Specifications
Overview of ESS Energy Storage Systems
Arc flash related calculation of the battery system is estimated with the Direct-Current Incident Energy Calculations referenced in Informative Annex D of NFPA 70E Standard for Electrical Safety in the Workplace. The ESS system is assumed to estimate the worst-case scenario of 8 LIBSESMG17UL battery cabinets in parallel. Estimated arc flash: < 0.97 cal/cm2.
Input/output voltage,
VAC, 3-phase, 50/60 Hz: 480 V.
Ambient temperature
range: 23 °C ±5 °C.
Max. short-circuit
current: 65 kA.
ESS model name | Max. input current (A) | Max. output current (A) | Max. energy output (W) | Max. power input (kVA) | Max. power output (kVA) |
---|---|---|---|---|---|
GVL200K500DS - 1LIBSESMG17UL |
303 | 241 | 34600 | 252 | 184 |
GVL200K500DS - 2LIBSESMG17UL |
303 |
241 |
69200 |
252 |
200 |
GVL200K500DS - 3LIBSESMG17UL |
303 |
241 |
103800 |
252 |
200 |
GVL200K500DS - 4LIBSESMG17UL |
303 |
241 |
138400 |
252 |
200 |
GVL200K500DS - 5LIBSESMG17UL |
303 |
241 |
173000 |
252 |
200 |
GVL200K500DS - 6LIBSESMG17UL |
303 |
241 |
207600 |
252 |
200 |
GVL200K500DS - 7LIBSESMG17UL |
303 |
241 |
242200 |
252 |
200 |
GVL200K500DS - 8LIBSESMG17UL |
303 |
241 |
276800 |
252 |
200 |
GVL200K500DS - 1LIBSESMG16UL |
303 | 241 | 32600 | 252 | 173 |
GVL200K500DS - 2LIBSESMG16UL |
303 |
241 |
65200 |
252 |
200 |
GVL200K500DS - 3LIBSESMG16UL |
303 |
241 |
97800 |
252 |
200 |
GVL200K500DS - 4LIBSESMG16UL |
303 |
241 |
130400 |
252 |
200 |
GVL200K500DS - 5LIBSESMG16UL |
303 |
241 |
163000 |
252 |
200 |
GVL200K500DS - 6LIBSESMG16UL |
303 |
241 |
195600 |
252 |
200 |
GVL200K500DS - 7LIBSESMG16UL |
303 |
241 |
228200 |
252 |
200 |
GVL200K500DS - 8LIBSESMG16UL |
303 |
241 |
260800 |
252 |
200 |
GVL300K500DS - 2LIBSESMG17UL |
455 |
361 |
69200 |
378 |
300 |
GVL300K500DS - 3LIBSESMG17UL |
455 |
361 |
103800 |
378 |
300 |
GVL300K500DS - 4LIBSESMG17UL |
455 |
361 |
138400 |
378 |
300 |
GVL300K500DS - 5LIBSESMG17UL |
455 |
361 |
173000 |
378 |
300 |
GVL300K500DS - 6LIBSESMG17UL |
455 |
361 |
207600 |
378 |
300 |
GVL300K500DS - 7LIBSESMG17UL |
455 |
361 |
242200 |
378 |
300 |
GVL300K500DS - 8LIBSESMG17UL |
455 |
361 |
276800 |
378 |
300 |
GVL300K500DS - 2LIBSESMG16UL |
455 |
361 |
65200 |
378 |
300 |
GVL300K500DS - 3LIBSESMG16UL |
455 |
361 |
97800 |
378 |
300 |
GVL300K500DS - 4LIBSESMG16UL |
455 |
361 |
130400 |
378 |
300 |
GVL300K500DS - 5LIBSESMG16UL |
455 |
361 |
163000 |
378 |
300 |
GVL300K500DS - 6LIBSESMG16UL |
455 |
361 |
195600 |
378 |
300 |
GVL300K500DS - 7LIBSESMG16UL |
455 |
361 |
228200 |
378 |
300 |
GVL300K500DS - 8LIBSESMG16UL |
455 |
361 |
260800 |
378 |
300 |
GVL400K500DS - 2LIBSESMG17UL |
607 | 481 | 69200 | 505 | 368 |
GVL400K500DS - 3LIBSESMG17UL |
607 |
481 |
103800 |
505 |
400 |
GVL400K500DS - 4LIBSESMG17UL |
607 |
481 |
138400 |
505 |
400 |
GVL400K500DS - 5LIBSESMG17UL |
607 |
481 |
173000 |
505 |
400 |
GVL400K500DS - 6LIBSESMG17UL |
607 |
481 |
207600 |
505 |
400 |
GVL400K500DS - 7LIBSESMG17UL |
607 |
481 |
242200 |
505 |
400 |
GVL400K500DS - 8LIBSESMG17UL |
607 |
481 |
276800 |
505 |
400 |
GVL400K500DS - 2LIBSESMG16UL |
607 | 481 | 65200 | 505 | 346 |
GVL400K500DS - 3LIBSESMG16UL |
607 |
481 |
97800 |
505 |
400 |
GVL400K500DS - 4LIBSESMG16UL |
607 |
481 |
130400 |
505 |
400 |
GVL400K500DS - 5LIBSESMG16UL |
607 |
481 |
163000 |
505 |
400 |
GVL400K500DS - 6LIBSESMG16UL |
607 |
481 |
195600 |
505 |
400 |
GVL400K500DS - 7LIBSESMG16UL |
607 |
481 |
228200 |
505 |
400 |
GVL400K500DS - 8LIBSESMG16UL |
607 |
481 |
260800 |
505 |
400 |
GVL500KDS - 3LIBSESMG17UL |
758 |
601 |
103800 |
630 |
500 |
GVL500KDS - 4LIBSESMG17UL |
758 |
601 |
138400 |
630 |
500 |
GVL500KDS - 5LIBSESMG17UL |
758 |
601 |
173000 |
630 |
500 |
GVL500KDS - 6LIBSESMG17UL |
758 |
601 |
207600 |
630 |
500 |
GVL500KDS - 7LIBSESMG17UL |
758 |
601 |
242200 |
630 |
500 |
GVL500KDS - 8LIBSESMG17UL |
758 |
601 |
276800 |
630 |
500 |
GVL500KDS - 3LIBSESMG16UL |
758 |
601 |
97800 |
630 |
500 |
GVL500KDS - 4LIBSESMG16UL |
758 |
601 |
130400 |
630 |
500 |
GVL500KDS - 5LIBSESMG16UL |
758 |
601 |
163000 |
630 |
500 |
GVL500KDS - 6LIBSESMG16UL |
758 |
601 |
195600 |
630 |
500 |
GVL500KDS - 7LIBSESMG16UL |
758 |
601 |
228200 |
630 |
500 |
GVL500KDS - 8LIBSESMG16UL |
758 |
601 |
260800 |
630 |
500 |
Specifications for 200-500 kW UPS
UPS rating | 200 kW | 300 kW | 400 kW | 500 kW | |
---|---|---|---|---|---|
Input | Connections | Single
mains: 4-wire* (L1, L2, L3, N, G) or 3-wire* (L1, L2, L3, G) Dual mains: 3-wire* (L1, L2, L3, G) |
|||
Input voltage range (V) | 408-552 | ||||
Frequency (Hz) | 40-70 | ||||
Nominal input current (A) | 249 | 373 | 497 | 621 | |
Maximum input current (A) | 303 | 455 | 607 | 758 | |
Input current limitation (A) | 313 | 470 | 626 | 783 | |
Total harmonic distortion (THDI) | <3% at 100% load | ||||
Input power factor | >0.99 at load >25%, 0.95 at >15% load | ||||
Protection | Built-in backfeed protection and fuses | ||||
Ramp-in | Adaptive 1-300 seconds | ||||
Bypass | Connections | 4-wire (L1, L2, L3, N, G) or 3-wire (L1, L2, L3, G) |
|||
Bypass voltage range (V) | 432-528 | ||||
Frequency (Hz) | 50 or 60 | ||||
Frequency range (Hz) | Programmable: ±1, ±3, ±10. Default is ±3. | ||||
Nominal bypass current (A) | 247 | 371 | 494 | 618 | |
Maximum short circuit rating (three cycles) | 65 kAIC 65 kAIC with maintenance bypass cabinet (GVLMBCA200K500G) 45 kAIC Icw with bottom entry cabinet (GVBEC) 65 kAIC Icw with bottom entry cabinet (GVBEC and GVLOPT012 installed) 65 kAIC with backfeed breaker kit (GVLOPT003) installed in the UPS* |
||||
I2t thyristor value (A2s) | 3.1 MA2s | ||||
Bypass backfeed protection options | 1:
Upstream installation of breaker with shunt trip connected to the
UPS, OR 2: Installation with maintenance bypass cabinet (GVLMBCA200K500H / GVLMBCA200K500G), OR 3: Installation of backfeed breaker kit (GVLOPT004 / GVLOPT003) in the UPS. |
||||
Output | Connections* | 4-wire (L1, L2, L3, N, G) or 3-wire (L1, L2, L3, G, GEC*) |
|||
Output voltage regulation | Symmetrical load ±
1% Asymmetrical load ± 3% |
||||
Overload capacity |
Normal operation:
150% for 1 minute, 125% for 10 minutes, (110% continuous*) |
||||
Dynamic load response | ± 5% after 2 ms, ± 1% after 50 ms | ||||
Output power factor | 1 | ||||
Nominal output current (A) | 241 | 361 | 481 | 601 | |
Inverter output short circuit capabilities | Varies with time. See graph and table values in Inverter Short Circuit Capabilities (Bypass not Available). | ||||
Output frequency (Hz) | 50/60 (synchronized to bypass), 50/60 Hz ±0.1% (free-running) | ||||
Synchronized slew rate (Hz/sec) | Programmable: 0.25, 0.5, 1, 2, 4, 6 | ||||
Total harmonic distortion (THDU) | <1% for linear load, <5% for non-linear load | ||||
Output performance classification (according to IEC/ EN62040-3) | VFI-SS-11 | ||||
Load crest factor | 3 | ||||
Load power factor | 0.5 leading to 0.5 lagging without derating |
Specifications for Lithium-ion Battery Cabinets
LIBSESMG16UL | LIBSESMG17UL | |
---|---|---|
Charging power in % of output power | 0-40%
load: 80% 100% load: 20% |
0-40%
load: 80% 100% load: 20% |
Nominal battery voltage (VDC) at 3.8 V per cell | 486 |
517 |
Peak current at end of discharge voltage (A) |
450 |
450 |
Charge current default rate (CA rate) |
0.7 |
0.7 |
Maximum continuous charge current rate (CA rate) |
1.0 |
1.0 |
Float charge voltage (VDC) at 4.2 V per cell |
538 |
571 |
End of discharge voltage (VDC) at 3.0 V per cell |
384 |
408 |
Maximum continuous 100% depth of discharge power (kW) |
173 |
184 |
Maximum partial depth of discharge power (kW) |
218 |
231 |
Short circuit rating value (kA) - Isc, RMS (Isc, MAX) |
2.9 (9.0) |
2.9 (9.0) |
100 ℃ (212 °F).
Upstream and Downstream Protection for UL
Preconditions for Live Swap of Power Modules
Live Swap of power modules is only allowed under the following preconditions for the UPS installation; Follow either scenario 1 or scenario 2:
Preconditions for UPS installation — scenario 1 with instantaneous override values and trip times set according to the tables below in Recommended Upstream Protection for UL | Preconditions for UPS installation — scenario 2 with alternative disconnect device configurations supported with GVLOPT011 and disconnect device with ERMS mode* |
---|---|
Circuit breakers must have instantaneous trip time of maximum 50 ms. | Circuit breakers must be installed for input (unit input disconnect device UIB) and bypass (static switch input disconnect device SSIB). |
Circuit breakers must have instantaneous override values set according to the table below. | Circuit breakers (UIB, SSIB) must be equipped with NEC 240.87, NFPA70E, IEEE1584, or EN51110-1 compliant ERMS mode. |
Circuit breakers must be installed for input (unit input disconnect device UIB) and bypass (static switch input disconnect device SSIB). | For parallel systems with three or more UPSs: Circuit breakers must be installed for the output (unit output disconnect device UOB) of each UPS. The unit output disconnect device (UOB) is sized as the static switch input disconnect device (SSIB). |
For parallel system with three or more UPSs: Circuit breakers must be installed for the output (unit output disconnect device UOB) of each UPS. The unit output disconnect device (UOB) is sized as the static switch input disconnect device (SSIB). | Circuit breaker (UOB) must be equipped with NEC 240.87, NFPA70E, IEEE1584, or EN51110-1 compliant ERMS mode. |
Live Swap is not supported for >65kAbf installations where current limiting disconnect devices are used to protect the UPS. | GVLOPT011 (Galaxy VL door switch kit) must be installed in the UPS and connected so ERMS mode is set to ON on UIB and SSIB and UOB when the front door of the UPS is opened. |
In ERMS mode, the instantaneous trip current shall be set to 5000 A or less. All time-delay settings shall be set to zero. |
Schneider Electric reserves the right to remove the Live Swap label from the product front if the preconditions for scenario 1 or scenario 2 are not met.
![]() |
---|
Hazard of electric shock, explosion, or arc flash
Only perform Live Swap of the power modules in UPS installations
that follow the preconditions for scenario 1 or scenario 2.
Failure to follow these instructions will result in death or serious injury.
|
Recommended Upstream Protection for UL
The bypass/output disconnect devices are sized based on the nominal current +10%. This is to accommodate either low grid voltage or deviation in cable length between parallel UPSs. The battery disconnect devices are sized based on the end-of-discharge voltage which has been defined as 380 VDC.
UPS rating | 200 kW | 250 kW | ||
---|---|---|---|---|
Input | Bypass | Input | Bypass | |
Breaker type
Breaker type |
LJF36400CU31X | LJF36400CU31X |
LJF36400CU31X |
LJF36400CU31X |
Ir | 320 | 280 | 400 | 360 |
tr | ≥4 | ≥4 | ≥4 | ≥4 |
li (x In) | ≤12 | ≤12 | ≤12 | ≤12 |
UPS rating | 300 kW | 350 kW | 400 kW | |||
---|---|---|---|---|---|---|
Input | Bypass | Input | Bypass | Input | Bypass | |
Breaker type
Breaker type |
PJF36060CU31A |
PJF36060CU31A |
PJF36060CU31A |
PJF36060CU31A |
PJF36080CU31A | PJF36060CU31A |
Ir | 480 | 420 | 540 | 480 | 640 | 540 |
tr | ≥4 | ≥4 | ≥4 | ≥4 | ≥4 | ≥4 |
li (x In) | ≤12 | ≤12 | ≤10 | ≤12 | ≤10 | ≤12 |
UPS rating | 450 kW | 500 kW | ||
---|---|---|---|---|
Input | Bypass | Input | Bypass | |
Breaker type
Breaker type |
PJF36080CU31A | PJF36080CU31A | PJF36080CU31A | PJF36080CU31A |
Ir | 720 | 640 | 800 | 720 |
tr | ≥4 | ≥4 | ≥4 | ≥4 |
li (x In) | ≤8 | ≤10 | ≤8 | ≤10 |
Recommended Cable Sizes for UL
![]() |
---|
hazard of electric shock, explosion, or arc flash
Failure to follow these instructions will result in death or serious injury.
|
![]() |
---|
hazard of electric shock, explosion, or arc flash
Failure to follow these instructions will result in death or serious injury.
|
The maximum number of cable connections per busbar in the UPS:
-
4 on input/output/bypass busbars
-
4 x 600 kcmil on input/output/bypass busbars
-
5 x 500 kcmil or 8 x 300 kcmil on DC+/DC- busbars
-
8 on N busbar
-
16 on ground busbar
Cable sizes in this manual are based on Table 310.15 (B)(16) of the National Electrical Code (NEC) with the following assertions*:
-
90 °C (194 °F) conductors (75 °C (167 °F) termination)
-
An ambient temperature of 30 °C (86 °F)
-
Use of copper or aluminum conductors for the UPS.
-
Use of copper conductors for the Lithium-ion battery cabinet.
If the ambient temperature is greater than 30 °C (86 °F), larger conductors are to be selected in accordance with the correction factors of the NEC.
Equipment grounding conductors (EGC) are sized in accordance with the minimum requirements in NEC Article 250.122 and Table 250.122.
The bypass/output cables are sized based on the nominal current +10%. This is to accommodate either low grid voltage or deviation in length between parallel UPSs. The battery cables are sized based on end-of-discharge voltage which has been defined as 380 VDC.
Copper
UPS rating | 200 kW | 300 kW | 400 kW | 500 kW |
---|---|---|---|---|
Voltage (V) | 480 | 480 | 480 | 480 |
Input phases (AWG/kcmil) | 1 x 350 | 2 x 4/0 | 2 x 350 | 2 x 500 |
Input EGC (AWG/kcmil) | 1 x 3 | 2 x 2 | 2 x 1/0 | 2 x 1/0 |
Bypass/output phases (AWG/kcmil) | 1 x 300 | 1 x 600 | 2 x 300 | 2 x 400 |
Bypass EGC/output EGC (AWG/kcmil) | 1 x 4 | 1 x 2 | 2 x 1 | 2 x 1/0 |
DC+/DC- (AWG/kcmil) | 1 x 350 / 2 x 250 | 1 x 350 / 2 x 250 | 1 x 350 / 2 x 250 | 1 x 350 / 2 x 250 |
DC EGC (AWG/kcmil) | 1 x 350 / 2 x 250 | 1 x 350 / 2 x 250 | 1 x 350 / 2 x 250 | 1 x 350 / 2 x 250 |
Inverter midpoint cable for 3-wire parallel (AWG/kcmil) | 1 x 350 | 2 x 4/0 | 2 x 350 | 2 x 500 |
Aluminum
UPS rating | 200 kW | 300 kW | 400 kW | 500 kW |
---|---|---|---|---|
Voltage (V) | 480 | 480 | 480 | 480 |
Input phases (AWG/kcmil) | 1 x 500 | 2 x 300 | 2 x 500 | (3 x 400)* |
Input EGC (AWG/kcmil) | 1 x 1 | 2 x 1/0 | 2 x 3/0 | 3 x 3/0 |
Bypass/output phases (AWG/kcmil) | 1 x 400 | 2 x 250 | 2 x 400 | 2 x 600 |
Bypass EGC/output EGC (AWG/kcmil) | 1 x 2 | 2 x 1/0 | 2 x 2/0 | 2 x 3/0 |
Inverter midpoint cable for 3-wire parallel (AWG/kcmil) | 1 x 500 | 2 x 300 | 2 x 500 | 3 x 400 |
Guidance for Organizing Input, Bypass, And Output Cables
The input, bypass, and output cables must be grouped in circuits. On raceways, use one of the two shown cable formations.
Recommended Bolt and Lug Sizes
NOTICE |
---|
risk of equipment damage
Use only UL approved compression cable lugs.
Failure to follow these instructions can result in equipment damage.
|
Recommended Bolt and Lug Sizes for the UPS – Copper
Cable size | Bolt size | Cable lug type (one hole) | Cable lug type (two hole NEMA) | Crimping tool | Die |
---|---|---|---|---|---|
1/0 AWG | M10x35mm |
LCB1/0-12-X |
LCC1/0-12-X |
CT-930 |
CD-920-1/0 Pink P42 |
2/0 AWG | M10x35mm |
LCB2/0-12-X |
LCC2/0-12-X |
CT-930 |
CD-920-2/0 Black P45 |
3/0 AWG | M10x35mm |
LCB3/0-12-X |
LCC3/0-12-X |
CT-930 |
CD-920-3/0 Orange P50 |
4/0 AWG | M10x35mm |
LCB4/0-12-X |
LCC4/0-12-X |
CT-930 |
CD-920-4/0 Purple P54 |
250 kcmil | M10x35mm |
LCB250-12-X |
LCC250-12-X |
CT-930 |
CD-920-250 Yellow P62 |
300 kcmil | M10x35mm |
LCB300-12-X |
LCC300-12-X |
CT-930 |
CD-920-300 White P66 |
350 kcmil | M10x35mm |
LCB350-12-X |
LCC350-12-X |
CT-930 |
CD-920-350 Red P71 |
400 kcmil | M10x35mm |
LCB400-12-X |
LCC400-12-6 |
CT-930 |
CD-920-400 Blue P76 |
450 kcmil | M10x35mm | — |
LCC450-12-6 |
CT-930 | — |
500 kcmil | M10x35mm |
LCB500-12-X |
LCC500-12-6 |
CT-930 |
CD-920-500 Brown P87 |
Recommended Bolt and Lug Sizes for the Lithium-ion Battery Cabinet– Copper — One Hole Cable Lugs
Cable size | Bolt size | Cable lug type | Crimping tool | Die |
---|---|---|---|---|
2 x 250 kcmil | M10x30 | LCB250-12-X | CT-930 | CD-920-250 Yellow P62 |
350 kcmil | M10x30 | LCC350-12-X | CT-930 | CD-920-350 Red P71 |
Recommended Bolt and Lug Sizes for the Lithium-ion Battery Cabinet– Copper — Two Hole Cable Lugs
Cable size | Bolt size | Cable lug type | Crimping tool | Die |
---|---|---|---|---|
2 x 250 kcmil | M10x30 | LCC250-12-X | CT-930 | CD-920-250 Yellow P62 |
350 kcmil | M10x30 | LCC350-12-X | CT-930 | CD-920-350 Red P71 |
Recommended Bolt and Lug Sizes for the UPS – Aluminum
Cable size | Bolt size | Cable lug type (one hole) | Cable lug type (two hole NEMA) | Crimping tool | Die |
---|---|---|---|---|---|
1/0 AWG | M10x35mm |
LAA1/0-12-5 |
LAB1/0-12-X |
CT-930 |
CD-920-1/0 Pink P42 |
2/0 AWG | M10x35mm |
LAA2/0-12-5 |
LAB2/0-12-5 |
CT-930 |
CD-920-2/0 Black P45 |
3/0 AWG | M10x35mm |
LAA3/0-12-5 |
LAB3/0-12-5 |
CT-930 |
CD-920-3/0 Orange P50 |
4/0 AWG | M10x35mm |
LAA4/0-12-5 |
LAB4/0-12-5R |
CT-930 |
CD-920-4/0 Purple P54 |
250 kcmil | M10x35mm |
LAA250-12-5 |
LAB250-12-5 |
CT-930 |
CD-920-250 Yellow P62 |
300 kcmil | M10x35mm |
LAA300-12-2 |
LAB300-12-2 |
CT-930 |
CD-920-300 White P66 |
350 kcmil | M10x35mm |
LAA350-12-2 |
LAB350-12-2R |
CT-930 |
CD-920-350 Red P71 |
400 kcmil | M10x35mm | — |
LAB400-12-2 |
CT-930 |
CD-920-400 Blue P76 |
500 kcmil | M10x35mm |
LAA500-12-2 |
LAB500-12-2R |
CT-930 |
CD-920-500 Brown P87 |
Inverter Short Circuit Capabilities (Bypass not Available)
IK1 – Short Circuit between a Phase and Neutral
IK1 480 V
S [kVA] |
10ms; I[A]/I2t [A2t] | 20ms; I[A]/I2t [A2t] | 30ms; I[A]/I2t [A2t] | 100ms; I[A]/I2t [A2t] | 1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
200 |
560 /3090 |
560 /6180 |
560 /9280 |
480 /29020 |
380 /167430 |
250 |
700 /4830 |
700 /9660 |
700 /14490 |
610 /45350 |
480 /261610 |
300 |
830 /6960 |
830 /13910 |
830 /20870 |
730 /65300 |
570 /376720 |
350 |
970 /9470 |
970 /18940 |
970 /28410 |
850 /88880 |
670 /512750 |
400 |
1110 /12370 |
1110 /24740 |
1110 /37100 |
970 /116090 |
760 /669720 |
450 |
1250 /15650 |
1250 /31310 |
1250 /46960 |
1090 /146930 |
860 /847610 |
500 |
1390 /19330 |
1390 /38650 |
1390 /57970 |
1210 /181390 |
950 /1046430 |
IK2 – Short Circuit between Two Phases
IK2 480 V
S [kVA] |
10ms; I[A]/I2t [A2t] | 20ms; I[A]/I2t [A2t] | 30ms; I[A]/I2t [A2t] | 100ms; I[A]/I2t [A2t] | 1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
200 |
560 /3150 |
560 /6280 |
560 /9350 |
470 /27550 |
370 /158630 |
250 |
700 /4920 |
700 /9810 |
700 /14610 |
590 /43050 |
460 /247850 |
300 |
840 /7090 |
840 /14130 |
840 /21040 |
700 /61990 |
550 /356910 |
350 |
980 /9640 |
980 /19230 |
980 /28640 |
820 /84380 |
650 /485790 |
400 |
1120 /12600 |
1120 /25110 |
1120 /37410 |
940 /110210 |
740 /634500 |
450 |
1260 /15940 |
1250 /31790 |
1250 /47350 |
1050 /139480 |
830 /803040 |
500 |
1400 /19680 |
1390 /39240 |
1390 /58450 |
1170 /172200 |
920 /991410 |
IK3 – Short Circuit between Three Phases
IK3 480 V
S [kVA] |
10ms; I[A]/I2t [A2t] | 20ms; I[A]/I2t [A2t] | 30ms; I[A]/I2t [A2t] | 100ms; I[A]/I2t [A2t] | 1s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
200 |
500 /2470 |
500 /4950 |
500 /7420 |
480 /24390 |
380 /159310 |
250 |
620 /3870 |
620 /7730 |
620 /11600 |
600 /38110 |
470 /248920 |
300 |
750 /5570 |
750 /11140 |
750 /16700 |
720 /54880 |
570 /358450 |
350 |
870 /7580 |
870 /15160 |
870 /22740 |
840 /74690 |
660 /487890 |
400 |
990 /9900 |
990 /19800 |
990 /29700 |
960 /97560 |
750 /637240 |
450 |
1120 /12530 |
1120 /25060 |
1120 /37580 |
1070 /123470 |
850 /806510 |
500 |
1240 /15470 |
1240 /30930 |
1240 /46400 |
1190 /152440 |
940 /995690 |
Torque Specifications
Bolt size | Torque for UPS | Torque for Lithium-ion battery cabinet |
---|---|---|
M4 | 1.7 Nm (1.25 lb-ft / 15 lb-in) | 1.7 Nm (1.25 lb-ft / 15 lb-in) |
M5 | 2.2 Nm (1.62 lb-ft / 19.5 lb-in) | NA |
M6 | 5 Nm (3.69 lb-ft / 44.3 lb-in) | 5 Nm (3.69 lb-ft / 44.3 lb-in) |
M8 | 17.5 Nm (12.91 lb-ft / 154.9 lb-in) |
14 Nm (10.33 lb-ft) |
M10 | 30 Nm (22 lb-ft / 194.7 lb-in) |
30 Nm (22.13 lb-ft) |
M12 | 50 Nm (36.87 lb-ft / 442.5 lb-in) |
46 Nm (33.93 lb-ft) |
Environment
Operating | Storage | |||
---|---|---|---|---|
UPS | Lithium-ion battery cabinet | UPS | Lithium-ion battery cabinet | |
Temperature | 0
°C to 40 °C (32 °F to 104 °F) without load derating. 40 °C to 50 °C (104 °F to 122 °F) when derated to 70% power. |
Recommended operating temperature is 18 °C to 28 °C (64 °F to 82 °F) |
-25 °C to 55 °C (-13 °F to 131 °F) for systems without batteries. |
Lithium-ion battery cabinet: 0 °C to 40 °C (32 °F to 104 °F) Battery modules: Recommended storage for battery modules is 20 °C (68 °F) or cooler (non-freezing) |
Relative humidity | 5-95% non-condensing |
0-95% non-condensing |
10-80% non-condensing |
Lithium-ion battery cabinet: 0-90% non-condensing Lithium-ion battery modules: Recommended storage for battery modules is 40-80% non-condensing |
Elevation | Designed for operation in 0-3000 m (0-10000 feet) elevation. Derating required from 1000-3000 m (3300-10000 feet) with forced air cooling: Up to 1000 m (3300 feet): 1.000 Up to 1500 m (5000 feet): 1.000 conditioned by 2 x 300 mm2 input cables at 500 kW Up to 1500 m (5000 feet) : 0.975 Up to 2000 m (6600 feet): 1.000 conditioned by 2 x 300 mm2 input cables at 500 kW Up to 2000 m (6600 feet): 0.950 Up to 2500 m (8300 feet): 0.975 conditioned by 2 x 300 mm2 input cables at 500 kW Up to 2500 m (8300 feet): 0.925 Up to 3000 m (10000 feet): 0.950 conditioned by 2 x 300 mm2 input cables at 500 kW Up to 3000 m (10000 feet): 0.900 Derating required from 1000-3000 m (3300-10000 feet) with convection cooling: Up to 1000 m (3300 feet): 1.000 Up to 1500 m (5000 feet) : 0.985 Up to 2000 m (6600 feet): 0.970 Up to 2500 m (8300 feet): 0.955 Up to 3000 m (10000 feet): 0.940 |
0-3000 m (0-10000 feet) | ||
Audible noise one meter (three feet) from unit |
62 dB at 70% load 68 dB at 100% load for 480 V systems |
|||
Protection class | IP20 | IP20 | ||
Color | RAL 9003, gloss level 85% | RAL 9003, gloss level 85% |
Compliance
UPS | Lithium-ion battery cabinet | |
Safety | IEC
62040-1: 2017, Edition 2.0, Uninterruptible Power Systems (UPS) -
Part 1: Safety requirements UL 1778 5th edition |
IEC 62619:2017 Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety requirements for secondary lithium cells and batteries, for use in industrial applications IEC 62477-1:2012+A11:2014 Safety requirements for power electronic converter systems and equipment Part 1: General UL 1973:2022 Batteries for Use in Stationary, Vehicle Auxiliary and Light Electric Rail Applications UL 9540A:2019 Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems |
EMC/EMI/RFI | IEC
62040-2: 2016-11, 3rd edition Uninterruptible Power Systems (UPS)
- Part 2: Electromagnetic compatibility (EMC) requirements C2 FCC Part 15 Subpart B, Class A |
IEC 62040-2:2016 Uninterruptible Power Systems (UPS) - Part 2: Electromagnetic compatibility (EMC) requirements C2 FCC Part 15, Radio Frequency Devices, class A |
Performance |
Performance in accordance with: IEC 62040-3: 2021-04, 3rd edition Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the performance and test requirements. |
— |
Environmental |
IEC 60068-2-1:2007 Environmental testing – Part 2-1: Tests – Test A: Cold IEC 60068-2-2:2007 Environmental testing – Part 2-2: Tests – Test B: Dry heat IEC 60068-2-78:2012 Environmental testing – Part 2-78: Tests – Test Cab: Damp heat, steady state |
|
Markings |
UL1778 Listing and CSA C22.2 NO.107.3 |
ANSI/CAN/UL 1973 Listing |
Transportation | IEC 60721-4-2 Level 2M2 |
IEC60068-2-27:2008 Environmental testing – Part 2-27: Tests – Test Ea and guidance: Shock IEC60068-2-31:2008 Environmental testing – Part 2-31: Tests – Test Ec: Rough handling shocks, primarily for equipment-type specimens IEC60068-2-64:2008 Environmental testing – Part 2-64: Tests – Test Fh: Vibration, broadband random and guidance |
Seismic | ICC-ES AC 156 (2015); OSHPD Pre-approved; Sds=1.45 g for z/h=1 and Sds=2.00 g for z/h=0; Ip=1.5 |
OSHPD, CBC 2019, SDS=2.0g (z/h = 1); 2.5g (z/h = 0) |
Earthing system* | TN,
TT, TNC, IT, TN-S, TNC-S Solid-grounded, HRG |
|
Overvoltage category | This
UPS is OVCII compliant. If the UPS is installed in an environment with an OVC rating higher than II, an SPD (surge protection device) must be installed upstream of the UPS to reduce the overvoltage category to OVCII. |
II |
Protective class | I | |
Pollution degree | 2 |
Guidance for Organizing Battery Cables
Weights and Dimensions
UPS Weights and Dimensions
UPS rating | Weight kg (lbs) | Height mm (in) | Width mm (in) | Depth mm (in) |
---|---|---|---|---|
200 kW | 550 (1212) | 1970 (78) | 850 (33) | 925 (36) |
300 kW | 626 (1380) | 1970 (78) | 850 (33) | 925 (36) |
400 kW | 702 (1547) | 1970 (78) | 850 (33) | 925 (36) |
500 kW | 778 (1715) | 1970 (78) | 850 (33) | 925 (36) |
Lithium-ion Battery Cabinet Weights and Dimensions
Weight kg (lbs) | Height mm (in) | Width mm (in) | Depth mm (in) | |
---|---|---|---|---|
LIBSESMG16UL |
470 (1036) |
1970 (78) |
650 (25.59) |
587 (23.11) |
LIBSESMG17UL |
490 (1080) |
1970 (78) |
650 (25.59) |
587 (23.11) |