JYT97577–01

Appendix A - System Communication Schematics

NOTE: The notice below pertains to all figures in this appendix.
NOTICE
HAZARD OF equipment damage, loss of operation
  • Maximize the distance between and segregate the 24 VDC and communications wiring from potentially noisy circuit breaker power cables.
  • If 24 VDC and communications wiring must cross power cables, cross as close to 90 degrees to the power cables as possible.
  • Limit parallel runs of control cable and power cables to the absolute minimum possible.
  • Flatten control cables and route along metallic structure when possible. Do not create loops with surplus cabling.
Failure to follow these instructions can result in equipment damage.

MMS I-LEM Communication Schematic Diagram

MMS I-LEM Communication Schematic Diagram

MMS I-LEM Comms Legend

A

Circuit Breaker Communication Module ULP (BCM)

E

MicroLogic Trip Unit (P or H) 

B

OF, SD, SDE, PF, and CH switches

F

Zone Selective Interlocking Connections, Twisted Pair Cable

C

COM Terminal Block (E1 to E6) for communications via ULP Cord

G

24 VDC Power Output, Twisted Pair Cable

D

Shunt Trip (MX1) and Shunt Close (XF) communicating voltage releases (on electrically operated devices only)

H

MMS I-Line Enable Module

ERMS I-LEM Communication Schematic Diagram

ERMS I-LEM Communication Schematic Diagram

ERMS I-LEM Comms Legend

A

Circuit Breaker Communication Module ULP (BCM)

F

Breaker ULP Cord, LV434197

B

OF, SD, SDE, PF, and CH switches

G

24 VDC Power Output, Twisted Pair Cable

C

COM Terminal Block (E1 to E6) for communications via ULP Cord

H

Ethernet Cable

D

Shunt Trip (MX1) and Shunt Close (XF) communicating voltage releases (on electrically operated devices only)

J

ERMS I-Line Enable Module

E

MicroLogic Trip Unit (P or H) 

   

ERMS I-LEM with Communicating Circuit Breakers Communication Schematic Diagram

ERMS I-LEM with Communicating Circuit Breakers Communication Schematic Diagram

ERMS I-LEM with Communicating Circuit Breakers Comms Legend

A

Circuit Breaker Communication Module ULP (BCM or BSCM)

G

24 VDC Power Output, Twisted Pair Cable

B

OF, SD, SDE, PF, and CH switches

H

Modbus Serial Cable

C

COM Terminal Block (E1 to E6) for communications via ULP Cord

J

Ethernet Cable

D

Shunt Trip (MX1) and Shunt Close (XF) communicating voltage releases (on electrically operated devices only)

K

ERMS I-Line Enable Module

E

MicroLogic Trip Unit (P or H only for Circuit Breaker with ERMS)

L

U–PaS I-Line Enable Module

F

Circuit Breaker ULP Cord, LV434197

M

IFM I-Line Enable Module

ERM2 I-LEM Communication Schematic Diagram

ERM2 I-LEM Communication Schematic Diagram

ERM2 I-LEM Comms Legend

A

Circuit Breaker Communication Module ULP (BCM or BSCM)

F

Circuit Breaker ULP Cord, LV434197

B

OF, SD, SDE, PF, and CH switches

G

24 VDC Power Output, Twisted Pair Cable

C

COM Terminal Block (E1 to E6) for communications via ULP Cord

H

Modbus Serial Cable

D

Shunt Trip (MX1) and Shunt Close (XF) communicating voltage releases (on electrically operated devices only)

J

ERMS I-Line Enable Module

E

MicroLogic Trip Unit (P or H only for Circuit Breaker with ERMS)

   

IFM I-LEM Communication Schematic Diagram

IFM I-LEM Communication Schematic Diagram

IFM I-LEM Comms Legend

A

Circuit Breaker Communication Module ULP (BCM or BSCM)

F

Circuit Breaker ULP Cord, LV434197

B

OF, SD, SDE, PF, and CH switches

G

24 VDC Power Output, Twisted Pair Cable

C

COM Terminal Block (E1 to E6) for communications via ULP Cord

H

Modbus Serial Cable

D

Shunt Trip (MX1) and Shunt Close (XF) communicating voltage releases (on electrically operated devices only)

J

IFM I-Line Enable Module

E

MicroLogic Trip Unit

   

U-PaS I-LEM Communication Schematic Diagram

U-PaS I-LEM Communication Schematic Diagram

U-PaS I-LEM Comms Legend

A

Circuit Breaker Communication Module ULP (BCM or BSCM)

G

24 VDC Power Output, Twisted Pair Cable

B

OF, SD, SDE, PF, and CH switches

H

Modbus Serial Cable

C

COM Terminal Block (E1 to E6) for communications via ULP Cord

J

Ethernet Cable

D

Shunt Trip (MX1) and Shunt Close (XF) communicating voltage releases (on electrically operated devices only)

K

U-PaS I-Line Enable Module

E

MicroLogic Trip Unit

L

IFM I-Line Enable Module

F

Circuit Breaker ULP Cord, LV434197

   

Power Meter I-LEM Communication Schematic Diagram

Power Meter I-LEM Communication Schematic Diagram

Power Meter I-LEM Comms Legend

H

Modbus Serial Cable

J

Ethernet Cable

K

5 A Current Transducers

L

Power Meter I-Line Enable Module

Power Meter I-LEM with Communicating Circuit Breakers Communication Schematic Diagram

Power Meter I-LEM with Communicating Circuit Breakers Communication Schematic Diagram

Power Meter I-LEM with Communicating Circuit Breakers Comms Legend

A

Circuit Breaker Communication Module ULP (BCM or BSCM)

H

Modbus Serial Cable

B

OF, SD, SDE, PF, and CH switches

J

Ethernet Cable

C

COM Terminal Block (E1 to E6) for communications via ULP Cord

K

5 A Current Transducers

D

Shunt Trip (MX1) and Shunt Close (XF) communicating voltage releases (on electrically operated devices only)

L

Power Meter I-Line Enable Module

E

MicroLogic Trip Unit

M

U–PaS I-Line Enable Module

F

Circuit Breaker ULP Cord, LV434197

N

IFM I-Line Enable Module

G

24 VDC Power Output, Twisted Pair Cable

   
QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?