Harmonic voltage default measurements

Harmonic voltage default measurements are stored in the EN50160 Hrm Vlt data recorder.

EN50160 Hrm Vlt data recorder

Register label Source module type Description

V1-Hrm N

Harmonics evaluation

Number of valid intervals on phase 1

V1-Hrm N invld

Harmonics evaluation

Number of invalid intervals on phase 1

V1-Hrm N1

Harmonics evaluation

Number of intervals in which one or more of the individual harmonic levels exceed the harmonic voltage criteria on phase 1

V1-Hrm N2

Harmonics evaluation

Number of intervals in which the THD value for phase 1 exceeds 8%

V2-Hrm N

Harmonics evaluation

Number of valid intervals on phase 2

V2-Hrm N invld

Harmonics evaluation

Number of invalid intervals on phase 2

V2-Hrm N1

Harmonics evaluation

Number of intervals in which one or more of the individual harmonic levels exceed the harmonic voltage criteria on phase 2

V2-Hrm N2

Harmonics evaluation

Number of intervals in which the THD value for phase 2 exceeds 8%

V3-Hrm N

Harmonics evaluation

Number of valid intervals on phase 3

V3-Hrm N invld

Harmonics evaluation

Number of invalid intervals on phase 3

V3-Hrm N1

Harmonics evaluation

Number of intervals in which one or more of the individual harmonic levels exceed the harmonic voltage criteria on phase 3

V3-Hrm N2

Harmonics evaluation

Number of intervals in which the THD value for phase 3 exceeds 8%

Parameter data is stored every 10 minutes in the EN50160 PrmHrm1-2 data recorders.

EN50160 PrmHrm1-2 data recorders

Register label Description

PQ V1 THD 10m

Phase 1 voltage total harmonic distribution (THD) 10 minute mean

PQ V1 THD mn

Phase 1 voltage minimum 3-second THD value over 10 minutes

PQ V1 THD mx

Phase 1 voltage maximum 3-second THD value over 10 minutes

PQ V1 TOHD 10m

Phase 1 voltage total odd harmonics distribution (TOHD) 10 minute mean

PQ V1 TOHD mn

Phase 1 voltage minimum 3-second TOHD value over 10 minutes

PQ V1 TOHD mx

Phase 1 voltage maximum 3-second TOHD value over 10 minutes

PQ V1 TEHD 10m

Phase 1 voltage total even harmonics distribution (TEHD) 10 minute mean

PQ V1 TEHD mn

Phase 1 voltage minimum 3-second TEHD value over 10 minutes

PQ V1 TEHD mx

Phase 1 voltage maximum 3-second TEHD value over 10 minutes

PQ V2 THD 10m

Phase 2 voltage total harmonic distribution (THD) 10 minute mean

PQ V2 THD mn

Phase 2 voltage minimum 3-second THD value over 10 minutes

PQ V2 THD mx

Phase 2 voltage maximum 3-second THD value over 10 minutes

PQ V2 TOHD 10m

Phase 2 voltage total odd harmonics distribution (TOHD) 10 minute mean

PQ V2 TOHD mn

Phase 2 voltage minimum 3-second TOHD value over 10 minutes

PQ V2 TOHD mx

Phase 2 voltage maximum 3-second TOHD value over 10 minutes

PQ V2 TEHD 10m

Phase 2 voltage total even harmonics distribution (TEHD) 10 minute mean

PQ V2 TEHD mn

Phase 2 voltage minimum 3-second TEHD value over 10 minutes

PQ V2 TEHD mx

Phase 2 voltage maximum 3-second TEHD value over 10 minutes

PQ V3 THD 10m

Phase 3 voltage total harmonic distribution (THD) 10 minute mean

PQ V3 THD mn

Phase 3 voltage minimum 3-second THD value over 10 minutes

PQ V3 THD mx

Phase 3 voltage maximum 3-second THD value over 10 minutes

PQ V3 TOHD 10m

Phase 3 voltage total odd harmonics distribution (TOHD) 10 minute mean

PQ V3 TOHD mn

Phase 3 voltage minimum 3-second TOHD value over 10 minutes

PQ V3 TOHD mx

Phase 3 voltage maximum 3-second TOHD value over 10 minutes

PQ V3 TEHD 10m

Phase 3 voltage total even harmonics distribution (TEHD) 10 minute mean

PQ V3 TEHD mn

Phase 3 voltage minimum 3-second TEHD value over 10 minutes

PQ V3 TEHD mx

Phase 3 voltage maximum 3-second TEHD value over 10 minutes