Example calculations
A balanced 3-phase Wye system uses 480:120 volt VTs and 120:5 amp CTs. The signals at the secondary side are 119 volts line-to-neutral and 5.31 amps, with a power factor of 0.85. The desired pulse output frequency is 20 Hz (20 pulses per second).
-
At full load (120% of nominal current = 6 A) and power factor (PF = 1), calculate the maximum total output power (Pmax):
-
Check the maximum pulse frequency against the limits for the LED and pulse outputs:
-
26.6 Hz ≤ LED maximum pulse frequency (35 Hz)
-
26.6 Hz > pulse output maximum pulse frequency (20 Hz)
NOTE: The maximum pulse frequency is within the limits for LED energy pulsing. However, the maximum pulse frequency is greater than the limits for pulse output energy pulsing. Pulse output frequencies greater than 20 Hz will saturate the pulse output and cause it to stop pulsing. Therefore in this example, you can only use the LED for energy pulsing. -
Adjustments to allow energy pulsing at the pulse outputs
If you want to use the pulse output, you must reduce the output pulse frequency so it is within the limits.
Using the values
from the above example, the maximum pulse constant for the pulse output
is:
-
Set the pulse constant (K) to a value below Kmax, for example, 300 pulses/kWh. Calculate the new maximum output pulse frequency at Pmax:
-
Check the new maximum pulse frequency against the limits for the LED and pulse outputs:
-
17.1 Hz ≤ LED maximum pulse frequency (35 Hz)
-
17.1 Hz ≤ pulse output maximum frequency (20 Hz)
-
-
Set the new pulse constant (K) on your meter.