Rendement 400 V
400 V UPS
20 kW met N+1 vermogensmodule | Normaal bedrijf | ECO-modus | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
93,7% |
94,0% |
93,6% |
95,4% |
95,4% |
95,5% |
50% belasting |
95,7% |
95,9% |
95,7% |
97,6% |
97,5% |
97,6% |
75% belasting |
96,4% |
96,6% |
96,4% |
98,2% |
98,2% |
98,2% |
100% belasting |
96,7% |
96,9% |
96,7% |
98,5% |
98,5% |
98,5% |
20 kW met N+1 vermogensmodule | eConversion | Batterijbedrijf | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
95,4% |
95,3% |
95,3% |
93,2% |
93,1% |
93,0% |
50% belasting |
97,5% |
97,5% |
97,5% |
95,4% |
95,3% |
95,3% |
75% belasting |
98,2% |
98,2% |
98,2% |
96,2% |
96,1% |
96,0% |
100% belasting |
98,5% |
98,5% |
98,5% |
96,6% |
96,5% |
96,4% |
30 kW met N+1 vermogensmodule | Normaal bedrijf | ECO-modus | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
92,5% |
92,5% |
92,4% |
96,3% |
96,3% |
96,3% |
50% belasting |
95,1% |
95,0% |
94,9% |
97,9% |
98,0% |
98,0% |
75% belasting |
95,9% |
95,9% |
95,8% |
98,5% |
98,5% |
98,5% |
100% belasting |
96,4% |
96,4% |
96,4% |
98,8% |
98,8% |
98,8% |
30 kW met N+1 vermogensmodule | eConversion | Batterijbedrijf | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
94,8% |
94,5% |
94,4% |
93,4% |
93,2% |
93,2% |
50% belasting |
97,1% |
97,1% |
97,1% |
95,5% |
95,3% |
95,2% |
75% belasting |
98,0% |
97,9% |
97,9% |
96,2% |
96,0% |
96,0% |
100% belasting |
98,4% |
98,4% |
98,4% |
96,5% |
96,4% |
96,3% |
40 kW met N+1 vermogensmodule | Normaal bedrijf | ECO-modus | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
93,9% |
93,8% |
93,7% |
97,2% |
97,2% |
97,2% |
50% belasting |
95,8% |
95,7% |
95,7% |
98,4% |
98,4% |
98,4% |
75% belasting |
96,4% |
96,4% |
96,4% |
98,8% |
98,8% |
98,8% |
100% belasting |
96,7% |
96,7% |
96,7% |
99,0% |
99,0% |
99,0% |
40 kW met N+1 vermogensmodule | eConversion | Batterijbedrijf | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
96,1% |
95,9% |
95,9% |
94,5% |
94,2% |
94,2% |
50% belasting |
97,8% |
97,8% |
97,7% |
96,0% |
95,8% |
95,8% |
75% belasting |
98,4% |
98,4% |
98,4% |
96,5% |
96,4% |
96,3% |
100% belasting |
98,7% |
98,7% |
98,7% |
96,7% |
96,6% |
96,6% |
50 kW met N+1 vermogensmodule | Normaal bedrijf | ECO-modus | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
94,7% |
94,6% |
94,5% |
97,7% |
97,7% |
97,7% |
50% belasting |
96,2% |
96,1% |
96,1% |
98,6% |
98,6% |
98,6% |
75% belasting |
96,6% |
96,6% |
96,6% |
98,9% |
98,9% |
99,0% |
100% belasting |
96,7% |
96,8% |
96,9% |
99,1% |
99,1% |
99,1% |
50 kW met N+1 vermogensmodule | eConversion | Batterijbedrijf | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
96,7% |
96,7% |
96,6% |
95,1% |
94,9% |
94,8% |
50% belasting |
98,2% |
98,1% |
98,1% |
96,3% |
96,2% |
96,1% |
75% belasting |
98,6% |
98,6% |
98,6% |
96,7% |
96,6% |
96,5% |
100% belasting |
98,8% |
98,8% |
98,8% |
96,8% |
96,8% |
96,8% |
60 kW | Normaal bedrijf | ECO-modus | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
95,7% |
96,0% |
95,7% |
98,0% |
98,1% |
98,1% |
50% belasting |
96,7% |
96,6% |
96,7% |
98,9% |
98,9% |
98,9% |
75% belasting |
96,7% |
96,8% |
96,9% |
99,1% |
99,1% |
99,1% |
100% belasting |
96,6% |
96,6% |
96,8% |
99,2% |
99,2% |
99,2% |
60 kW | eConversion | Batterijbedrijf | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
97,6% |
97,7% |
97,6% |
95,7% |
95,6% |
95,5% |
50% belasting |
98,6% |
98,6% |
98,6% |
96,6% |
96,5% |
96,5% |
75% belasting |
99,0% |
98,9% |
99,0% |
96,7% |
96,7% |
96,7% |
100% belasting |
99,1% |
99,0% |
99,1% |
96,6% |
96,6% |
96,6% |
80 kW | Normaal bedrijf | ECO-modus | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
95,8% |
95,7% |
95,4% |
98,3% |
98,4% |
98,4% |
50% belasting |
96,6% |
96,7% |
96,6% |
98,9% |
99,0% |
99,0% |
75% belasting |
96,7% |
96,8% |
96,8% |
99,1% |
99,1% |
99,2% |
100% belasting |
96,6% |
96,8% |
96,8% |
99,1% |
99,2% |
99,2% |
80 kW | eConversion | Batterijbedrijf | ||||
---|---|---|---|---|---|---|
Spanning (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% belasting |
97,8% |
97,8% |
97,7% |
96,2% |
96,0% |
96,0% |
50% belasting |
98,7% |
98,7% |
98,7% |
96,8% |
96,7% |
96,7% |
75% belasting |
98,9% |
98,9% |
98,9% |
96,8% |
96,7% |
96,7% |
100% belasting |
99,0% |
99,0% |
99,0% |
96,6% |
96,6% |
96,6% |
100 kW | Normaal bedrijf | ECO-modus | ||
---|---|---|---|---|
Spanning (V) | 400 | 415 | 400 | 415 |
25% belasting |
96,1% |
95,9% |
98,6% |
98,6% |
50% belasting |
96,8% |
96,7% |
99,1% |
99,1% |
75% belasting |
96,8% |
96,8% |
99,1% |
99,2% |
100% belasting |
96,5% |
96,6% |
99,1% |
99,2% |
100 kW | eConversion | Batterijbedrijf | ||
---|---|---|---|---|
Spanning (V) | 400 | 415 | 400 | 415 |
25% belasting |
98,1% |
98,2% |
96,3% |
96,3% |
50% belasting |
98,8% |
98,8% |
96,7% |
96,7% |
75% belasting |
99,0% |
99,0% |
96,7% |
96,7% |
100% belasting |
99,0% |
99,0% |
96,4% |
96,5% |