Plug-In Units
Class 5615, 5630 / Refer to Catalog 5600CT9101
Fusible Plug-In Units, Class R Fuse Kits, and Hooksticks
Fusible Plug-In Units[1]
Ampere Rating |
Type of Connection |
240 Vac 3-Pole, 3 Fuse + G |
120/208 Vac, (240 Vac Max.) 4-Pole, 3 Fuse + G |
600 Vac 3-Pole, 3 Fuse + G |
277/480 Vac, (600 Vac Max.) 4-Pole, 3 Fuse + G |
---|---|---|---|---|---|
Catalog No. |
Catalog No. |
Catalog No. |
Catalog No. |
||
30 |
Plug-in |
||||
60 |
|||||
100 |
|||||
200 |
|||||
200[2] |
|||||
400 |
|||||
600 |
|||||
800 |
Bolt-on |
— |
— |
PTQ36080G( ) [4] |
PTQ46080G() [4] |
1000 |
— |
— |
PTQ36100G( ) [4] |
PTQ46100G( ) [4] |
|
1200 |
— |
— |
PTQ36120G( ) [4] |
PTQ46120G( ) [4] |
|
Class J Fuses – Provisions for installing Class J fuses are included in 30 through 600 A fusible devices. Conversion to Class J fuse spacing requires relocating the load side fuse base assembly from standard Class H fuse location to an alternate position in the enclosure. |
A |
C |
|
B |
||
A–High Ampere Plug-In Connection B – High Ampere Bolt-On Connection C – Low Ampere Plug-In Connection |
There are three different types of plug-in connections:
-
High Ampere Bolt-On Connection (catalog numbers that begin with “PT”)—bolted “joint pack” type connection
-
Used on I-Line™/I-Line II busway amperages 800 A aluminum and greater.
-
Used on I-Line™/I-Line II busway amperages 1000 A copper and greater.
-
-
High Ampere Plug-In Connection (catalog numbers that begin with “PB”)—
individual bolted jaws for connections -
Low Ampere Plug-In Connection (catalog numbers that begin with “P,” except for “PB” and “PT”)—spring pressure jaws for connection
Class R Fuse Kits[5]
Switch Size (A) |
Voltage Rating |
Kit [5] Catalog No. |
---|---|---|
30 |
250 V [6] 600 V [6] |
|
60 |
250 V [6] 600 V [6] |
|
100 200 |
All |
|
400 600 |
All |
|
Class R Fuse Kits when installed reject all but class R fuses. |
Surge Protective Device Plug-In Units
All Busway SPD Plug-In Units include as standard:
-
Individually Fused Modules
-
Circuit Breaker Disconnect
-
Cover Mounted Diagnostic Panel
-
EMI/RFI Filter
-
Audible Alarm with Test/Disable/Enable
Surge Capacity
System Voltage |
160,000 Amperes Per Phase |
240,000 Amperes Per Phase |
---|---|---|
Catalog Number[1] |
Catalog Number[1] |
|
208Y/120 Vac, 3Ø4W/Grd. |
||
240Y/120 Vac, 3Ø4W/Grd. |
||
480Y/277 Vac, 3Ø4W/Grd. |
||
600Y/347 Vac, 3Ø4W/Grd. |
Options
Description |
When Required Add Suffix to Catalog Number |
---|---|
Surge Counter and Dry Contacts |
— |
Remote Monitor with Dry Contacts |
M |