990-91377-001

Derating Due to Load Power Factor

0.7 leading to 0.7 lagging without derating.

UPS rating UPS output
Lagging Leading
PF=1 PF=0.7 PF=0.8 PF=0.9 PF=0.9 PF=0.8 PF=0.7
200 kW/kVA 200 kVA / 140 kW 200 kVA / 160 kW 200 kVA / 180 kW 200 kVA / 180 kW 200 kVA / 160 kW 200 kVA / 140 kW
250 kW/kVA 250 kVA / 175 kW 250 kVA / 200 kW 250 kVA / 225 kW 250 kVA / 225 kW 250 kVA / 200 kW 250 kVA / 175 kW
300 kW/kVA 300 kVA / 210 kW 300 kVA / 240 kW 300 kVA / 270 kW 300 kVA / 270 kW 300 kVA / 240 kW 300 kVA / 210 kW
350 kW/kVA 350 kVA / 245 kW 350 kVA / 280 kW 350 kVA / 315 kW 350 kVA / 315 kW 350 kVA / 280 kW 350 kVA / 245 kW
400 kW/kVA 400 kVA / 280 kW 400 kVA / 320 kW 400 kVA / 360 kW 400 kVA / 360 kW 400 kVA / 320 kW 400 kVA / 280 kW
450 kW/kVA 450 kVA / 315 kW 450 kVA / 360 kW 450 kVA / 405 kW 450 kVA / 405 kW 450 kVA / 360 kW 450 kVA / 315 kW
500 kW/kVA 500 kVA / 350 kW 500 kVA / 400 kW 500 kVA / 450 kW 500 kVA / 450 kW 500 kVA / 400 kW 500 kVA / 350 kW