Power frequency default measurements
EN50160 Frq/Mg data recorder
| Register label | Source module type | Description | 
|---|---|---|
| 
                            Freq N  | 
                        
                            Signal limit evaluation  | 
                        
                            Number of valid intervals  | 
                     
| 
                            Freq N1  | 
                        
                            Signal limit evaluation  | 
                        
                            Number of intervals where the frequency is within ± 1% of nominal  | 
                     
| 
                            Freq N2  | 
                        
                            Signal limit evaluation  | 
                        
                            Number of intervals where the frequency is within +4% and -6% of nominal.  | 
                     
| 
                            Freq N invld  | 
                        
                            Signal limit evaluation  | 
                        
                            Number of invalid intervals  | 
                     
Parameter data is recorded every 10 minutes in the EN50160 Prm-f/V data recorder.
EN50160 Prm-f/V data recorder
| Register label | Description | 
|---|---|
| 
                            PQ Freq mean  | 
                        
                            10-minute mean  | 
                     
| 
                            PQ Freq low  | 
                        
                            minimum one-cycle value over 10 minutes  | 
                     
| 
                            PQ Freq high  | 
                        
                            maximum one-cycle value over 10 minutes  |