Specifications
NOTICE |
---|
hazard of equipment damage
Refer to the UPS installation manual for detailed specifications
for the UPS system.
Failure to follow these instructions can result in equipment damage.
|
Battery Breaker Specifications
DANGER |
---|
hazard of electric shock, explosion or arc flash
This product must only be used with the Galaxy VS UPS,
the Galaxy VL UPS, the Galaxy VXL UPS, the Easy UPS 3-Phase Modular,
or the Easy UPS 3M Advanced.
Failure to follow these instructions will result in death or serious injury.
|
Battery breaker |
C63S3TM600D |
Battery type | VRLA, lead-acid, Lithium-ion |
Maximum battery short-circuit level (kA) | 35 |
Minimum short-circuit current to trip circuit breaker (A) | 1600 |
Applicable Products
GVBBB630EL-1CB | GVBBB630EL-2CB | GVBBB630EL-3CB | |
---|---|---|---|
Galaxy VS | Yes | – | – |
Galaxy VL | Yes | Yes | Yes |
Galaxy VXL | Yes | Yes | Yes |
Easy UPS 3-Phase Modular | Yes | Yes | – |
Easy UPS 3M Advanced | Yes | Yes | – |
Trip Settings
Battery Breaker Box with One Breaker (GVBBB630EL-1CB)
UPS rating | Minimum configuration | Maximum configuration | Battery blocks | ||||
---|---|---|---|---|---|---|---|
Minimum number of battery breaker boxes | Max. battery backup time (minutes) | Breaker setting | Maximum number of battery breaker boxes | Max. battery backup time (minutes) | Breaker setting | ||
500 kW | 3xGVBBB630EL-1CB | Any | 480 | 8xGVBBB630EL-1CB | Any | 420 | 40-48 |
600 kW | 3xGVBBB630EL-1CB | <30 | 600 | 8xGVBBB630EL-1CB | Any | 420 | 40-48 |
625 kW | 3xGVBBB630EL-1CB | <30 | 600 | 8xGVBBB630EL-1CB | Any | 420 | 40-48 |
750 kW | 4xGVBBB630EL-1CB | <60 | 540 | 8xGVBBB630EL-1CB | Any | 420 | 40-48 |
875 kW | 4xGVBBB630EL-1CB | <30 | 600 | 8xGVBBB630EL-1CB | Any | 420 | 40-48 |
1000 kW | 7xGVBBB630EL-1CB | Any | 420 | 8xGVBBB630EL-1CB | Any | 420 | 40-48 |
1125 kW | 8xGVBBB630EL-1CB | Any | 420 | 8xGVBBB630EL-1CB | Any | 420 | 40-48 |
1250 kW | 8xGVBBB630EL-1CB | Any | 420 | 8xGVBBB630EL-1CB | Any | 420 | 40-48 |
Battery Breaker Box with Two Breakers (GVBBB630EL-2CB)
UPS rating | Max. battery backup time (minutes) | Battery blocks | Battery strings total | Battery breaker 1 | Battery breaker 2 | ||
---|---|---|---|---|---|---|---|
Battery strings | Ir/Im settings | Battery strings | Ir/Im settings | ||||
250 kW | Any |
40-48 |
2 |
1 |
420/1500 |
1 |
420/1500 |
250 kW |
40-48 |
3 |
2 |
420/1500 |
1 |
420/1500 |
|
250 kW |
40-48 |
4 |
2 |
420/1500 |
2 |
420/1500 |
|
250 kW |
40-48 |
5 |
3 |
420/1500 |
2 |
420/1500 |
|
250 kW |
40-48 |
6 |
3 |
420/1500 |
3 |
420/1500 |
|
250 kW |
40-48 |
7 |
4 |
420/1500 |
3 |
420/1500 |
|
250 kW |
40-48 |
8 |
4 |
420/1500 |
4 |
420/1500 |
|
300 kW | Any |
40-48 |
2 |
1 |
420/1500 |
1 |
420/1500 |
300 kW | <60 |
40-48 |
3 |
2 |
480/1500 |
1 |
420/1500 |
300 kW | Any |
40-48 |
4 |
2 |
420/1500 |
2 |
420/1500 |
300 kW |
40-48 |
5 |
3 |
480/1500 |
2 |
420/1500 |
|
300 kW |
40-48 |
6 |
3 |
420/1500 |
3 |
420/1500 |
|
300 kW |
40-48 |
7 |
4 |
420/1500 |
3 |
420/1500 |
|
300 kW |
40-48 |
8 |
4 |
420/1500 |
4 |
420/1500 |
|
350 kW | Any |
40-48 |
2 |
1 |
420/1500 |
1 |
420/1500 |
350 kW |
<30 |
40-48 |
3 |
2 |
600/1500 |
1 |
420/1500 |
350 kW | Any |
40-48 |
4 |
2 |
420/1500 |
2 |
420/1500 |
350 kW |
<60 |
40-48 |
5 |
3 |
540/1500 |
2 |
420/1500 |
350 kW | Any |
40-48 |
6 |
3 |
420/1500 |
3 |
420/1500 |
350 kW |
<60 |
40-48 |
7 |
4 |
480/1500 |
3 |
420/1500 |
350 kW | Any |
40-48 |
8 |
4 |
420/1500 |
4 |
420/1500 |
400 kW | <30 |
40-48 |
2 |
1 |
480/1500 |
1 |
480/1500 |
400 kW | <15 |
40-48 |
3 |
2 |
540/1500 |
1 |
420/1500 |
400 kW | <30 |
40-48 |
4 |
2 |
480/1500 |
2 |
480/1500 |
400 kW |
40-48 |
5 |
3 |
540/1500 |
2 |
420/1500 |
|
400 kW |
40-48 |
6 |
3 |
480/1500 |
3 |
480/1500 |
|
400 kW |
40-48 |
7 |
4 |
540/1500 |
3 |
420/1500 |
|
400 kW |
40-48 |
8 |
4 |
480/1500 |
4 |
480/1500 |
|
450 kW |
<30 |
41-48 |
2 |
1 |
540/1500 |
1 |
540/1500 |
450 kW |
<30 |
41-48 |
4 |
2 |
540/1500 |
2 |
540/1500 |
450 kW |
<15 |
41-48 |
5 |
3 |
600/1500 |
2 |
420/1500 |
450 kW |
<30 |
41-48 |
6 |
3 |
540/1500 |
3 |
540/1500 |
450 kW |
<15 |
41-48 |
7 |
4 |
600/1500 |
3 |
480/1500 |
450 kW |
<30 |
41-48 |
8 |
4 |
540/1500 |
4 |
540/1500 |
500 kW | <30 |
40-48 |
2 |
1 |
600/1500 |
1 |
600/1500 |
500 kW |
40-48 |
4 |
2 |
600/1500 |
2 |
600/1500 |
|
500 kW |
40-48 |
6 |
3 |
600/1500 |
3 |
600/1500 |
|
500 kW |
40-48 |
8 |
4 |
600/1500 |
4 |
600/1500 |
UPS rating | Minimum configuration | Maximum configuration | Battery blocks | ||||
---|---|---|---|---|---|---|---|
Minimum number of battery breaker boxes | Max. battery backup time (minutes) | Breaker setting | Maximum number of battery breaker boxes | Max. battery backup time (minutes) | Breaker setting | ||
500 kW | 1xGVBBB630EL-2CB | <30 |
600 |
4xGVBBB630EL-2CB | Any |
420 |
40-48 |
600 kW | 2xGVBBB630EL-2CB | Any |
420 |
4xGVBBB630EL-2CB | Any |
420 |
40-48 |
625 kW | 2xGVBBB630EL-2CB | Any |
480 |
4xGVBBB630EL-2CB | Any |
420 |
40-48 |
750 kW | 2xGVBBB630EL-2CB | Any |
540 |
4xGVBBB630EL-2CB | Any |
420 |
40-48 |
875 kW | 2xGVBBB630EL-2CB | <60 |
600 |
4xGVBBB630EL-2CB | Any |
420 |
40-48 |
1000 kW | 2xGVBBB630EL-2CB | <30 |
600 |
4xGVBBB630EL-2CB | Any |
420 |
40-48 |
1125 kW | 2xGVBBB630EL-2CB | <15 |
600 |
4xGVBBB630EL-2CB | Any |
420 |
40-48 |
1250 kW | 4xGVBBB630EL-2CB | Any |
480 |
4xGVBBB630EL-2CB | Any |
480 |
40-48 |
Battery Breaker Box with Three Breakers (GVBBB630EL-3CB)
UPS rating | Max. battery backup time (minutes) | Battery blocks | Battery strings total | Battery breaker 1 | Battery breaker 2 | Battery breaker 3 | |||
---|---|---|---|---|---|---|---|---|---|
Battery strings | Ir/Im settings | Battery strings | Ir/Im settings | Battery strings | Ir/Im settings | ||||
400 kW | Any |
40-48 |
3 |
1 |
420/1500 |
1 |
420/1500 |
1 |
420/1500 |
400 kW | >60 |
40-48 |
4 |
2 |
600/1500 |
1 |
600/1500 |
1 |
600/1500 |
400 kW | Any |
40-48 |
5 |
2 |
480/1500 |
2 |
480/1500 |
1 |
480/1500 |
400 kW |
40-48 |
6 |
2 |
420/1500 |
2 |
420/1500 |
2 |
420/1500 |
|
400 kW |
40-48 |
7 |
3 |
540/1500 |
2 |
540/1500 |
2 |
540/1500 |
|
400 kW |
40-48 |
8 |
3 |
480/1500 |
3 |
480/1500 |
2 |
480/1500 |
|
400 kW |
40-48 |
9 |
3 |
420/1500 |
3 |
420/1500 |
3 |
420/1500 |
|
400 kW |
40-48 |
10 |
4 |
480/1500 |
3 |
480/1500 |
3 |
480/1500 |
|
400 kW |
40-48 |
11 |
4 |
480/1500 |
4 |
480/1500 |
3 |
480/1500 |
|
400 kW |
40-48 |
12 |
4 |
420/1500 |
4 |
420/1500 |
4 |
420/1500 |
|
450 kW | Any |
40-48 |
3 |
1 |
480/1500 |
1 |
480/1500 |
1 |
480/1500 |
450 kW |
<60 |
40-48 |
4 |
2 |
600/1500 |
1 |
600/1500 |
1 |
600/1500 |
450 kW | Any |
40-48 |
5 |
2 |
480/1500 |
2 |
480/1500 |
1 |
480/1500 |
450 kW |
40-48 |
6 |
2 |
600/1500 |
2 |
600/1500 |
2 |
600/1500 |
|
450 kW |
40-48 |
7 |
3 |
540/1500 |
2 |
540/1500 |
2 |
540/1500 |
|
450 kW |
40-48 |
8 |
3 |
480/1500 |
3 |
480/1500 |
2 |
480/1500 |
|
450 kW |
40-48 |
9 |
3 |
600/1500 |
3 |
600/1500 |
3 |
600/1500 |
|
450 kW |
40-48 |
10 |
4 |
540/1500 |
3 |
540/1500 |
3 |
540/1500 |
|
450 kW |
40-48 |
11 |
4 |
480/1500 |
4 |
480/1500 |
3 |
480/1500 |
|
450 kW |
40-48 |
12 |
4 |
600/1500 |
4 |
600/1500 |
4 |
600/1500 |
|
500 kW | Any |
40-48 |
3 |
1 |
420/1500 |
1 |
420/1500 |
1 |
420/1500 |
500 kW | <30 |
40-48 |
4 |
2 |
600/1500 |
1 |
420/1500 |
1 |
420/1500 |
500 kW | <60 |
40-48 |
5 |
2 |
420/1500 |
2 |
480/1500 |
1 |
420/1500 |
500 kW | Any |
40-48 |
6 |
2 |
420/1500 |
2 |
420/1500 |
2 |
420/1500 |
500 kW | <60 |
40-48 |
7 |
3 |
540/1500 |
2 |
420/1500 |
2 |
420/1500 |
500 kW | Any |
40-48 |
8 |
3 |
480/1500 |
3 |
480/1500 |
2 |
420/1500 |
500 kW |
40-48 |
9 |
3 |
420/1500 |
3 |
420/1500 |
3 |
420/1500 |
|
500 kW | <60 |
40-48 |
10 |
4 |
480/1500 |
3 |
420/1500 |
3 |
420/1500 |
500 kW | Any |
40-48 |
11 |
4 |
480/1500 |
4 |
480/1500 |
3 |
420/1500 |
500 kW |
40-48 |
12 |
4 |
420/1500 |
4 |
420/1500 |
4 |
420/1500 |
UPS rating | Minimum configuration | Maximum configuration | Battery blocks | ||||
---|---|---|---|---|---|---|---|
Minimum number of battery breaker boxes | Max. battery backup time (minutes) | Breaker setting | Maximum number of battery breaker boxes | Max. battery backup time (minutes) | Breaker setting | ||
500 kW | 1xGVBBB630EL-3CB | Any | 480 | 2xGVBBB630EL-3CB | Any | 420 | 40-48 |
600 kW | 1xGVBBB630EL-3CB | <60 | 600 | 2xGVBBB630EL-3CB | Any | 420 | 40-48 |
625 kW | 1xGVBBB630EL-3CB | <60 | 600 | 2xGVBBB630EL-3CB | Any | 420 | 40-48 |
750 kW | 1xGVBBB630EL-3CB | <30 | 600 | 2xGVBBB630EL-3CB | Any | 420 | 40-48 |
875 kW | 1xGVBBB630EL-3CB | <15 | 600 | 2xGVBBB630EL-3CB | Any | 420 | 40-48 |
1000 kW | 2xGVBBB630EL-3CB | Any | 480 | 2xGVBBB630EL-3CB | Any | 480 | 40-48 |
1125 kW | 2xGVBBB630EL-3CB | Any | 540 | 2xGVBBB630EL-3CB | Any | 540 | 40-48 |
1250 kW | 2xGVBBB630EL-3CB | <60 | 600 | 2xGVBBB630EL-3CB | <60 | 600 | 40-48 |
Recommended Cable Sizes
DANGER |
---|
hazard of electric shock, explosion, or arc flash
All wiring must comply with all applicable national and/or
electrical codes. The maximum allowable cable size is 120 mm2 for GVBBB630EL-1CB. The maximum allowable cable size is 240 mm2 for GVBBB630EL-2CB and GVBBB630EL-3CB.
Failure to follow these instructions will result in death or serious injury.
|
Refer to the UPS installation manual for recommended cable sizes.
Torque Specifications
Bolt size | Torque |
---|---|
M4 | 1.7 Nm |
M5 | 2.2 Nm |
M6 | 5 Nm |
M8 | 17.5 Nm |
M10 | 30 Nm |
M12 | 50 Nm |
Battery Breaker Box Shipping Weights and Dimensions
Commercial reference | Weight kg | Height mm* | Width mm | Depth mm |
---|---|---|---|---|
GVBBB630EL-1CB | 40 | 560 | 800 | 1200 |
GVBBB630EL-2CB | 72 | 560 | 1000 | 1200 |
GVBBB630EL-3CB | 82 | 560 | 1000 | 1200 |
Battery Breaker Box Weights and Dimensions
Commercial reference | Weight kg | Height mm | Width mm | Depth mm |
---|---|---|---|---|
GVBBB630EL-1CB | 35 | 800 | 500 | 280 |
GVBBB630EL-2CB | 66 | 1000 | 750 | 280 |
GVBBB630EL-3CB | 76 | 1000 | 750 | 280 |
Environment
Operating | Storage | |
---|---|---|
Temperature | 0 °C to 40 °C | -25 °C to 55 °C |
Relative humidity | 0-95% non-condensing | 0-95% non-condensing |
Color |
RAL 9003, gloss level 85% |
|
Protection class | IP20 |
Compliance
Safety | IEC 62040-1:2017,
Edition 2.0, Uninterruptible power systems (UPS) – Part 1:
Safety requirements IEC 62040-1: 2008-6, 1st edition, Uninterruptible Power Systems (UPS) – Part 1: General and safety requirements for UPS IEC 62040-1:2013-01, 1st edition amendment 1 |
Markings | CE, RCM, EAC, WEEE |
Transportation | IEC TR 60721-4-2, 2M2 |
Seismic | ICC-ES AC156, Level 1 |
Pollution degree | 2 |
Overvoltage category | III |