Corriente nominal de cortocircuito del interruptor de seguridad sin fusibles
Interruptores de seguridad sin fusibles, NEMA tipo 7/9 SCCR 10 kAIR de 600 VCA máximo
Capacidad del interruptor |
Tipo de fusible o interruptor * |
240 VCA |
480 VCA |
600 VCA |
250 VCC |
---|---|---|---|---|---|
Valores nominales del interruptor (A) |
Con protección de fusibles ascendentes |
240 VCA |
480 VCA |
600 VCA |
250 VCC/600 VCC |
TODOS |
H, K |
10 kA |
10 kA |
10 kA |
Hasta 10 kA |
R, T, J, L |
200 kA |
200 kA |
200 kA |
Hasta 10 kA |
|
Valores nominales del interruptor (A) |
Con protección de interruptor automático ascendente |
240 VCA |
480 VCA |
600Y/347 VCA |
250 VCC |
30, 60, 100 |
BD |
25 kA |
18 kA |
14 kA |
Hasta 10 kA |
30, 60, 100 |
BG |
65 kA |
35 kA |
18 kA |
Hasta 10 kA |
30, 60, 100 |
BJ |
100 kA |
65 kA |
25 kA |
Hasta 10 kA |
30, 60, 100 |
BK |
100 kA |
65 kA |
65 kA |
Hasta 10 kA |
Valores nominales del interruptor (A) |
Con protección de interruptor automático ascendente |
240 VCA |
480 VCA |
600 VCA |
250 VCC |
TODOS |
Interruptor automático de cualquier marca |
10 kA |
10 kA |
10 kA |
Hasta 10 kA |
30, 60, 100 |
HD |
25 kA |
18 kA |
14 kA |
Hasta 10 kA |
30, 60, 100 |
HG |
65 kA |
35 kA |
18 kA |
Hasta 10 kA |
30, 60, 100 |
HJ |
65 kA |
35 kA |
18 kA |
Hasta 10 kA |
30, 60, 100 |
HL |
65 kA |
35 kA |
35 kA |
Hasta 10 kA |
30, 60, 100 |
HR |
65 kA |
35 kA |
35 kA |
Hasta 10 kA |
30, 60, 100 |
FA |
14 kA |
14 kA |
14 kA |
Hasta 10 kA |
30, 60, 100 |
FH |
18 kA |
18 kA |
18 kA |
Hasta 10 kA |
200 |
HD, JD |
25 kA |
18 kA |
14 kA |
Hasta 10 kA |
200 |
HG, JG |
65 kA |
35 kA |
18 kA |
Hasta 10 kA |
200 |
HJ, JJ |
65 kA |
65 kA |
25 kA |
Hasta 10 kA |
200 |
HL, JL |
65 kA |
35 kA |
35 kA |
Hasta 10 kA |
200 |
HR, JR |
65 kA |
35 kA |
35 kA |
Hasta 10 kA |
400 |
LA |
25 kA |
25 kA |
25 kA |
Hasta 10 kA |
400 |
LH |
25 kA |
25 kA |
25 kA |
Hasta 10 kA |
400, 600 |
LD |
25 kA |
18 kA |
14 kA |
Hasta 10 kA |
400, 600 |
LG |
65 kA |
35 kA |
18 kA |
Hasta 10 kA |
400, 600 |
LJ |
100 kA |
65 kA |
25 kA |
Hasta 10 kA |
400, 600 |
LL |
100 kA |
65 kA |
50 kA |
Hasta 10 kA |
400, 600 |
LR |
100 kA |
65 kA |
65 kA |
Hasta 10 kA |