990-93888A-001

Specifications

Overview of ESS Energy Storage Systems

Arc flash related calculation of the battery system is estimated with the Direct-Current Incident Energy Calculations referenced in Informative Annex D of NFPA 70E Standard for Electrical Safety in the Workplace. The ESS system is assumed to estimate the worst-case scenario of 8 LIBSESMG17UL battery cabinets in parallel. Estimated arc flash: < 0.97 cal/cm2.

Input/output voltage, VAC, 3-phase, 50/60 Hz: 480 V.
Ambient temperature range: 23 °C ±5 °C.
Max. short-circuit current: 65 kA.

ESS model name Max. input current (A) Max. output current (A) Max. energy output (W) Max. power input (kVA) Max. power output (kVA)

GVL200K500DS - 1LIBSESMG17UL

303 241 34600 252 184

GVL200K500DS - 2LIBSESMG17UL

303

241

69200

252

200

GVL200K500DS - 3LIBSESMG17UL

303

241

103800

252

200

GVL200K500DS - 4LIBSESMG17UL

303

241

138400

252

200

GVL200K500DS - 5LIBSESMG17UL

303

241

173000

252

200

GVL200K500DS - 6LIBSESMG17UL

303

241

207600

252

200

GVL200K500DS - 7LIBSESMG17UL

303

241

242200

252

200

GVL200K500DS - 8LIBSESMG17UL

303

241

276800

252

200

GVL200K500DS - 1LIBSESMG16UL

303 241 32600 252 173

GVL200K500DS - 2LIBSESMG16UL

303

241

65200

252

200

GVL200K500DS - 3LIBSESMG16UL

303

241

97800

252

200

GVL200K500DS - 4LIBSESMG16UL

303

241

130400

252

200

GVL200K500DS - 5LIBSESMG16UL

303

241

163000

252

200

GVL200K500DS - 6LIBSESMG16UL

303

241

195600

252

200

GVL200K500DS - 7LIBSESMG16UL

303

241

228200

252

200

GVL200K500DS - 8LIBSESMG16UL

303

241

260800

252

200

GVL300K500DS - 2LIBSESMG17UL

455

361

69200

378

300

GVL300K500DS - 3LIBSESMG17UL

455

361

103800

378

300

GVL300K500DS - 4LIBSESMG17UL

455

361

138400

378

300

GVL300K500DS - 5LIBSESMG17UL

455

361

173000

378

300

GVL300K500DS - 6LIBSESMG17UL

455

361

207600

378

300

GVL300K500DS - 7LIBSESMG17UL

455

361

242200

378

300

GVL300K500DS - 8LIBSESMG17UL

455

361

276800

378

300

GVL300K500DS - 2LIBSESMG16UL

455

361

65200

378

300

GVL300K500DS - 3LIBSESMG16UL

455

361

97800

378

300

GVL300K500DS - 4LIBSESMG16UL

455

361

130400

378

300

GVL300K500DS - 5LIBSESMG16UL

455

361

163000

378

300

GVL300K500DS - 6LIBSESMG16UL

455

361

195600

378

300

GVL300K500DS - 7LIBSESMG16UL

455

361

228200

378

300

GVL300K500DS - 8LIBSESMG16UL

455

361

260800

378

300

GVL400K500DS - 2LIBSESMG17UL

607 481 69200 505 368

GVL400K500DS - 3LIBSESMG17UL

607

481

103800

505

400

GVL400K500DS - 4LIBSESMG17UL

607

481

138400

505

400

GVL400K500DS - 5LIBSESMG17UL

607

481

173000

505

400

GVL400K500DS - 6LIBSESMG17UL

607

481

207600

505

400

GVL400K500DS - 7LIBSESMG17UL

607

481

242200

505

400

GVL400K500DS - 8LIBSESMG17UL

607

481

276800

505

400

GVL400K500DS - 2LIBSESMG16UL

607 481 65200 505 346

GVL400K500DS - 3LIBSESMG16UL

607

481

97800

505

400

GVL400K500DS - 4LIBSESMG16UL

607

481

130400

505

400

GVL400K500DS - 5LIBSESMG16UL

607

481

163000

505

400

GVL400K500DS - 6LIBSESMG16UL

607

481

195600

505

400

GVL400K500DS - 7LIBSESMG16UL

607

481

228200

505

400

GVL400K500DS - 8LIBSESMG16UL

607

481

260800

505

400

GVL500KDS - 3LIBSESMG17UL

758

601

103800

 630

500

GVL500KDS - 4LIBSESMG17UL

758

601

138400

630

500

GVL500KDS - 5LIBSESMG17UL

758

601

173000

630

500

GVL500KDS - 6LIBSESMG17UL

758

601

207600

630

500

GVL500KDS - 7LIBSESMG17UL

758

601

242200

630

500

GVL500KDS - 8LIBSESMG17UL

758

601

276800

630

500

GVL500KDS - 3LIBSESMG16UL

758

601

97800

630

500

GVL500KDS - 4LIBSESMG16UL

758

601

130400

630

500

GVL500KDS - 5LIBSESMG16UL

758

601

163000

630

500

GVL500KDS - 6LIBSESMG16UL

758

601

195600

630

500

GVL500KDS - 7LIBSESMG16UL

758

601

228200

630

500

GVL500KDS - 8LIBSESMG16UL

758

601

260800

630

500

Specifications for 200-500 kW UPS

  UPS rating 200 kW 300 kW 400 kW 500 kW
Input Connections Single mains: 4-wire* (L1, L2, L3, N, G) or
3-wire* (L1, L2, L3, G)
Dual mains: 3-wire* (L1, L2, L3, G)
Input voltage range (V) 408-552
Frequency (Hz) 40-70
Nominal input current (A) 249 373 497 621
Maximum input current (A) 303 455 607 758
Input current limitation (A) 313 470 626 783
Total harmonic distortion (THDI) <3% at 100% load
Input power factor >0.99 at load >25%, 0.95 at >15% load
Protection Built-in backfeed protection and fuses
Ramp-in Adaptive 1-300 seconds
Bypass Connections 4-wire (L1, L2, L3, N, G) or
3-wire (L1, L2, L3, G)
Bypass voltage range (V) 432-528
Frequency (Hz) 50 or 60
Frequency range (Hz) Programmable: ±1, ±3, ±10. Default is ±3.
Nominal bypass current (A) 247 371 494 618
Maximum short circuit rating (three cycles) 65 kAIC
65 kAIC with maintenance bypass cabinet (GVLMBCA200K500G)
45 kAIC Icw with bottom entry cabinet (GVBEC)
65 kAIC Icw with bottom entry cabinet (GVBEC and GVLOPT012 installed)
65 kAIC with backfeed breaker kit (GVLOPT003) installed in the UPS*
I2t thyristor value (A2s) 3.1 MA2s
Bypass backfeed protection options 1: Upstream installation of breaker with shunt trip connected to the UPS, OR
2: Installation with maintenance bypass cabinet (GVLMBCA200K500H / GVLMBCA200K500G), OR
3: Installation of backfeed breaker kit (GVLOPT004 / GVLOPT003) in the UPS.
Output Connections* 4-wire (L1, L2, L3, N, G) or
3-wire (L1, L2, L3, G, GEC*)
Output voltage regulation Symmetrical load ± 1%
Asymmetrical load ± 3%
Overload capacity

Normal operation: 150% for 1 minute, 125% for 10 minutes, (110% continuous*)
Battery operation: 125% for 1 minute
Bypass operation: 125% continuous, 1600% for 100 milliseconds

Dynamic load response ± 5% after 2 ms, ± 1% after 50 ms
Output power factor 1
Nominal output current (A) 241 361 481 601
Inverter output short circuit capabilities Varies with time. See graph and table values in Inverter Short Circuit Capabilities (Bypass not Available).
Output frequency (Hz) 50/60 (synchronized to bypass), 50/60 Hz ±0.1% (free-running)
Synchronized slew rate (Hz/sec) Programmable: 0.25, 0.5, 1, 2, 4, 6
Total harmonic distortion (THDU) <1% for linear load, <5% for non-linear load
Output performance classification (according to IEC/ EN62040-3) VFI-SS-11
Load crest factor 3
Load power factor 0.5 leading to 0.5 lagging without derating

Specifications for Lithium-ion Battery Cabinets

  LIBSESMG16UL LIBSESMG17UL
Charging power in % of output power 0-40% load: 80%
100% load: 20%
0-40% load: 80%
100% load: 20%
Nominal battery voltage (VDC) at 3.8 V per cell 486

517

Peak current at end of discharge voltage (A) 

450

450

Charge current default rate (CA rate) 

0.7

0.7

Maximum continuous charge current rate (CA rate) 

1.0

1.0

Float charge voltage (VDC) at 4.2 V per cell

538

571

End of discharge voltage (VDC) at 3.0 V per cell

384

408

Maximum continuous 100% depth of discharge power (kW)

173

184

Maximum partial depth of discharge power (kW)

218

231

Short circuit rating value (kA) - Isc, RMS (Isc, MAX)

2.9 (9.0)

2.9 (9.0)

NOTE: If the battery temperature is higher than the threshold after a full discharge at maximum continuous discharge power, the UPS may have to reduce the charge current to zero to protect the battery.
NOTE: The battery temperature must return to room temperature ±3 °C (5 °F) before a new discharge at maximum continuous discharge power. If not, the battery disconnect device may be tripped due to overtemperature protection.
NOTE: The working temperature for the busbars should be no more than
100 ℃ (212 °F).

Upstream and Downstream Protection for UL

Preconditions for Live Swap of Power Modules

Live Swap of power modules is only allowed under the following preconditions for the UPS installation; Follow either scenario 1 or scenario 2:

Preconditions for UPS installation — scenario 1 with instantaneous override values and trip times set according to the tables below in Recommended Upstream Protection for UL Preconditions for UPS installation — scenario 2 with alternative disconnect device configurations supported with GVLOPT011 and disconnect device with ERMS mode*
Circuit breakers must have instantaneous trip time of maximum 50 ms. Circuit breakers must be installed for input (unit input disconnect device UIB) and bypass (static switch input disconnect device SSIB).
Circuit breakers must have instantaneous override values set according to the table below. Circuit breakers (UIB, SSIB) must be equipped with NEC 240.87, NFPA70E, IEEE1584, or EN51110-1 compliant ERMS mode.
Circuit breakers must be installed for input (unit input disconnect device UIB) and bypass (static switch input disconnect device SSIB). For parallel systems with three or more UPSs: Circuit breakers must be installed for the output (unit output disconnect device UOB) of each UPS. The unit output disconnect device (UOB) is sized as the static switch input disconnect device (SSIB).
For parallel system with three or more UPSs: Circuit breakers must be installed for the output (unit output disconnect device UOB) of each UPS. The unit output disconnect device (UOB) is sized as the static switch input disconnect device (SSIB). Circuit breaker (UOB) must be equipped with NEC 240.87, NFPA70E, IEEE1584, or EN51110-1 compliant ERMS mode.
Live Swap is not supported for >65kAbf installations where current limiting disconnect devices are used to protect the UPS. GVLOPT011 (Galaxy VL door switch kit) must be installed in the UPS and connected so ERMS mode is set to ON on UIB and SSIB and UOB when the front door of the UPS is opened.
  In ERMS mode, the instantaneous trip current shall be set to 5000 A or less. All time-delay settings shall be set to zero.

Schneider Electric reserves the right to remove the Live Swap label from the product front if the preconditions for scenario 1 or scenario 2 are not met.

DANGER
Hazard of electric shock, explosion, or arc flash
Only perform Live Swap of the power modules in UPS installations that follow the preconditions for scenario 1 or scenario 2.
Failure to follow these instructions will result in death or serious injury.

Recommended Upstream Protection for UL

The bypass/output disconnect devices are sized based on the nominal current +10%. This is to accommodate either low grid voltage or deviation in cable length between parallel UPSs. The battery disconnect devices are sized based on the end-of-discharge voltage which has been defined as 380 VDC.

NOTE: Overcurrent protection is to be provided by others and marked with its function.
UPS rating 200 kW 250 kW
  Input Bypass Input Bypass
Breaker type
Breaker type
LJF36400CU31X LJF36400CU31X

LJF36400CU31X

LJF36400CU31X
Ir 320 280 400 360
tr ≥4 ≥4 ≥4 ≥4
li (x In) ≤12 ≤12 ≤12 ≤12
UPS rating 300 kW 350 kW 400 kW
  Input Bypass Input Bypass Input Bypass
Breaker type
Breaker type

PJF36060CU31A

PJF36060CU31A

PJF36060CU31A

PJF36060CU31A

PJF36080CU31A PJF36060CU31A
Ir 480 420 540 480 640 540
tr ≥4 ≥4 ≥4 ≥4 ≥4 ≥4
li (x In) ≤12 ≤12 ≤10 ≤12 ≤10 ≤12
UPS rating 450 kW 500 kW
  Input Bypass Input Bypass
Breaker type
Breaker type
PJF36080CU31A PJF36080CU31A PJF36080CU31A PJF36080CU31A
Ir 720 640 800 720
tr ≥4 ≥4 ≥4 ≥4
li (x In) ≤8 ≤10 ≤8 ≤10

Recommended Cable Sizes for UL

DANGER
hazard of electric shock, explosion, or arc flash
  • All wiring must comply with all applicable national and/or electrical codes.
  • The maximum allowable cable size is 600 kcmil for input/bypass/output/neutral/ground cables in the UPS.
  • The maximum allowable cable size is 500 kcmil for DC cables in the UPS.
  • Shrink sleeve must be fitted over cable lug crimped zone and must overlap with the cable insulation on all power cables.
Failure to follow these instructions will result in death or serious injury.
DANGER
hazard of electric shock, explosion, or arc flash
  • All wiring must comply with all applicable national and/or electrical codes.
  • The maximum allowable cable size is 350 kcmil for DC cables in the Lithium-ion battery cabinet.
  • Shrink sleeve must be fitted over cable lug crimped zone and must overlap with the cable insulation on all power cables.
Failure to follow these instructions will result in death or serious injury.

The maximum number of cable connections per busbar in the UPS:

  • 4 on input/output/bypass busbars

  • 4 x 600 kcmil on input/output/bypass busbars

  • 5 x 500 kcmil or 8 x 300 kcmil on DC+/DC- busbars

  • 8 on N busbar

  • 16 on ground busbar

NOTE: Overcurrent protection is to be provided by others.

Cable sizes in this manual are based on Table 310.15 (B)(16) of the National Electrical Code (NEC) with the following assertions*:

  • 90 °C (194 °F) conductors (75 °C (167 °F) termination)

  • An ambient temperature of 30 °C (86 °F)

  • Use of copper or aluminum conductors for the UPS.

  • Use of copper conductors for the Lithium-ion battery cabinet.

If the ambient temperature is greater than 30 °C (86 °F), larger conductors are to be selected in accordance with the correction factors of the NEC.

Equipment grounding conductors (EGC) are sized in accordance with the minimum requirements in NEC Article 250.122 and Table 250.122.

NOTE: 100% rated circuit disconnect devices for UIB, UOB, MBB, SSIB. 100% rated disconnect devices for battery disconnect devices.

The bypass/output cables are sized based on the nominal current +10%. This is to accommodate either low grid voltage or deviation in length between parallel UPSs. The battery cables are sized based on end-of-discharge voltage which has been defined as 380 VDC.

Copper

UPS rating 200 kW 300 kW 400 kW 500 kW
Voltage (V) 480 480 480 480
Input phases (AWG/kcmil) 1 x 350 2 x 4/0 2 x 350 2 x 500
Input EGC (AWG/kcmil) 1 x 3 2 x 2 2 x 1/0 2 x 1/0
Bypass/output phases (AWG/kcmil) 1 x 300 1 x 600 2 x 300 2 x 400
Bypass EGC/output EGC (AWG/kcmil) 1 x 4 1 x 2 2 x 1 2 x 1/0
DC+/DC- (AWG/kcmil) 1 x 350 / 2 x 250 1 x 350 / 2 x 250 1 x 350 / 2 x 250 1 x 350 / 2 x 250
DC EGC (AWG/kcmil) 1 x 350 / 2 x 250 1 x 350 / 2 x 250 1 x 350 / 2 x 250 1 x 350 / 2 x 250
Inverter midpoint cable for 3-wire parallel (AWG/kcmil) 1 x 350 2 x 4/0 2 x 350 2 x 500

Aluminum

UPS rating 200 kW 300 kW 400 kW 500 kW
Voltage (V) 480 480 480 480
Input phases (AWG/kcmil) 1 x 500 2 x 300 2 x 500 (3 x 400)*
Input EGC (AWG/kcmil) 1 x 1 2 x 1/0 2 x 3/0 3 x 3/0
Bypass/output phases (AWG/kcmil) 1 x 400 2 x 250 2 x 400 2 x 600
Bypass EGC/output EGC (AWG/kcmil) 1 x 2 2 x 1/0 2 x 2/0 2 x 3/0
Inverter midpoint cable for 3-wire parallel (AWG/kcmil) 1 x 500 2 x 300 2 x 500 3 x 400
NOTE: Aluminum cables are not supported for the Lithium-ion battery cabinets.

Guidance for Organizing Input, Bypass, And Output Cables

The input, bypass, and output cables must be grouped in circuits. On raceways, use one of the two shown cable formations.

Recommended Bolt and Lug Sizes

NOTICE
risk of equipment damage
Use only UL approved compression cable lugs.
Failure to follow these instructions can result in equipment damage.

Recommended Bolt and Lug Sizes for the UPS – Copper

Cable size Bolt size Cable lug type (one hole) Cable lug type (two hole NEMA) Crimping tool Die
1/0 AWG M10x35mm

LCB1/0-12-X

LCC1/0-12-X

CT-930

CD-920-1/0 Pink P42

2/0 AWG M10x35mm

LCB2/0-12-X

LCC2/0-12-X

CT-930

CD-920-2/0 Black P45

3/0 AWG M10x35mm

LCB3/0-12-X

LCC3/0-12-X

CT-930

CD-920-3/0 Orange P50

4/0 AWG M10x35mm

LCB4/0-12-X

LCC4/0-12-X

CT-930

CD-920-4/0 Purple P54

250 kcmil M10x35mm

LCB250-12-X

LCC250-12-X

CT-930

CD-920-250 Yellow P62

300 kcmil M10x35mm

LCB300-12-X

LCC300-12-X

CT-930

CD-920-300 White P66

350 kcmil M10x35mm

LCB350-12-X

LCC350-12-X

CT-930

CD-920-350 Red P71

400 kcmil M10x35mm

LCB400-12-X

LCC400-12-6

CT-930

CD-920-400 Blue P76

450 kcmil M10x35mm

LCC450-12-6

CT-930
500 kcmil M10x35mm

LCB500-12-X

LCC500-12-6

CT-930

CD-920-500 Brown P87

Recommended Bolt and Lug Sizes for the Lithium-ion Battery Cabinet– Copper — One Hole Cable Lugs

Cable size Bolt size Cable lug type Crimping tool Die
2 x 250 kcmil M10x30 LCB250-12-X CT-930 CD-920-250 Yellow P62
350 kcmil M10x30 LCC350-12-X CT-930 CD-920-350 Red P71

Recommended Bolt and Lug Sizes for the Lithium-ion Battery Cabinet– Copper — Two Hole Cable Lugs

Cable size Bolt size Cable lug type Crimping tool Die
2 x 250 kcmil M10x30 LCC250-12-X CT-930 CD-920-250 Yellow P62
350 kcmil M10x30 LCC350-12-X CT-930 CD-920-350 Red P71

Recommended Bolt and Lug Sizes for the UPS – Aluminum

Cable size Bolt size Cable lug type (one hole) Cable lug type (two hole NEMA) Crimping tool Die
1/0 AWG M10x35mm

LAA1/0-12-5

LAB1/0-12-X

CT-930

CD-920-1/0 Pink P42

2/0 AWG M10x35mm

LAA2/0-12-5

LAB2/0-12-5

CT-930

CD-920-2/0 Black P45

3/0 AWG M10x35mm

LAA3/0-12-5

LAB3/0-12-5

CT-930

CD-920-3/0 Orange P50

4/0 AWG M10x35mm

LAA4/0-12-5

LAB4/0-12-5R

CT-930

CD-920-4/0 Purple P54

250 kcmil M10x35mm

LAA250-12-5

LAB250-12-5

CT-930

CD-920-250 Yellow P62

300 kcmil M10x35mm

LAA300-12-2

LAB300-12-2

CT-930

CD-920-300 White P66

350 kcmil M10x35mm

LAA350-12-2

LAB350-12-2R

CT-930

CD-920-350 Red P71

400 kcmil M10x35mm

LAB400-12-2

CT-930

CD-920-400 Blue P76

500 kcmil M10x35mm

LAA500-12-2

LAB500-12-2R

CT-930

CD-920-500 Brown P87

NOTE: Aluminum cables are not supported for the Lithium-ion battery cabinets.

Inverter Short Circuit Capabilities (Bypass not Available)

IK1 – Short Circuit between a Phase and Neutral

IK1 480 V

S [kVA]

10ms; I[A]/I2t [A2t] 20ms; I[A]/I2t [A2t] 30ms; I[A]/I2t [A2t] 100ms; I[A]/I2t [A2t] 1s; I[A]/I2t [A2t]

200

560 /3090

560 /6180

560 /9280

480 /29020

380 /167430

250

700 /4830

700 /9660

700 /14490

610 /45350

480 /261610

300

830 /6960

830 /13910

830 /20870

730 /65300

570 /376720

350

970 /9470

970 /18940

970 /28410

850 /88880

670 /512750

400

1110 /12370

1110 /24740

1110 /37100

970 /116090

760 /669720

450

1250 /15650

1250 /31310

1250 /46960

1090 /146930

860 /847610

500

1390 /19330

1390 /38650

1390 /57970

1210 /181390

950 /1046430

IK2 – Short Circuit between Two Phases

IK2 480 V

S [kVA]

10ms; I[A]/I2t [A2t] 20ms; I[A]/I2t [A2t] 30ms; I[A]/I2t [A2t] 100ms; I[A]/I2t [A2t] 1s; I[A]/I2t [A2t]

200

560 /3150

560 /6280

560 /9350

470 /27550

370 /158630

250

700 /4920

700 /9810

700 /14610

590 /43050

460 /247850

300

840 /7090

840 /14130

840 /21040

700 /61990

550 /356910

350

980 /9640

980 /19230

980 /28640

820 /84380

650 /485790

400

1120 /12600

1120 /25110

1120 /37410

940 /110210

740 /634500

450

1260 /15940

1250 /31790

1250 /47350

1050 /139480

830 /803040

500

1400 /19680

1390 /39240

1390 /58450

1170 /172200

920 /991410

IK3 – Short Circuit between Three Phases

IK3 480 V

S [kVA]

10ms; I[A]/I2t [A2t] 20ms; I[A]/I2t [A2t] 30ms; I[A]/I2t [A2t] 100ms; I[A]/I2t [A2t] 1s; I[A]/I2t [A2t]

200

500 /2470

500 /4950

500 /7420

480 /24390

380 /159310

250

620 /3870

620 /7730

620 /11600

600 /38110

470 /248920

300

750 /5570

750 /11140

750 /16700

720 /54880

570 /358450

350

870 /7580

870 /15160

870 /22740

840 /74690

660 /487890

400

990 /9900

990 /19800

990 /29700

960 /97560

750 /637240

450

1120 /12530

1120 /25060

1120 /37580

1070 /123470

850 /806510

500

1240 /15470

1240 /30930

1240 /46400

1190 /152440

940 /995690

Torque Specifications

Bolt size Torque for UPS Torque for Lithium-ion battery cabinet
M4 1.7 Nm (1.25 lb-ft / 15 lb-in) 1.7 Nm (1.25 lb-ft / 15 lb-in)
M5 2.2 Nm (1.62 lb-ft / 19.5 lb-in) NA
M6 5 Nm (3.69 lb-ft / 44.3 lb-in) 5 Nm (3.69 lb-ft / 44.3 lb-in)
M8 17.5 Nm (12.91 lb-ft / 154.9 lb-in)

14 Nm (10.33 lb-ft)

M10 30 Nm (22 lb-ft / 194.7 lb-in)

30 Nm (22.13 lb-ft)

M12 50 Nm (36.87 lb-ft / 442.5 lb-in)

46 Nm (33.93 lb-ft)

Environment

  Operating Storage
  UPS Lithium-ion battery cabinet UPS Lithium-ion battery cabinet
Temperature 0 °C to 40 °C (32 °F to 104 °F) without load derating.
40 °C to 50 °C (104 °F to 122 °F) when derated to 70% power.

Recommended operating temperature is 18 °C to 28 °C (64 °F to 82 °F)

-25 °C to 55 °C (-13 °F to 131 °F) for systems without batteries.

Lithium-ion battery cabinet: 0 °C to 40 °C (32 °F to 104 °F)

Battery modules: Recommended storage for battery modules is 20 °C (68 °F) or cooler (non-freezing)

Relative humidity 5-95% non-condensing

0-95% non-condensing

10-80% non-condensing

Lithium-ion battery cabinet: 0-90% non-condensing

Lithium-ion battery modules: Recommended storage for battery modules is 40-80% non-condensing

Elevation Designed for operation in 0-3000 m (0-10000 feet) elevation.

Derating required from 1000-3000 m (3300-10000 feet) with forced air cooling:
Up to 1000 m (3300 feet): 1.000
Up to 1500 m (5000 feet): 1.000 conditioned by 2 x 300 mm2 input cables at 500 kW
Up to 1500 m (5000 feet) : 0.975
Up to 2000 m (6600 feet): 1.000 conditioned by 2 x 300 mm2 input cables at 500 kW
Up to 2000 m (6600 feet): 0.950
Up to 2500 m (8300 feet): 0.975 conditioned by 2 x 300 mm2 input cables at 500 kW
Up to 2500 m (8300 feet): 0.925
Up to 3000 m (10000 feet): 0.950 conditioned by 2 x 300 mm2 input cables at 500 kW
Up to 3000 m (10000 feet): 0.900

Derating required from 1000-3000 m (3300-10000 feet) with convection cooling:
Up to 1000 m (3300 feet): 1.000
Up to 1500 m (5000 feet) : 0.985
Up to 2000 m (6600 feet): 0.970
Up to 2500 m (8300 feet): 0.955
Up to 3000 m (10000 feet): 0.940
0-3000 m (0-10000 feet)    
Audible noise one meter (three feet) from unit

62 dB at 70% load

68 dB at 100% load for 480 V systems

     
Protection class IP20 IP20    
Color RAL 9003, gloss level 85% RAL 9003, gloss level 85%    

Compliance

  UPS Lithium-ion battery cabinet
Safety IEC 62040-1: 2017, Edition 2.0, Uninterruptible Power Systems (UPS) - Part 1: Safety requirements
UL 1778 5th edition

IEC 62619:2017 Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety requirements for secondary lithium cells and batteries, for use in industrial applications

IEC 62477-1:2012+A11:2014 Safety requirements for power electronic converter systems and equipment Part 1: General

UL 1973:2022 Batteries for Use in Stationary, Vehicle Auxiliary and Light Electric Rail Applications

UL 9540A:2019 Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems

EMC/EMI/RFI IEC 62040-2: 2016-11, 3rd edition Uninterruptible Power Systems (UPS) - Part 2: Electromagnetic compatibility (EMC) requirements C2
FCC Part 15 Subpart B, Class A

IEC 62040-2:2016 Uninterruptible Power Systems (UPS) - Part 2: Electromagnetic compatibility (EMC) requirements C2

FCC Part 15, Radio Frequency Devices, class A

Performance

Performance in accordance with: IEC 62040-3: 2021-04, 3rd edition Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the performance and test requirements.

Environmental  

IEC 60068-2-1:2007 Environmental testing – Part 2-1: Tests – Test A: Cold

IEC 60068-2-2:2007 Environmental testing – Part 2-2: Tests – Test B: Dry heat

IEC 60068-2-78:2012 Environmental testing – Part 2-78: Tests – Test Cab: Damp heat, steady state

Markings

UL1778 Listing and CSA C22.2 NO.107.3

ANSI/CAN/UL 1973 Listing

Transportation IEC 60721-4-2 Level 2M2

IEC60068-2-27:2008 Environmental testing – Part 2-27: Tests – Test Ea and guidance: Shock

IEC60068-2-31:2008 Environmental testing – Part 2-31: Tests – Test Ec: Rough handling shocks, primarily for equipment-type specimens

IEC60068-2-64:2008 Environmental testing – Part 2-64: Tests – Test Fh: Vibration, broadband random and guidance

Seismic ICC-ES AC 156 (2015); OSHPD Pre-approved; Sds=1.45 g for z/h=1 and Sds=2.00 g for z/h=0; Ip=1.5

OSHPD, CBC 2019, SDS=2.0g (z/h = 1); 2.5g (z/h = 0)

Earthing system* TN, TT, TNC, IT, TN-S, TNC-S
Solid-grounded, HRG
Overvoltage category This UPS is OVCII compliant.
If the UPS is installed in an environment with an OVC rating higher than II, an SPD (surge protection device) must be installed upstream of the UPS to reduce the overvoltage category to OVCII.
II
Protective class I
Pollution degree 2

Guidance for Organizing Battery Cables

NOTE: For 3rd party batteries, use only high rate batteries for UPS applications.
NOTE: When the battery bank is placed remotely, the organizing of the cables is important to reduce voltage drop and inductance. The distance between the battery bank and the UPS must not exceed 200 m (656 ft). Contact Schneider Electric for installations with a longer distance.
NOTE: To minimize the risk of electromagnetic radiation, it is highly recommended to follow the below guidance and to use grounded metallic tray supports.
Cable Length
<30 m Not recommended Acceptable Recommended Recommended
31–75 m Not recommended Not recommended Acceptable Recommended
76–150 m Not recommended Not recommended Acceptable Recommended
151–200 m Not recommended Not recommended Not recommended Recommended

Weights and Dimensions

UPS Weights and Dimensions

UPS rating Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
200 kW 550 (1212) 1970 (78) 850 (33) 925 (36)
300 kW 626 (1380) 1970 (78) 850 (33) 925 (36)
400 kW 702 (1547) 1970 (78) 850 (33) 925 (36)
500 kW 778 (1715) 1970 (78) 850 (33) 925 (36)

Lithium-ion Battery Cabinet Weights and Dimensions

  Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)

LIBSESMG16UL

470 (1036)

1970 (78)

650 (25.59)

587 (23.11)

LIBSESMG17UL

490 (1080)

1970 (78)

650 (25.59)

587 (23.11)

Clearance

NOTE: Clearance dimensions are published for airflow and service access only. Consult with the local safety codes and standards for additional requirements in your local area.
NOTE: Clearance dimensions for the lithium-ion battery cabinet have been verified by UL 9540A 4th edition (project No. 4789548397, issued by UL on 21 May 2021).

Front View of the UPS

Lithium-ion Battery Cabinet

* Rear clearance is only required for Lithium-ion battery cabinet with seismic anchoring.

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?