Inverter Short–Circuit Capabilities (Bypass not Available)
IK1 – Short-Circuit between a Phase and Neutral

480 V IK1
S [kVA] | Ik10ms [A] Normal operation /Battery operation | Ik30ms [A] Normal operation /Battery operation | Ik100ms [A] Normal operation /Battery operation | Ik500ms [A] Normal operation /Battery operation | Ik1s [A] Normal operation /Battery operation | Ik5s [A] Normal operation /Battery operation | I2 t total [A2s] Normal operation /Battery operation |
---|---|---|---|---|---|---|---|
250 |
– /810 |
– /810 |
– /570 |
– /290 |
– /290 |
– /290 |
– /493600 |
500 |
– /1620 |
– /1620 |
– /1140 |
– /580 |
– /580 |
– /580 |
– /1974400 |
750 |
– /2430 |
– /2430 |
– /1710 |
– /870 |
– /870 |
– /870 |
– /4442400 |
1000 |
– /3240 |
– /3240 |
– /2280 |
– /1160 |
– /1160 |
– /1160 |
– /7897600 |
1250 |
– /4050 |
– /4050 |
– /2850 |
– /1450 |
– /1450 |
– /1450 |
– /12340000 |
1500 |
– /4860 |
– /4860 |
– /3420 |
– /1740 |
– /1740 |
– /1740 |
– /17769600 |
IK2 – Short-Circuit between Two Phases

480 V IK2
S [kVA] | Ik10ms [A] Normal operation /Battery operation | Ik30ms [A] Normal operation /Battery operation | Ik100ms [A] Normal operation /Battery operation | Ik500ms [A] Normal operation /Battery operation | Ik1s [A] Normal operation /Battery operation | Ik5s [A] Normal operation /Battery operation | I2 t total [A2s] Normal operation /Battery operation |
---|---|---|---|---|---|---|---|
250 |
790 /790 |
770 /770 |
550 /550 |
430 /280 |
430 /280 |
280 /280 |
606450 /460820 |
500 |
1580 /1580 |
1540 /1540 |
1100 /1100 |
860 /560 |
860 /560 |
560 /560 |
2425800 /1843280 |
750 |
2370 /2370 |
2310 /2310 |
1650 /1650 |
1290 /840 |
1290 /840 |
840 /840 |
5458050 /4147380 |
1000 |
3160 /3160 |
3080 /3080 |
2200 /2200 |
1720 /1120 |
1720 /1120 |
1120 /1120 |
9703200 /7373120 |
1250 |
3950 /3950 |
3850 /3850 |
2750 /2750 |
2150 /1400 |
2150 /1400 |
1400 /1400 |
15161250 /11520500 |
1500 |
4740 /4740 |
4620 /4620 |
3300 /3300 |
2580 /1680 |
2580 /1680 |
1680 /1680 |
21832200 /16589520 |
IK3 – Short-Circuit between All Three Phases

480 V IK3
S [kVA] | Ik10ms [A] Normal operation /Battery operation | Ik30ms [A] Normal operation /Battery operation | Ik100ms [A] Normal operation /Battery operation | Ik500ms [A] Normal operation /Battery operation | Ik1s [A] Normal operation /Battery operation | Ik5s [A] Normal operation /Battery operation | I2 t total [A2s] Normal operation /Battery operation |
---|---|---|---|---|---|---|---|
250 |
670 /660 |
670 /660 |
610 /610 |
440 /440 |
360 /440 |
300 /300 |
580600 /589380 |
500 |
1340 /1320 |
1340 /1320 |
1220 /1220 |
880 /880 |
720 /880 |
600 /600 |
2322400 /2357520 |
650 |
1742 /1716 |
1742 /1716 |
1586 /1586 |
1144 /1144 |
936 /1144 |
780 /780 |
3924856 /3984209 |
1000 |
2680 /2640 |
2680 /2640 |
2440 /2440 |
1760 /1760 |
1440 /1760 |
1200 /1200 |
9289600 /9430080 |
1250 |
3350 /3300 |
3350 /3300 |
3050 /3050 |
2200 /2200 |
1800 /2200 |
1500 /1500 |
14515000 /14734500 |
1500 |
4020 /3960 |
4020 /3960 |
3660 /3660 |
2640 /2640 |
2160 /2640 |
1800 /1800 |
20901600 /21217680 |