Specifications
UPS rating | 20 kW | 30 kW | 40 kW | 50 kW |
---|---|---|---|---|
Input voltage (V) | 600 | |||
Input connections | 4-wire (L1, L2, L3, N, G) | |||
Nominal input current (A) | 20 | 30 | 40 | 50 |
Maximum input current (A) | 24 | 36 | 47 | 59 |
Bypass voltage (V) | 600 | |||
Bypass connections | 4-wire (L1, L2, L3, N, G) | |||
Nominal bypass current (A) | 19 | 29 | 39 | 49 |
Output connections | 4-wire (L1, L2, L3, N, G) | |||
Output voltage (V) | 480 | |||
Nominal output current (A) | 29 | 44 | 59 | 74 |
Frequency (Hz) | 60 | |||
Circuit breaker interrupting ratings (kA) | 25 at 600 V (for UIB/SSIB) | |||
Continuous operation limited to maximum 110% load. |
UPS rating | 60 kW | 80 kW | 100 kW | 120 kW | 150 kW |
---|---|---|---|---|---|
Input voltage (V) | 600 | ||||
Input connections | 4-wire (L1, L2, L3, N, G) | ||||
Nominal input current (A) | 60 | 79 | 99 | 119 | 149 |
Maximum input current (A) | 70 | 94 | 118 | 141 | 178 |
Bypass voltage (V) | 600 | ||||
Bypass connections | 4-wire (L1, L2, L3, N, G) | ||||
Nominal bypass current (A) | 59 | 78 | 97 | 117 | 146 |
Output connections | 4-wire (L1, L2, L3, N, G) | ||||
Output voltage (V) | 480 | ||||
Nominal output current (A) | 88 | 117 | 147 | 177 | 222 |
Frequency (Hz) | 60 | ||||
Circuit breaker interrupting ratings (kA) | 25 at 600 V (for UIB/SSIB) | ||||
Continuous operation limited to maximum 110% load. |
For specifications for the surge protection device: Refer to the installation manual provided with the surge protection device (SSP08EMA12).
Trip Settings
Trip Settings for UIB and SSIB (SSIB is Only Applicable to Dual Mains System)
UPS rating | Breaker type | Ir | tr at 6 Ir | li (x In) |
---|---|---|---|---|
20 kW |
JJF36250CU31X |
70 |
0.5 |
1.5 |
30 kW |
JJF36250CU31X |
70 |
0.5 |
1.5 |
40 kW |
JJF36250CU31X |
70 |
0.5 |
1.5 |
50 kW |
JJF36250CU31X |
80 |
0.5 |
1.5 |
60 kW |
JJF36250CU31X |
100 |
0.5 |
1.5 |
80 kW |
JJF36250CU31X |
125 |
0.5 |
1.5 |
100 kW |
JJF36250CU31X |
175 |
0.5 |
1.5 |
120 kW |
JJF36250CU31X |
200 |
0.5 |
1.5 |
150 kW |
JJF36250CU31X |
250 |
0.5 |
1.5 |
Recommended Upstream Protection
Trip Settings for Input Breaker and Bypass Breaker (Bypass is Only Applicable to Dual Mains System)
UPS rating | Breaker type | Ir | tr at 6 Ir | li (x In) |
---|---|---|---|---|
20 kW |
HJL36060U31X |
35 |
0.5 |
1.5 |
30 kW |
HJL36060U31X |
50 |
0.5 |
1.5 |
40 kW |
HJL36060U31X |
60 |
0.5 |
1.5 |
50 kW |
HJF36100U31X |
80 |
0.5 |
1.5 |
60 kW |
HJL36100U31X |
100 |
0.5 |
1.5 |
80 kW |
HJF36150U31X |
125 |
0.5 |
1.5 |
100 kW |
JJL36250CU31X |
175 |
0.5 |
1.5 |
120 kW |
JJL36250CU31X |
200 |
0.5 |
1.5 |
150 kW |
JJL36250CU31X |
250 |
0.5 |
1.5 |
Recommended Cable Sizes
![]() |
---|
hazard of electric shock, explosion, or arc flash
All wiring must comply with all applicable national and/or electrical codes. The maximum
allowable cable size is 4/0 AWG.
Failure to follow these instructions will result in death or serious injury.
|
Cable sizes in this manual are based on Table 310.15 (B)(16) of the National Electrical Code (NEC) with the following assertions:
-
90 °C (194 °F) conductors (75 °C (167 °F) termination)
-
An ambient temperature of 30 °C (86 °F)
-
Use of copper or aluminum conductors
If the ambient temperature is greater than 30 °C (86 °F), larger conductors are to be selected in accordance with the correction factors of the NEC.
Equipment grounding conductors (EGC) are sized in accordance with NEC Article 250.122 and Table 250.122.
Copper
Aluminum
UPS rating | 20 kW | 30 kW | 40 kW | 50 kW | 60 kW | 80 kW | 100 kW | 120 kW | 150 kW |
---|---|---|---|---|---|---|---|---|---|
Input phases (AWG/kcmil) |
8 |
4 |
3 |
2 |
1/0 |
3/0 |
4/0 |
2 x 4/0 |
2 x 2/0 |
Input EGC (AWG/kcmil) |
8 |
8 |
6 |
6 |
6 |
4 |
4 |
4 |
2 x 2 |
Bypass phases (AWG/kcmil) |
10 |
6 |
4 |
3 |
2 |
1/0 |
3/0 |
4/0 |
2 x 4/0 |
Bypass EGC (AWG/kcmil) |
8 |
8 |
8 |
6 |
6 |
6 |
4 |
4 |
4 |
Output phases (AWG/kcmil) |
6 |
6 |
4 |
2 |
1 |
2/0 |
3/0 |
250 |
300 |
Output EGC (AWG/kcmil) |
6 |
6 |
6 |
6 |
6 |
4 |
4 |
4 |
2 |
Neutral (AWG/kcmil) |
4 |
2 |
1/0 |
2/0 |
4/0 |
2 x 1/0 |
2 x 2/0 |
2 x 250 |
2 x 2/0 |
Recommended Bolt and Lug Sizes
NOTICE |
---|
risk of equipment damage
Use only UL approved compression cable lugs.
Failure to follow these instructions can result in equipment damage.
|
Copper — One Hole Cable Lugs
Cable size | Bolt size | Cable lug type | Crimping tool | Die |
---|---|---|---|---|
10 AWG | M8 x 35 mm | LCA10-56-L | NA | NA |
8 AWG | M8 x 35 mm | LCA8-56-L | CT-720 | CD-720-1 Red P21 |
6 AWG | M8 x 35 mm | LCA6-56-L | CT-720 | CD-720-1 Blue P24 |
4 AWG | M8 x 35 mm | LCA4-56-L | CT-720 | CD-720-1 Gray P29 |
3 AWG | M8 x 35 mm | LCA4-56-L | CT-720 | CD-720-1 Gray P29 |
2 AWG | M8 x 35 mm | LCA2-56-Q | CT-720 | CD-720-1 Brown P33 |
1 AWG | M8 x 35 mm | LCA1-56-E | CT-720 | CD-720-2 Green P37 |
1/0 AWG | M8 x 35 mm | LCA1/0-56-X | CT-720 | CD-720-2 Pink P42 |
2/0 AWG | M8 x 35 mm | LCA2/0-56-X | CT-720 | CD-720-2 Black P45 |
3/0 AWG | M8 x 35 mm | LCA3/0-56-X | CT-720 | CD-720-2 Orange P50 |
4/0 AWG | M8 x 35 mm | LCA4/0-56-X | CT-720 | CD-720-3 Purple P54 |
Aluminum — One Hole Cable Lugs
Cable size | Bolt size | Cable lug type | Crimping tool | Die |
---|---|---|---|---|
6 AWG | M8 x 35 mm | LAA6–56–x | CT-720 | CD-720–1 Gray P29 |
4 AWG | M8 x 35 mm | LAA4–56–x | CT-720 | CD-720–2 Green P37 |
2 AWG | M8 x 35 mm | LAA2–56–x | CT-720 | CD-720–2 Pink P42 |
1 AWG | M8 x 35 mm | LAA1–56–X | CT-720 | CD-720–2 Gold P45 |
1/0 AWG | M8 x 35 mm | LAA1/0–56–5 | CT-720 | CD-720–2 Tan P50 |
2/0 AWG | M8 x 35 mm | LAA2/0–38–5 | CT-720 | CD-720–3 Olive P54 |
3/0 AWG | M8 x 35 mm | LAA3/0–38–5 | CT-720 | CD-720–3 Ruby P60 |
4/0 AWG | M8 x 35 mm | LAA4/0–38–5 | CT-720 | CD-720–4 White P66 |
Copper — Two Hole Cable Lugs
Cable size | Bolt size | Cable lug type* | Crimping tool | Die |
---|---|---|---|---|
6 AWG | M8 x 35 mm | LCC6-12-L | CT-930 | CD-920-6 Blue P24 |
4 AWG | M8 x 35 mm | LCC4-12-L | CT-930 | CD-920-4 Gray P29 |
3 AWG | M8 x 35 mm | |||
2 AWG | M8 x 35 mm | LCC2-12-Q | CT-930 | CD-920-2 Brown P33 |
1 AWG | M8 x 35 mm | LCC1-12-E | CT-930 | CD-920-1 Green P37 |
1/0 AWG | M8 x 35 mm | LCC1/0-12-X | CT-930 | CD-920-1/0 Pink P42 |
2/0 AWG | M8 x 35 mm | LCC2/0-12-X | CT-930 | CD-920-2/0 Black P45 |
3/0 AWG | M8 x 35 mm | LCC3/0-12-X | CT-930 | CD-920-3/0 Orange P50 |
4/0 AWG | M8 x 35 mm | LCC4/0-12-X | CT-930 | CD-920-4/0 Purple P54 |
Aluminum — Two Hole Cable Lugs
Cable size | Bolt size | Cable lug type* | Crimping tool | Die |
---|---|---|---|---|
2/0 AWG | M8 x 35 mm | LAB2/0–12–5 | CT-720 | CD-720–3 Olive P54 |
3/0 AWG | M8 x 35 mm | LAB3/0–12–5 | CT-720 | CD-720–3 Ruby P60 |
4/0 AWG | M8 x 35 mm | LAB4/0–12–5R | CT-720 | CD-720–4 White P66 |
Torque Specifications
Bolt size | Torque |
---|---|
M4 | 1.7 Nm (1.25 lb-ft / 15 lb-in) |
M5 | 2.2 Nm (1.62 lb-ft / 19.5 lb-in) |
M6 | 5 Nm (3.69 lb-ft / 44.3 lb-in) |
M8 | 17.5 Nm (12.91 lb-ft / 154.9 lb-in) |
M10 | 30 Nm (22 lb-ft / 194.7 lb-in) |
M12 | 50 Nm (36.87 lb-ft / 442.5 lb-in) |
Input Transformer Cabinet Weights and Dimensions
Commercial reference | Weight kg (lbs) | Height mm (in) | Width mm (in) | Depth mm (in) |
---|---|---|---|---|
GVSBPIT100 with surge protection device (SSP08EMA12) installed | 370 (816) | 1800 (70.86) | 600 (23.62) | 836 (32.91) |
GVSBPIT150 with surge protection device (SSP08EMA12) installed | 370 (816) | 1800 (70.86) | 600 (23.62) | 836 (32.91) |
Clearance
Environment
Operating | Storage | |
---|---|---|
Temperature | 0 °C to 40 °C (32 °F to 104 °F) | -25 °C to 55 °C (-13 °F to 131 °F) |
Relative humidity | 0 - 95% non-condensing | 0-95% non-condensing |
Elevation | Designed for operation in 0-3000 m (0-10000 feet) elevation. Power derating required from 1000-3000 m (3300-10000 feet): Up to 1000 m (3300 feet): 1.000 Up to 1500 m (5000 feet): 0.975 Up to 2000 m (6600 feet): 0.950 Up to 2500 m (8300 feet): 0.925 Up to 3000 m (10000 feet): 0.900 |
|
Protection class | IP20 | |
Color | Input transformer cabinet (GVSBPIT100, GVSBPIT150): RAL 9003, gloss level 85% Surge protection device (SSP08EMA12): Black |