NHA2768503-07

Demand parameters

Demand is a measure of average consumption (typically power or current) over a fixed programmed time interval.

Power / current demand setup parameters

Parameter Values Description
Method
  • Thermal: Ther

  • Timed Sliding Block: t.Sb

  • Timed Block: t.b

  • Timed Rolling Block: t.rb

  • Command Sync Block: CS.b

  • Command Sync Rolling Block: CS.rb

  • Clock Sync Block: CL.b

  • Clock Sync Rolling Block: Cl.rb

NOTE: Command sync and clock sync methods are applicable for meters with RS-485 communication only.

Select the appropriate demand calculation method for your needs.

Interval 1 – 60

Set the demand interval, in minutes.

Subinterval (update time) 1 – 60

Applies only to rolling block methods.

Define how many subintervals the demand interval should be equally divided into.

Clock Sync Time 00:00 – 23:59

Applies only to clock sync methods (these synchronize the demand interval to the meter’s internal clock).

Define what time of day you want to synchronize the demand.