the rightmost section of the MCC being added. Discard both barriers.
NOTE: Ensure that rivet parts do not fall into the MCC. -
Install the deflector bracket (see Installing the Deflector Bracket) on the right most section of the MCC being added using two 8-32 Phillips head screws included in the kit. The same holes from which the rivets were removed are used to mount the deflector bracket. The top holes of the bracket must align with the holes in the top plate of the enclosure.
-
Attach a left splice bracket (see Installing the Deflector Bracket), 90 in. (2286 mm) long, to the front corner channel of the right most section of the MCC being added using six
1/4–20 screws contained in the kit. The short flange must be flush with the front of the corner channel and that the holes in the bracket line up with the holes in the corner channel. -
Install a left splice bracket (see Installing the Deflector Bracket), 90 in. (2286 mm) long, to the rear corner channel of the right most section of the MCC being added using six
1/4–20 screws contained in the kit. The short flange must be flush with the back of the corner channel and that the holes in the bracket line up with the holes in the corner channel. -
Attach a right splice bracket (see Installing the Deflector Bracket), 94 in. (2388 mm) long, to the left splice bracket installed in step 7 using six 10–32 flat Phillips head screws contained in the kit. The short flange must be behind the flange of the left splice bracket. The right splice bracket extends below the left splice bracket by approximately one in. (25 mm) when properly installed.
-
Install a right splice bracket (see Installing the Deflector Bracket), 94 in. (2388 mm) long, to the left splice bracket installed in step 8 using six 10–32 flat Phillips head screws contained in the kit. The short flange must be in front of the flange of the left splice bracket. The right splice bracket extends below the left splice bracket by approximately one in. (25 mm) when properly installed.
-
Position the structures that are to be spliced. Check that the fronts are flush to ensure proper alignment of all components.
-
Splice sections using the instructions in the Model 5 Instruction Bulletin (8998IM9101) if joining to a Model 5 MCC, or the instructions in Splice Gaskets for Type 1 Gasketed, Type 1 Sprinkler-resistant, and Type 12 Enclosures if joining to a Model 6 MCC.
NOTE: When splicing the horizontal bus between the new and existing MCC sections, remove the splice bars contained in the leftmost section of the existing MCC. Discard the splice bars. Install the horizontal bus splice assembly provided in this kit using the instructions beginning in Splicing Power Bus for Type 1 and Type 12 Enclosures. Use the remaining six 1/4–20 hex head screws provided in the kit to splice the corner channels of the existing MCC to the right splice brackets installed in steps 9 and 10. -
Using the 10–32 hex head screws removed in step 3, re-attach the back plate (see Re-attaching the Back Plates) to the rightmost section of the new MCC. Install the back bracket (see Installing the Deflector Bracket) under the back plate using the left side holes of the back bracket. The notch at the top of the back bracket must be installed toward the new MCC section.
-
Using the 10–32 screws removed in step 3, re-attach the back plate (see Re-attaching the Back Plates) to the right section.
-
Install the splice deflector (see Installing the Deflector Bracket) to the rightmost section of the MCC being added. Use the five 1/4–20 screws supplied in the kit. Both the top plate flanges must be covered.
-
Install five of the 1/4–20 screws removed in step 2 through the splice deflector and into the top plate of the leftmost section of the existing MCC.
-
Using the six 10–32 screws supplied in the kit, secure the right front vertical channel of the new Type 3R enclosure to the left front vertical channel of the existing Type 3R enclosure.
NOTE: Install the screws through the clearance holes in the left front vertical channel of the existing MCC into the right front vertical channel of the new MCC. -
Before energizing the equipment, replace all covers and barriers.
Joining to the Right Side of an Existing Type 3R MCC Enclosure
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Remove the end deflector (see Removing the End Deflector) from the rightmost section of the existing MCC and the end deflector, if supplied, from the leftmost section of the MCC being added. Retain hardware for use in step 12. Discard both end deflectors.
-
Remove the back plate from the rightmost section of the existing MCC and from the leftmost section of the MCC being added. Retain the back plates and mounting hardware for re-installation.
-
Remove the end plate (see Removing the End Deflector) from the rightmost section of the existing MCC and the end plate, if supplied, from the leftmost section of the MCC being added. Discard both end plates.
-
Remove the insulating barrier (see Removing the Insulating Barrier) from the rightmost section of the existing MCC by punching out the rivets that are holding the barrier in place. Repeat this procedure for the barrier, if provided, located in the leftmost section of the MCC being added. Discard both barriers.
NOTE: Ensure that rivet parts do not fall into the MCC. -
Install the left splice bracket (see Installing the Splice Deflector), 94 in. (2388 mm) long, to the right front vertical channel of the existing MCC. Use six 10–32 hex head screws provided in the kit. The long flange of the splice channel mounts to the side of the vertical channel with the short flange near the front of the vertical channel. When properly installed, the bottom of the left splice bracket is flush with the bottom of the vertical channel.
-
Install the right splice bracket (see Installing the Splice Deflector), 90 in. (2286 mm) long, to the left splice bracket installed in step 6 using six 10–32 flat Phillips head screws provided in the kit. The short flange of the right splice bracket must be in front of the flange of the left splice bracket. When properly installed, the left splice bracket extends approximately one in. (25 mm) below the right splice bracket.
-
Position the structures that are to be spliced together. Make sure that the fronts are flush. This ensures proper alignment of all components.
-
Splice sections using the instructions in the Model 5 Instruction Bulletin (8998IM9101) if joining to a Model 5 MCC, or the instructions in Splice Gaskets for Type 1 Gasketed, Type 1 Sprinkler-resistant, and Type 12 Enclosures if joining to a Model 6 MCC. Use the 12 1/4–20 hex head screws provided in the kit to splice the corner channels of the existing MCC to the corner channels of the new MCC.
-
Re-attach the back plate (see Re-attaching the Back Plates) to the leftmost section of the MCC being added by using the 10–32 hex head screws removed in step 4. Install the back bracket (see Installing the Splice Deflector) under the back plate using the right side holes of the back bracket. The notch at the top of the back bracket must be installed toward the new MCC section.
-
Using the hardware removed in step 3, re-attach the back plate (see Re-attaching the Back Plates) to the rightmost section of the existing MCC.
-
Install the splice adaptor (see Installing the Splice Deflector) to the leftmost section of the MCC being added by using five 1/4–20 screws provided in the kit.
-
Position the end deflector, provided in the kit, over the top plate flanges of both sections (see Installing the Splice Deflector) and install with five 1/4–20 screws removed in step 2.
-
Using six 10–32 hex head screws, provided in the kit, secure the right front vertical channel of the MCC being added to the right splice bracket installed in step 7 (see Installing the Splice Deflector).
-
Before energizing the equipment, replace all covers and barriers.
Joining Type 3R Sections
This section provides instructions for joining Type 3R MCC sections (manufactured after February 1998).
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Remove the right section back plate (see Attach the Multi-Section Bracket).
NOTE: Steps 3 and 4 apply only if a new section is being added to an existing MCC line-up. If installing a new line-up, skip to step 5. -
Remove the end deflector cap from the right side of the existing Type 3R section (seeRemove Mid and End-deflector Caps from the Top of the MCC). Also, remove the mid-deflector cap from the section being added to the right.
-
Remove the end closing plate from the right side of the existing section.
-
After placing the structures side-by-side, join them as described in Joining Type 1, Type 1 Gasketed, and Type 12 Sections.
Re-attach the back plate (removed in step 2) to the right section using the additional hardware supplied. Attach the right side to the multi-section bracket (see Attach the Multi-Section Bracket).
-
Install the mid deflector, ensuring both top plate flanges are covered (see Remove Mid and End-deflector Caps from the Top of the MCC).
-
Using the six 10-32 screws supplied, secure the left front vertical channel of the Type 3R extension to the right front vertical channel of the Type 3R extension (see Secure the Vertical Channels).
-
If the lifting angle is to be removed from the sections after installation, replace all hardware in the order shown (see Replace Lifting Angle Hardware).
Joining Type 1 Sprinkler-resistant Sections
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
This section contains instruction for joining MCC sections provided with a sprinkler-resistant enclosure.
-
Join sections together as described in Joining Type 1, Type 1 Gasketed, and Type 12 Sections.
See Removing the Lifting Angles and Hardware for steps 2 and 3.
-
Uninstall and discard the lifting angles (A) by removing the 3/8-in bolts and washers (B) securing them.
-
Remove the 10-32 screws (C) on top of the MCC section closest to the sides of the MCC sections on which the drip hood splice plate will be installed.
See Installing the Drip Hood Splice Plate for steps 4 and 5.
-
Install the drip hood splice plate (D) by reusing the hardware removed in steps 2 and 3.
-
Install the rest of the hardware removed in step 2.
Splicing Power Bus for Type 1 and Type 12 Enclosures
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
To splice the power bus:
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
Remove the horizontal wireway covers and slide the horizontal bus barriers to gain access to the captive splice connectors (see Horizontal Wireway Covers and Bus Barriers Removed). See Appendix A–Removal and Installation of Horizontal Bus Barrier Panels for the steps for removing horizontal bus barriers.
Power Bus Splicing MCCs with Single Bar/Phase Splice Kit (600 A and 800 A, Copper Horizontal Bus, 65,000 A Short Circuit or Less, Shipped after August 2012)
-
Remove all four bolts from the integral splice bar (see Remove Bolts from Single-splice Bar).
-
Move the single splice bar to the left and align the two left holes in the splice bar with the corresponding holes in the horizontal bus on the left section (see Move and Align the Splice Bar to the Bus Holes).
-
Reinstall the four bolts into the horizontal bus on the left and right sections (see Insert Splice Bolts in the Left and Right Sections). Make sure the original conical washers are reinstalled with the concave side facing the horizontal bus (see Place a Conical Washer Under the Bolt Head).
-
Torque all bolts on both ends to 31–32 lb-ft. (41.87–43.22 N•m). (See Torquing the Bolts).
-
Return to step 2 in Splicing Power Bus for Type 1 and Type 12 Enclosures for all phases and for the neutral bus (if supplied). When all splices are complete, go to step 6.
-
Before energizing the equipment, slide the horizontal bus barriers into the closed position and replace all covers.
Power Bus Splicing MCCs with Multiple Bar/Phase Splice Kit
-
Remove the two left bolts. Loosen, but do not remove, the two right bolts on the splice assembly (see Remove the Left Bolts and Loosen the Right Bolts on the Splice Assembly).
NOTE: Do not remove the two right bolts from the splice assemblies. Doing so permits spacers to fall from the splice assembly. If this occurs, re-assemble the splice bars and spacers (if applicable) in the proper order before continuing. -
Slide the splice assembly to the left until the two left holes are in line with the corresponding holes in the horizontal bus on the left section (see Align the Splice and Bus Holes).
-
Reinstall the two left bolts through the splice bars and into the horizontal bus (see Insert the Splice Bolts); make sure the original conical washers are reinstalled with the concave side facing the splice bus (see Place a Conical Washer Under the Bolt Head).
-
Torque all bolts on both ends to 31–32 lb-ft. (41.87–43.22 N•m) (see Torque the Bolts).
-
Return to step 2 in for all phases and for the neutral bus (if supplied). When all splices are complete, go to step 6.
-
Before energizing the equipment, slide the horizontal bus barriers into the closed position and replace all covers.
Splicing Power Bus in Type 3R Enclosures
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
This section describes how to splice the power bus of a Type 3R enclosure (manufactured after February 1998) to the power bus of another Type 3R section. Bus splicing material is not captive if the section is equipped with offset bus. Refer to Splice Offset Horizontal Bus for instructions for splicing offset power bus in Type 3R enclosures.
To splice power bus:
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Remove the horizontal wireway covers and slide the horizontal bus barriers to gain access to the captive splice connectors (see Wireway Covers Removed and Horizontal Bus Barriers Open for the steps for removing horizontal bus barriers.
NOTE: On the integral splice bar assembly, located on the left side of each phase bus, the number of splice bars used on each phase is one greater than the number of main horizontal bus bars. The rear-most splice bar includes captive nuts. -
Remove the two left bolts from each splice assembly. Then loosen, but do not remove, the two right bolts of each splice assembly (see Loosen Bolts). If the bus has optional 85,000 A bus bracing supplied (see 85,000 A Bracing Option), also loosen the center nut of each splice assembly.
NOTE: Do not remove the two right bolts or the center bolt (if applicable) from the splice assemblies. Doing so permits spacers to fall from the splice assembly. If this occurs, re-assemble the splice bars and spacers (if applicable) in the proper order before continuing. -
Slide the splice assembly to the left until the two left holes are in line with the corresponding holes in the horizontal bus in the left section (see Slide the Splice Assembly to the Left).
-
Re-install the two left bolts through the splice assembly and into the horizontal bus (see Insert the Splice Bolts). Make sure the original conical washers are reinstalled with the concave side facing the splice bus (see Place a Conical Washer Under the Bolt Head).
-
Torque the splice connection bolts at horizontal bus connections to 31–32 lb-ft. (41.87–43.22 N•m). Torque 85 kA support nuts (if applicable) to 68–72 lb-ft. (92.2–97.6 N•m) (see Torque All Bolts).
-
Repeat steps 2–6 for all phases and the neutral bus (if supplied).
Before energizing the equipment, replace all covers and barriers.
Power Bus Splicing of 2500 A Bus with 100,000 A Short Circuit Rating
This section provides instructions for splicing the power bus of one section with 2500 A bus braced for 100,000 A to the power bus of another section of the same type. Splicing material is captive on the integral splice assembly unless the section is equipped with an offset bus.
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
To splice the power bus:
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Remove the horizontal wireway covers and slide the horizontal bus barriers to gain access to the captive splice connectors (see Wireway Covers Removed and Horizontal Bus Barriers Open). See Appendix A–Removal and Installation of Horizontal Bus Barrier Panels for the steps for removing horizontal bus barriers.
NOTE: On the integral splice bar assembly, located on the left side of each phase bus, the number of splice bars used on each phase is one greater than the number of main horizontal bus bars. Splice bars are held captive on the horizontal bus by a splice bar carrier assembly. The rear of the carrier assembly includes captive nuts (see Wireway Covers Removed and Horizontal Bus Barriers Open). -
Remove all four bolts from each splice assembly (see Remove the Bolts from the Splice Assembly).
-
Slide the splice assembly to the left until the two left holes are in line with the corresponding holes in the horizontal bus on the left section (see Align the Splice and Bus Holes).
-
Reinstall all four bolts through the splice assembly and into the horizontal bus (see Insert the Splice Bolts). Make sure the original conical washers are reinstalled with the concave side facing the splice bus (see Place a Conical Washer Under the Bolt Head).
-
Torque all bolts on both ends to 31–32 lb-ft. (41.87–43.22 N•m) (see Torque All Bolts).
-
Repeat steps 2–6 for all phases and the neutral bus (if supplied).
-
Before energizing the equipment, replace all covers and barriers.
Splicing Offset for 3000/3200 A Horizontal Bus (Left Side of Structure Only)
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
-
In all structures with an offset or 3000/3200 A horizontal bus, splice bars are provided as a kit. This kit is packaged in a carton and shipped inside the structure. The kit contains all splice bars and mounting hardware necessary for horizontal bus splicing.
-
Use the splice kit only if splicing is to be done on the left (while facing the structure). If the splice is not on the left, remove the kit before energizing and retain it for future expansion. If a structure is to be spliced to another structure on the right, follow splicing instructions provided for that structure application.
-
On the integral splice bar assembly, located on the left side of each phase bus, the number of splice bars used on each phase is one greater than the number of main horizontal bus bars. The rear-most splice bar includes captive nuts.
To splice a horizontal bus on the left side of the structure:
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Join sections together following the appropriate steps beginning at Locating the MCC and continuing through Joining Type 3R Sections. This provides proper alignment of the horizontal bus.
-
Position the rear splice bar (the bar with captive nuts (see Splice Offset Horizontal Bus) against the back face of the rear horizontal bus bar.
-
Install a plain splice bar between each lamination of horizontal bus; install the last bar against the front face of the horizontal bus (see Splice Offset Horizontal Bus).
-
Align the four mounting holes in the splice bus and the horizontal bus.
-
Re-install the two left bolts through the splice assembly and into the horizontal bus. Make sure the original conical washers are re-installed with the concave side facing the splice bus (see Place a Conical Washer Under the Bolt Head).
-
For 600–2500 A main bus splices, torque the bolts to 31-32 lb-ft. (41.87-43.22 N•m). For 3000/3200 A main bus splices, torque the bolts to 70 lb-ft. (94.92 N•m). Torque the center nut on 85 kA braced, 3R splice bar assemblies to 70 lb-ft. (94.92 N•m).
-
Repeat steps 2–6 for each of the three horizontal bus phases.
-
Before energizing the equipment, replace all covers and barriers.
Ground Bus Splicing for Type 1, Type 12, and Type 3R
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
To splice the ground bus:
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Remove ground bar bolts from the right and left sections (see Ground Splice Bar as Shipped).
-
Slide the ground splice bar into the right section, aligning the mounting holes (see Ground Bar Bolt Replaced).
-
Replace the ground bar bolts (see Ground Bar Bolt Replaced) in the right and left sections. Torque both bolts to 60–75 lb-in. (6.75–8.44 N•m).
-
Replace all covers and barriers and close all doors.
Ground Bus Splicing for Bottom-feed ArcBlok 1200 Main Sections
DANGER |
|---|
|
hazard of electric shock, explosion, or arc flash
Failure to follow these instructions will result in death or serious injury.
|
To splice the ground bus:
-
Remove the cable vault front cover to access the ground bus assembly.
-
Remove the ground bar bolts in the cable vault and in the adjacent MCC section.
-
Slide the ground splice bar into the right section, aligning the mounting holes.
-
Replace the ground bar bolts (see Ground Bar Bolt Replaced) in the right and left sections.
-
Torque the ground bar bolts to 60–75 lb-in. (6.75–8.44 N•m).
-
Place the ground closing plates into position to seal the cable vault (see Location of Ground Closing Plates).
-
Replace all covers and barriers and close all doors.
Ground Bus Splicing for Bottom-feed ArcBlok 2500 Main Sections
-
Remove the cable vault front cover to access the ground bus assembly.
-
For splicing to left adjacent section (if applicable):
-
Remove the bolts for the ground splice bar located on the left-side of the cable vault and the ground splice bar located on the right-side of the left adjacent section. (see Removing Bolts for Ground Splice Bar).
-
Discard the ground splice bar on the right side of the left adjacent section.
-
Loosen the ground closing plate hardware on the left side of the cable vault and slide the closing plate forward to reveal open slot in cable vault.
-
Slide the ground splice bar located inside the cable vault to the left so that it aligns with the mounting hole of the ground bus in the left adjacent section.
-
Re-install one ground splice bar bolt in both sections, (see Re-install Ground Splice Bar Bolt).
-
Torque the ground splice bar bolts to 60–75 lb-in. (6.75–8.44 N•m).
-
Slide the closing plate against the ground splice bar and tighten the ground closing plate hardware.
-
-
For splicing to right adjacent section (if applicable):
-
Remove the bolts for the ground splice bar located on the right-side of the cable vault.
-
If applicable, remove the bolts for the ground splice bar located on the left-side of the right adjacent section and discard the ground splice bar.
-
Loosen the ground closing plate hardware on the right side of the cable vault and slide the closing plate forward to reveal open slot in cable vault.
-
Slide the ground splice bar located inside the cable vault to the right so that it aligns with the mounting hole of the ground bus in the right adjacent section.
-
Re-install one ground splice bar bolt in both sections.
-
Torque the ground splice bar bolts to 60–75 lb-in. (6.75–8.44 N•m).
-
Slide the closing plate against the ground splice bar and tighten the ground closing plate hardware.
-
-
Replace all covers and barriers and close all doors.
Conductor Entry
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
Conduit entry space is provided at the top and bottom of the MCC structure. The top plates (and closing plates in bottom, if present) are removable for convenience in wiring and cutting conduit openings). A hinged door or cover allows access to the main lug, main circuit breaker, or main switch compartment. In some cases, the horizontal wireway cover must be removed.
Determine the conduit requirements per local electrical codes to protect connections on top of the MCC. For Type 1 Sprinkler-Resistant, Type 12, and Type 3R enclosures, protect the top of the MCC from the ingress of water.
Pull boxes are available if additional wiring space is required.
Cable connection torque values are listed in Connection Torque Values for Main Lug Compartments and Connection Torque Values for Main and Branch Feeders.
Conductor Entry for Line-side Isolation Cable Vaults with ArcBlok 1200
Conduit entry into main breaker sections equipped with ArcBlok and line-side Isolation cable vaults requires:
-
Use of an 18 in. pull box for top-feed entry with a removable top plate.
-
Line-side isolation cable vaults require removal of enclosure covers and barriers prior to removing the cable vault front cover and ArcBlok lug cover.
Conductor Entry for Line-Side Isolation Cable Vaults with ArcBlok 2500
-
Arcblok 2500 is only available in bottom-feed MCC units.
Wire Connections with ArcBlok 2500
-
Locate and terminate all conduit in the MCC enclosure in the “available conduit area” designated on the equipment drawing.
-
The conduit area is available towards the front of the section inside the cable vault.
-
Remove and retain the 10–32 size hardware securing the equipment breaker cover.
-
Remove and retain the breaker cover.
-
Remove and retain 10–32 size hardware securing the equipment lower front cover.
-
Remove and retain the equipment lower front cover.
-
Unplug the terminal block of the ArcBlok Event Indicator and put it on the right side of the cable vault. Do not disconnect wires from the terminal block.
-
Remove and retain 1/4–20 size hardware securing the cable vault front cover.
-
Remove and retain the cable vault front cover.
NOTICE damage to event indicatorDo not damage ArcBlok event indicator while installing or uninstalling the cable vault front cover. Call Schneider Electric Services if the event indicator is damaged.Failure to follow these instructions can result in equipment damage.
DANGERhazard of electric shock, explosion, or arc flash- Replace conduit closure plate after creating the conduit holes.
- Do not turn on power if conduit closure plate is not installed.
Failure to follow these instructions will result in death or serious injury.-
Remove and retain the conduit closure plate for reuse. The customer must create any holes necessary for conduit entering the bottom of the MCC. After creating the holes, reinstall the conduit closure plate (see Bottom-fed ArcBlok Main Bottom Conduit Closure Plate).
-
Pull the cables inside the cable vault and terminate them on the ArcBlok lugs shown in Lug Cross Section Showing Hole Placement. Torque all wire-binding screws to 842 lb–in. (95 N•m).
NOTICE damage to phase barriersDo not apply excessive force to the phase barriers during cable installation. Damage to the phase barriers can occur. Call Schneider Electric Services if the phase barriers are damaged.Failure to follow these instructions can result in equipment damage.-
Use a proper insulation stripping tool to strip a length of insulation from the end of the cable sufficient to fit into the full length of the lug barrel. Be careful not to nick or ring the strands.
-
Thoroughly clean aluminum cable contact surfaces with a wire brush, or scrub them with an abrasive cloth to remove oxides and foreign matter.
-
Immediately apply an acceptable joint compound to the bare aluminum surfaces.
-
Install the rear cables into the rear three-hole lug. Wire strip length: 3.875 in. (98 mm).
-
Install the cables into the front six-hole lug. Wire strip length: 2.50 in. (64mm) for the rear three holes. Wire strip length: 1.375 in. (35 mm) for the front three holes.
-
Screw any unused wire binding screws in completely. Screw in all wire binding screws without cables installed so they are not in the way of the Thermal Interface Module (TIM) (see TIM Sleeve).
-
-
Cable entry into the cable vault must use conduit connections installed on the conduit closure plate. The conduits must be sealed using duct seal putty.
-
Install the Thermal Interface Module (TIM):
-
Verify TIM mating surfaces and lugs are clean and undamaged. Clean with a dry, lint-free rag.
-
Install one TIM per phase and neutral using 1/4-20 size captive screws as shown in TIM Sleeve. Slide the plastic sleeve around each TIM against the top of the phase barriers. Sleeve must be flush with the top of the phase barriers. Torque all six TIM screws in a star pattern to 60 lb-in. (6.8 Nm).
NOTE: The TIM mounting screws are not completely removable.
-
-
Install the ArcBlok module front cover assembly to enclose the ArcBlok module using 1/4-20 size screws provided as shown in ArcBlok Front Cover Installation. Install the cover by aligning the four alignment pins in the cover with the holes in the module side plates. Fasten five screws on the top row and another five in the middle row of the front cover. Use the remaining five screws for the bottom row while installing the cable vault front cover as mentioned in step 13. Torque all ten screws on the front cover to 60 lb-in. (6.8 Nm).
NOTICE damage to tape on thermal interface module (TIM)Do not damage the tape on the TIM during installation of the ArcBlok front cover during this step. Call Schneider Electric Services if cover assembly is damaged.Failure to follow these instructions can result in equipment damage.NOTICE damage to arcblok module front cover assemblyDo not apply excessive force to the ArcBlok module front cover assembly during installation. Call Schneider Electric Services if cover assembly is damaged.Failure to follow these instructions can result in equipment damage. -
Install one heatsink per phase and neutral on the front surface of the TIM using 1/4-20 size captive screws as shown in ArcBlok Heat Sink Installation. Torque all six screws on the heatsink in a star pattern to 60 lb-in. (6.8 N•m).
CAUTIONRisk of burns from hot surfaces or heatsinksApply appropriate personal protective equipment (PPE) and follow safe electrical work practices when working near heatsinks. See NFPA 70E, NOM-029-STPS or CSA Z462 or local equivalent.Failure to follow these instructions can result in injury or equipment damage. -
Install the thermal sensor (if used) as labeled per phase in the thermal sensor mounting clip available underneath the heatsink with the temperature probe towards the base of the heat sink as shown in Thermal Sensor Installation.
NOTICE damage to sensor spring loaded probeDo not damage or let the sensor spring loaded probe tip out of place during the installation to avoid temperature data discrepancy. Call Schneider Electric Services if the sensor is damaged.Failure to follow these instructions can result in equipment damage. -
Perform substeps:
-
Reinstall the cable vault front cover using (15) 1/4-20 size screws retained in step 5 (see Reinstall Cable Vault Front Cover).
-
Locate (5) 1/4-20, x 1 in. long screws from ArcBlok Module kit and install at the top edge of the cable vault front cover to fasten the ArcBlok front cover. Torque all screws on cable vault front cover to 60 lb-in. (6•8 Nm) (see Reinstall Cable Vault Front Cover).
DANGERhazard of electric shock, explosion, or arc flash- Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E or CSAZ462.
- This equipment must be installed and serviced by qualified electrical personnel.
- Read instruction bulletin and become familiar with the equipment before installing, operating, servicing, or troubleshooting the equipment.
- Turn off all power supplying this equipment before working inside this cable vault.
- Always use a properly rated voltage sensing device to confirm power is off.
- Do not turn on power without this cover installed. Incident Energy levels greater than 1.2 cal/cm2 are present if cover is uninstalled.
- Replace all devices, doors, and covers before turning on power to this equipment.
- Apply torque to cable vault hardware to 60 lb-in. (6.8 N•m).
Failure to follow these instructions will result in death or serious injury.
-
-
Re-plug the terminal block of the ArcBlok Event Indicator removed in step 4.
-
Make sure the ArcBlok Event Indicator plunger is pushed back as shown in ArcBlok Event Indicator.
-
Reinstall the equipment front covers and breaker cover using 1/4–20 size hardware retained in steps 1 and 2.
-
Incoming Cable Lacing Instructions–ArcBlok 1200 Line-side Isolation Cable Vault
All cables must be laced and secured prior to installing the cable vault front cover.
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
-
For lacing material, select a sisal or hemp rope with a minimum of 2500 pounds of pull strength (625 pounds working load). Apply tape to any frayed end of the rope before lacing cables.
-
Lace the cables from all phases together in one bundle with a continuous length of rope. The ArcBlok lug cover must be in place and bolted down prior to lacing (ArcBlok Lug Cover in Place Prior to Lacing). Make sure interphase barriers are inserted in the grooves of the ArcBlok lug cover.
Lacing requires two sets of looping groups: an entry loop set and a second looping group nearer to the ArcBlok.
-
Attach one end of the rope to the cable bundle.
-
After attaching the rope to the cables, make a loop in the rope and pull the loop around the cable bundle from behind. Pull the loose end of the rope through the loop (see First Cable Lacing Loop).
-
Continue to pull the rope through the loop until the rope is tight. Continue to make a loop group of no more than two loops, wrapping the cable bundle four times.
-
Create the second loop group by pulling the rope around the cable bundle. Make a loop by pulling the loose end under the rope. Continue to pull the rope through the loop until it is tight around the cable bundle. Repeat the procedure until the cable bundle has no more than two loops, wrapping the cable bundle four times. The spacing between the upper and lower loop groups should be no less than four in. (102 mm) (see Upper and Lower Cable Lacing Groups).
-
Make sure the cable bundles do not disengage the interphase barriers from the grooves of the ArcBlok lug cover (see ArcBlok Interphase Barriers and ArcBlok Interphase Barriers and Lug Cover Grooves).
-
After the entire cable bundle has been laced, tie the ends of the ropes securely to the looping groups, then cut and tape the ends to help prevent fraying. Make sure the rope ends are not obstructing the cable vault front cover, overlapping seals, or rear panel damper.
After the entire cable bundle has been laced, tie the ends of the ropes securely to the looping groups, then cut and tape the ends to help prevent fraying. Make sure the rope ends are not obstructing the cable vault front cover, overlapping seals, or rear panel damper. -
While keeping the ArcBlok lug cover in place, remove all cover hardware.
NOTE: Make sure the interphase barriers remain inserted into the grooves of the ArcBlok lug cover (see ArcBlok Interphase Barriers and Lug Cover Grooves). -
Place the cable vault front cover on top of the ArcBlok lug cover.
-
Install 3/8–16 Keps nuts and torque them to 20–23 lb-ft. (27–31 N•m).
Incoming Cable Lacing Instructions–ArcBlok 2500 Line-side Isolation Cable Vault
| NOTICE |
|---|
|
Risk of loose cables
Lace and secure all cables. Cable restraint is required
on the line-side of the ArcBlok section.
Failure to follow these instructions can result in equipment damage.
|
Cable restraint is required on the line-side of the ArcBlok section. All cables must be laced and secured prior to installing the cable vault front cover.
-
Wrap cables using 1/2 in. (13 mm) diameter sisal rope or equivalent.
-
Lace the cables from all phases together in one bundle with a continuous length of rope.
-
Lacing requires two sets of looping groups: an entry loop group and a second loop group nearer to the ArcBlok.
-
Attach one end of the rope to on of the cables about 10 in. (254 mm) from the floor.
-
After attaching the rope, make a loop in it and pull the loop around the entire cable bundle from behind. Pull the loose end of the rope through the loop and continue to pull it until the rope is tight.
-
Make a second loop and pass behind the cables using the same procedure. Put the loose end of the rope through the loop and pull the loop tight. Repeat this step one additional time.
-
Start the second (upper) loop group by first pulling the rope around the cable bundle, then repeat the procedure described in step 6 for the upper loop group. The spacing between the upper and lower loop groups must be no more than 5 1/2 in. (139 mm). See Upper and Lower Loop Group Spacing.
-
After the entire cable bundle has been laced, tie the end of the rope securely to the looping groups, then cut and tape the end to prevent fraying. Make sure the rope is not obstructing the cable vault front cover, fuse disconnect switch wiring, or ArcBlok Event Indicator plunger.
Vent Hood Installation
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
This section contains instructions for installing a vent hood over the top plate vents on an MCC.
-
Do not install the vent hood until the MCC is in its final location.
-
Retain all hardware.
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Remove the 3/8 in. (9.525 mm) bolts, washers, and the lifting angle (see Remove the Hardware).
-
Remove the two 10-32 screws that secure the vent hood and closing plate to the top of the cabinet (see Reposition and Attach the Vent Hood).
-
Once the vent hood is removed, secure the top closing plate by reinstalling the 10-32 screws removed in step 3 (see Reposition and Attach the Vent Hood).
-
Position the vent hood on the top of the cabinet as shown.
-
Secure the vent hood in place using the two 3/8 in. (9.525 mm) bolts and washers removed in step 2. Torque the bolts to 28–33 lb-in. (3.164–3.729 N•m).
Pull Box Installation
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
This section contains instructions for installing pull boxes on low voltage MCCs. Pull boxes are either 12 or 18 in. (304.8 or 457.2 mm) high and mount on the top of the MCC.
-
Do not install the pull box until the MCC is in its final location.
-
Retain all hardware.
Standard Low Voltage MCC Pull Box
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm power is off.
-
Remove the 3/8 in. (9.525 mm) bolts, washers, and the lifting angle (see Remove the Hardware).
-
Remove the 10-32 screws that secure the top closing plate to the top of the cabinet (see Remove the Hardware).
-
Remove the top closing plate from the structure.
-
Remove the front panel from the pull box. Position the pull box on top of the cabinet as shown in Install the Pull Box.
-
Install the two 3/8 in. (9.525 mm) bolts and washers that were removed in step 2. Place them through the pull box lower side channels and into the top of the cabinet. Torque the bolts to 28–33 lb-in. (3.164–3.729 N•m).
-
Re-install the pull box front panel removed in step 5 and the top closing plate removed in step 4 (see Install the Pull Box).
Vented Low Voltage MCC Pull Box
-
Follow the same instructions for standard pull box installation (see Standard Low Voltage MCC Pull Box), except remove and discard the top closing plate from the MCC section. The vented pull box comes with a solid top plate.
Line-side Isolation, Low Voltage MCC Pull Box
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm power is off.
-
Remove the 3/8 in. (9.5 mm) bolts, washers, and the lifting angle (see Remove the Hardware).
-
Remove the 10–32 in. (4.8 mm) screws and vented hood (see Remove the Hardware).
-
Remove the 10–32 in (4.8 mm) screws and horizontal cross bus front cover (see Remove the Hardware).
-
Remove the pull box front cover for installation access (see Install the Pull Box).
-
Install 1/2 in. (12.7 mm) bolts and washers from inside the cabinet through the top closing plate and to the front pull box channel. Complete the connection with a washer and nut on the inside of the pull box.
-
Install two 1 /4 in (6.4 mm) screws on the pull box rear channel and to the top closing plate.
-
Install the two 3/8 in. (9.5 mm) bolts and washers that were removed in step 2. Place them through the lower side flanges of the vented hood, and into the top of the cabinet. Torque the bolts to 28–33 lb-in. (3.164–3.729 N•m).
-
Re-install the pull box front cover removed in step 5 (see Install the Pull Box) and the top horizontal wireway cover removed in step 4.
Sprinkler-resistant Low Voltage MCC Pull Box
Refer to Removing the Lifting Angles and Hardware for the following steps.
-
Uninstall and discard the lifting angles (A) by removing the 3/8 in. bolts and washers (B) securing them.
-
Remove and discard the top closing plate (C) from the MCC section by removing the 10-32 screws (D) securing it.
NOTE: For main sections with ArcBlok 1200 technology, do not remove the top closing plate (C) since the pull box is installed over it. Remove only the 10-32 screws (D).Refer to Installing the Pull Box.
-
Remove the front panel (E) from the pull box (F) by removing the 10-32 screws (G) securing it.
-
Position the pull box on top of the MCC section frame (for standard sections) or on top of the closing plate (for main sections with ArcBlok 1200 technology).
NOTE: The overhang located at the top of the pull box must be facing the front of the MCC section. -
Install the two 3/8 in. bolts and washers (B) removed in step 1. Place them through the pull box lower side channels and into the top of the MCC section.
-
Re-install the pull box front panel removed in step 3.
-
Remove the two 10-32 screws (H) located on the side of the pull box near the bottom.
-
Remove the two 10-32 screws, 3/8 in. bolt, and washer located on the top closing plate of the adjacent MCC section (I).
-
Install the pull box splice angle (J) re-using the hardware removed in steps 7 and 8.
Load and Control Wiring
The top and bottom horizontal wireways and the vertical wireway are convenient areas to run incoming line, load, and control wires (see Wiring in the Top Horizontal Wireway). Openings between sections permit wire to pass from one section into the next for interwiring.
Control and power wires are routed to each unit via the vertical wireway. When supplied, grommeted wire ports must be opened to route wire to the unit. The H-shaped cut pattern is pre-scored for easy opening. Using a small knife, cut through the center tabs and complete the H-shaped slice (see Vertical Wireway Grommet). When cutting, be sure not to damage the wires located near the grommet.
Pull-apart control terminals (see Pull-apart Type Terminal Blocks) are mounted on a 35 mm DIN rail located adjacent to the wiring ports toward the front of the unit. Terminate field control wiring on the removable portion of the block.
Crimp Lug Cable Assembly for Cabled Disconnect Unit Installation
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
-
Turn off all power supplying this equipment before working on or inside the equipment and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Access the horizontal bus in the motor control center (see Typical Cabled Disconnect Unit).
-
Remove the horizontal bus mounting nuts and washers (item E) from the horizontal bus assembly (see Typical Horizontal Bus Assembly).
-
Insert the loom bolts (item B) through the rear of the lug pad (item C).
-
Using the mounting nuts and washers from step 3, attach the lug pad to the horizontal bus mounting bolts (item A).
-
Torque the horizontal bus mounting nuts to 820–840 lb-in. (93–95 N•m).
-
Route the cable to the circuit breaker or fuse disconnect unit (see Typical Cabled Disconnect Unit); trim cable length as required.
-
Using the lug pad nuts and washers (item F), attach the crimp lug cable assembly (item D) to the loom bolts on the lug pad.
-
Torque the lug pad nuts to 820–840 lb-in. (93–95 N•m).
Cable Connection Torque Values
Connection Torque Values for Main Lug Compartments and Connection Torque Values for Main and Branch Feeders provide main disconnect and branch feeder torque values, which apply to both aluminum and copper conductors.
Connection Torque Values for Main Lug Compartments*
|
Socket Size Across Flat |
Torque |
|---|---|
|
3/8 in. |
375 lb-in. (42.4 N•m) |
|
1/2 in. |
500 lb-in. (55.6 N•m) for 800–1200 A, bottom main lug compartments |
|
600 lb-in. (67.8 N•m) for all others |
Connection Torque Values for Main and Branch Feeders
| Frame Size | Ampere Rating | Torque |
|---|---|---|
| B | 15–125 A | 44 lb-in (5.0 N•m) for #14 - #8Q80 lb-in. (9.0 N•m) for #6 - #3/0 |
| H | 15–30 A | 50 lb-in. (5.6 N•m) |
| 35–150 A | 120 lb-in. (13.6 N•m) | |
| J | 150–250 A | 225 lb-in. (25.4 N•m) |
| FA | 15–30 A | 35 lb-in. (3.9 N•m) |
| 35–100 A | 80 lb-in. (9.0 N•m) | |
| FC | 20–30 A | 35 lb-in. (4.0 N•m) |
| 40–100 A | 65 lb-in. (7.3 N•m) | |
| KA | 70–250 A | 250 lb-in. (28.2 N•m) |
| KC | 110–250 A | 250 lb-in. (28.2 N•m) |
| LA/LH | 125–400 A | 200 lb-in. (22.6 N•m) |
| LC/LI/LE/LX/LXI | 300–600 A | 300 lb-in. (33.9 N•m) |
| LG/LH/LL/LR | 300–600 A | 442 lb-in. (50 N•m) |
| MA/MH/ME/MX | 200–400 A | 300 lb-in. (33.9 N•m) |
| 450–1000 A | 300 lb-in. (33.9 N•m) | |
| NT | 400–1200 A | 600 lb-in. (67.8 N•m) |
| NW | 400–3200 A | 600 lb-in. (67.8 N•m) |
| PA/PH/PE/PX | 800–2000 A | 600 lb-in. (67.8 N•m) |
| MJ/MG | 300–800 A | 450 lb-in. (50.8 N•m) |
| PJ/PK/PG/PL | 250–1200 A | 450 lb-in. (50.8 N•m) |
| RJ/RK/RG/RL | 600–2500 A | 500 lb-in. (56.5 N•m) |
Component Instructional Information
Component manuals for devices such as adjustable frequency drive controllers, solid state reduced voltage starters, and programmable logic controllers are available from your local Schneider Electric representative, or can be downloaded from the Schneider Electric Download Center: se.com/us/en/download/ . See the Schneider Electric Literature Lists.
Modifying Fuse Clip Locations
DANGER |
|---|
|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
Install 30 and 60 A fuse bases for the proper fuse size and class and maximum voltage in Size 1 and 2 starter units. The base pan of the disconnect switch has five sets of mounting holes for this purpose. The lower fuse base is installed in the proper mounting holes at the factory (see Size 1 and 2 Fuse Clip Locations). Additional clips and bases may be required if changing fuse class.
Turn off all power supplying this equipment and follow lockout/tagout procedures before working on or inside equipment. Always use a properly rated voltage sensing device to confirm the power is off.































_0000696812.png)
_0000696831.png)




