Specifications
| NOTICE |
|---|
|
hazard of equipment damage
Refer to the UPS installation manual for detailed specifications
for the UPS system.
Failure to follow these instructions can result in equipment damage.
|
Classic Battery Cabinet Specifications
DANGER |
|---|
|
hazard of electric shock, explosion or arc flash
The classic battery cabinet must only be used with the
Galaxy VS UPS, the Galaxy VL UPS, or the Easy UPS 3-Phase Modular.
Failure to follow these instructions will result in death or serious injury.
|
| Commercial reference | Battery type | Number of battery blocks |
|---|---|---|
| GVSCBC7C | XP12V1800* or XP12-240 | 36 |
| GVSCBC7D | XP12-150 | 40 |
| GVSCBC7E | XP12-150 | 46 |
| GVSCBC10A2 | XP12-240 | 48 |
| GVSCBC10B2 | XP12-350 | 40 |
Trip Settings
Trip settings must be controlled during installation. Set the trip settings according to the relevant table below.
GVSCBC7C
| UPS rating | 20-50 kW | 60 kW | 80 kW | 100 kW | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Power factor |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
| Breaker type | C25S3D + C253MG250D | NA | ||||||||||
| Ir setting | 175 | 200 | 250 | 250 | ||||||||
| Im setting | 1250 | |||||||||||
GVSCBC7D
GVSCBC7E
| UPS rating | 20-50 kW | 60 kW | 80 kW | ||||||
|---|---|---|---|---|---|---|---|---|---|
| Power factor |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
| Breaker type | C25S3D + C253MG200D | ||||||||
| Ir setting | 140 | 160 | 200 | ||||||
| Im setting | 1000 | ||||||||
GVSCBC10A2
| UPS rating | 20-60 kW | 80 kW | 100 kW | 120 kW | 150 kW | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Power factor |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
| Breaker type | C25S3D + C253MG250D | NA | |||||||||||||
| Ir setting | 175 | 175 | 175 | 200 | 200 | 225 | 225 | 225 | 250 | 250 | 250 | ||||
| Im setting | 1250 | ||||||||||||||
| UPS rating | 200 kW | 250 kW | 300 kW | 350 kW | 400 kW | 450 kW | 500 kW |
|---|---|---|---|---|---|---|---|
| Power factor | 1 | ||||||
| Breaker type | C25S3D + C253MG250D | ||||||
| Number of classic battery cabinets | 2 x GVSCBC10A2 | 2 x GVSCBC10A2 | 3 x GVSCBC10A2 | 3 x GVSCBC10A2 | 4 x GVSCBC10A2 | 4 x GVSCBC10A2 | 4 x GVSCBC10A2 |
| Ir setting | 225 | 250 | 225 | 250 | 225 | 250 | 250 |
| Im setting | 1250 | ||||||
GVSCBC10B2
| UPS rating | 20-80 kW | 100 kW | 120 kW | 150 kW | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Power factor |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
| Breaker type | C40S3TM320D | |||||||||||
| Ir setting | 224 | 224 | 256 | 288 | 288 | 320 | 320 | |||||
| Im setting | 1500 | |||||||||||
| UPS rating | 200 kW | 250 kW | 300 kW | 350 kW | 400 kW | 450 kW | 500 kW |
|---|---|---|---|---|---|---|---|
| Power factor | 1 | ||||||
| Breaker type | C40S3TM320D | ||||||
| Number of classic battery cabinets | 2 x GVSCBC10B2 | 2 x GVSCBC10B2 | 3 x GVSCBC10B2 | 3 x GVSCBC10B2 | 4 x GVSCBC10B2 | 4 x GVSCBC10B2 | 4 x GVSCBC10B2 |
| Ir setting | 288 | 320 | 288 | 320 | 288 | 320 | 320 |
| Im setting | 1500 | ||||||
Recommended Cable Sizes
DANGER |
|---|
|
hazard of electric shock, explosion, or arc flash
All wiring must comply with all applicable national and/or
electrical codes. The maximum allowable cable size is 95 mm2.
Failure to follow these instructions will result in death or serious injury.
|
Cable sizes in this manual are based on table B.52.3 (52-C2) of IEC 60364-5-52 with the following assertions:
-
90 °C conductors
-
An ambient temperature of 30 °C
-
Use of copper conductors
-
Installation method C
Protective Earth (PE) cables are sized in accordance with table 54.3 of IEC 60364-4-54, Article 543.
If the ambient temperature is greater than 30 °C, larger conductors are to be selected in accordance with the correction factors of the IEC.
GVSCBC7C
| UPS rating | 20-60 kW | 80 kW | 100 kW | ||||||
|---|---|---|---|---|---|---|---|---|---|
|
Power factor |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
| DC+/DC- (mm2) | 50 | 70 | 70 | NA | |||||
| DC PE (mm2) | 25 | 35 | 35 | ||||||
GVSCBC7D
| UPS rating | 20-30 kW | 40-50 kW | 60 kW | ||||||
|---|---|---|---|---|---|---|---|---|---|
|
Power factor |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
| DC+/DC- (mm2) | 16 | 35 | 35 | ||||||
| DC PE (mm2) | 10 | 16 | 16 | ||||||
GVSCBC7E
| UPS rating | 20-60 kW | 80 kW | ||||
|---|---|---|---|---|---|---|
|
Power factor |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
| DC+/DC- (mm2) | 35 | 50 | ||||
| DC PE (mm2) | 16 | 25 | ||||
GVSCBC10A2
| UPS rating | 20-80 kW | 100-120 kW | 150 kW | ||||||
|---|---|---|---|---|---|---|---|---|---|
|
Power factor |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
| DC+/DC- (mm2) | 50 | 70 | 70 | NA | |||||
| DC PE (mm2) | 25 | 35 | 35 | ||||||
| UPS rating | 200 kW | 250 kW | 300 kW | 350 kW | 400 kW | 450 kW | 500 kW |
|---|---|---|---|---|---|---|---|
|
Power factor |
1 | ||||||
| Number of classic battery cabinets | 2 x GVSCBC10A2 | 2 x GVSCBC10A2 | 3 x GVSCBC10A2 | 3 x GVSCBC10A2 | 4 x GVSCBC10A2 | 4 x GVSCBC10A2 | 4 x GVSCBC10A2 |
| DC+/DC- (mm2) | 70 | ||||||
| DC PE (mm2) | 35 | ||||||
GVSCBC10B2
| UPS rating | 20-60 kW | 80-100 kW | 120-150 kW | ||||||
|---|---|---|---|---|---|---|---|---|---|
|
Power factor |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
0.8 |
0.9 |
1 |
| DC+/DC- (mm2) | 50 | 70 | 95 | ||||||
| DC PE (mm2) | 25 | 35 | 50 | ||||||
| UPS rating | 200 kW | 250 kW | 300 kW | 350 kW | 400 kW | 450 kW | 500 kW |
|---|---|---|---|---|---|---|---|
|
Power factor |
1 | ||||||
| Number of classic battery cabinets | 2 x GVSCBC10B2 | 2 x GVSCBC10B2 | 3 x GVSCBC10B2 | 3 x GVSCBC10B2 | 4 x GVSCBC10B2 | 4 x GVSCBC10B2 | 4 x GVSCBC10B2 |
| DC+/DC- (mm2) | 70 | 95 | |||||
| DC PE (mm2) | 35 | 50 | |||||
Torque Specifications
| Bolt size | Torque |
|---|---|
| M4 | 1.7 Nm |
| M5 | 2.2 Nm |
| M6 | 5 Nm |
| M8 | 17.5 Nm |
| M10 | 30 Nm |
| M12 | 50 Nm |
Clearance
Classic Battery Cabinet Shipping Weights and Dimensions
| Commercial reference | Weight kg | Height mm | Width mm | Depth mm |
|---|---|---|---|---|
| GVSCBC7C | 920 | 1980 | 815 | 970 |
| GVSCBC7D | 589 | 1980 | 815 | 970 |
| GVSCBC7E | 810 | 1980 | 815 | 970 |
| GVSCBC10A2 | 1300 | 1980 | 1130 | 970 |
| GVSCBC10B2 | 1532 | 1980 | 1130 | 970 |
Classic Battery Cabinet Weights and Dimensions
| Commercial reference | Weight kg | Height mm | Width mm | Depth mm |
|---|---|---|---|---|
| GVSCBC7C | 900 | 1900 | 710 | 845 |
| GVSCBC7D | 569 | 1900 | 710 | 845 |
| GVSCBC7E | 790 | 1900 | 710 | 845 |
| GVSCBC10A2 | 1102 | 1900 | 1010 | 845 |
| GVSCBC10B2 | 1368 | 1900 | 1010 | 845 |
Environment
| Operating | Storage | |
|---|---|---|
| Temperature | 0 °C to 40 °C | -15 °C to 40 °C |
| Relative humidity | 0-95% non-condensing | 10-80% non-condensing |
| Elevation | 0-1000 m | |
| Protection class | IP20 | |
| Color | RAL 9003, gloss level 85% | |
Compliance
| Safety | IEC 62040-1: 2017, Edition 2.0, Uninterruptible Power Systems (UPS) - Part 1: Safety requirements |
| Performance | IEC 62040-3: 2011-03, 2nd edition Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the performance and test requirements |
| Environmental | IEC 62040-4: 2013-04, 1st edition Uninterruptible Power Systems (UPS) - Part 4: Environmental aspects – Requirements and reporting |
| Markings | CE |
| Earthing system | TN-C, TN-S, TT |
| Overvoltage category | OVCIII |
| Protective class | I |
| Pollution degree | 2 |
DANGER