Typical sources of test errors
Typical sources of accuracy verification testing errors include:
- 
                     
Loose connections of voltage or current circuits, often caused by worn-out contacts or terminals. Inspect terminals of test equipment, cables, test harness and the meter under test.
 - 
                     
Meter ambient temperature is significantly different than 23 °C (73 °F).
 - 
                     
Floating (ungrounded) neutral voltage terminal in any configuration with unbalanced phase voltages.
 - 
                     
Inadequate meter control power, resulting in the meter resetting during the test procedure.
 - 
                     
Ambient light interference or sensitivity issues with the optical sensor.
 - 
                     
Unstable power source causing energy pulsing fluctuations.
 - 
                     
Incorrect test setup: not all phases connected to the reference device or the energy standard. All phases connected to the meter under test should also be connected to the reference meter/standard.
 - 
                     
Moisture (condensing humidity), debris or pollution present in the meter under test.