Compliance
UPS | Lithium-ion battery cabinet | |
---|---|---|
Safety | IEC
62040-1: 2017, Edition 2.0, Uninterruptible Power Systems (UPS) -
Part 1: Safety requirements UL 1778 5th edition |
IEC 62619:2017 Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety requirements for secondary lithium cells and batteries, for use in industrial applications IEC 62477-1:2012+A11:2014 Safety requirements for power electronic converter systems and equipment Part 1: General UL 1973:2022 Batteries for Use in Stationary, Vehicle Auxiliary and Light Electric Rail Applications UL 9540A:2019 Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems |
EMC/EMI/RFI | IEC
62040-2: 2016, 3rd edition Uninterruptible Power Systems (UPS) -
Part 2: Electromagnetic compatibility (EMC) requirements C2 FCC Part 15 Subpart B, Class A IEEE C62.41-1991 Location Category B1, IEEE Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits |
IEC 62040-2:2016 Uninterruptible Power Systems (UPS) - Part 2: Electromagnetic compatibility (EMC) requirements C2 FCC Part 15, Radio Frequency Devices, class A |
Performance |
Performance in accordance with: IEC 62040-3: 2021, 3rd edition Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the performance and test requirements. |
– |
Environmental |
IEC 60068-2-1:2007 Environmental testing – Part 2-1: Tests – Test A: Cold IEC 60068-2-2:2007 Environmental testing – Part 2-2: Tests – Test B: Dry heat IEC 60068-2-78:2012 Environmental testing – Part 2-78: Tests – Test Cab: Damp heat, steady state |
|
Transportation | IEC 60721-4-2 Level 2M2 |
IEC60068-2-27:2008 Environmental testing – Part 2-27: Tests – Test Ea and guidance: Shock IEC60068-2-31:2008 Environmental testing – Part 2-31: Tests – Test Ec: Rough handling shocks, primarily for equipment-type specimens IEC60068-2-64:2008 Environmental testing – Part 2-64: Tests – Test Fh: Vibration, broadband random and guidance |
Seismic | ICC-ES AC 156 (2015); OSHPD Pre-approved; Sds=1.45 g for z/h=1 and Sds=2.00 g for z/h=0; Ip=1.5 |
OSHPD, CBC 2019, SDS=2.0g (z/h = 1); 2.5g (z/h = 0) |
Earthing system | TN-C, TN-S, TT, IT | |
Overvoltage category | This
UPS is OVCII compliant. If the UPS is installed in an environment with an OVC rating higher than II, an SPD (surge protection device) must be installed upstream of the UPS to reduce the overvoltage category to OVCII. |
II |
Protective class | I | 1 |
Pollution degree | 2 | 2 |