Using the DeviceNet Communication Network
Overview
This chapter describes how to use the LTMR controller via the network port using the DeviceNet protocol.
![]() |
---|
LOSS OF CONTROL
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
|
(1) For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control".
![]() |
---|
UNEXPECTED RESTART OF THE MOTOR
Check that the PLC application software:
When switching to the Network control channels,
depending on the communication protocol configuration, the LTMR controller can take into account the latest
known state of the motor control commands issued from the PLC and
restart automatically the motor.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
|
DeviceNet Protocol Principles
Overview
The DeviceNet low-level controller area network (CAN) provides a communication link between simple industrial devices (such as actuators and sensors) and controlling devices.
The network carries control data and the properties of the device being controlled. It enables you to operate either in a primary/secondary mode or a peer-to-peer mode.
The DeviceNet powered 4-wire network operates in a trunk line/drop line configuration and supports up to 64 nodes.
Two main types of messages can be exchanged:
-
I/O messaging, dedicated to fast exchanges of process data.
-
Explicit messaging, dedicated to slower exchanges such as configuration, settings, or diagnostics data.
Connections and Data Exchange
I/O Messaging
I/O messages contain application-specific data. They are communicated across single or multicast connections between an application producer and its corresponding consuming application. Because I/O messages carry time-critical messages, they have high-priority identifiers.
An I/O Message consists of a Connection ID and associated I/O data. The meaning of the data within an I/O Message is implied by the associated Connection ID. The connection endpoints are assumed to have knowledge of the intended use or meaning of the I/O Message.
I/O Message Types
Secondary devices can produce data using one or more of the following I/O message types, depending on how the device is configured and the requirements of the application:
Type |
Description of Operation |
---|---|
Polled |
A secondary configured for polled I/O receives output data from the primary device. This data is received in a sequential order that is defined by the primary’s scan list. The primary’s polling rate is determined by the number of nodes in the scan list, the DeviceNet baud rate, the size of messages produced by the primary and each node in its scan list, and the internal timing of the primary device. |
Cyclic |
A device configured to produce a cyclic I/O message will produce its data at a precisely defined interval. This type of I/O messaging allows the user to configure the system to produce data at a rate appropriate for the application. Depending on the application this can reduce the amount of traffic on the wire and more efficiently use the available bandwidth. |
Change-of-state |
A device configured to produce a change-of-state (COS) message will produce data whenever it changes, or at a base heartbeat rate. This adjustable heartbeat rate enables the consuming device to verify that the producer is still present and active on the network. DeviceNet also defines a user-configurable Production Inhibit Time that limits how often COS messages are produced to prevent nodes from flooding the bandwidth. Users can adjust these parameters to provide optimum bandwidth utilization in a given application. |
Explicit Messaging
Explicit messaging connections provide multipurpose point-to-point communication paths between two particular devices. Explicit messages are used to command the performance of a particular task and to report the results of performing the task. You can therefore, use explicit messaging connections to configure nodes and diagnose problems.
DeviceNet defines an explicit messaging protocol that states the meaning or intended use of an explicit message within the CAN (Controller Area Network) data field. The message consists of a Connection ID and associated messaging protocol information.
Idle Message Management
When the LTMR controller receives an Idle Message sent by the DeviceNet network primary, it generates a communication loss and the LTMR controller is in fallback condition.
The conditions to exit the idle mode are the same as to exit the fallback condition.
Simplified Control and Monitoring
Configuration of the LTMR DeviceNet Network Port
Communication Parameters
Use the TeSys T DTM or the HMI to configure the DeviceNet communication parameters:
-
Network Port Address Setting
-
Network Port Baud Rate Setting
-
Config Via Network Port Enable
Setting the MAC-ID
The MAC-ID is the address of the module on the DeviceNet bus. A DeviceNet network is limited to 64 addressable nodes (node IDs 0 to 63). This means that you can assign a MAC-ID of 0-63.
You must set the MAC-ID before any communication can start. To do this, use the TeSys T DTM or the HMI to configure the communication parameter Network Port Address Setting. The factory setting for the address is 63.
Setting the Baud Rate
You can also set a baud rate of the following speeds:
-
125 kBaud
-
250 kBaud
-
500 kBaud
To set the baud rate, use the TeSys T DTM or the HMI to configure the communication parameter Network Port Baud Rate Setting.
The parameter has the following possible settings:
Network Port Baud Rate Setting |
Baud Rate |
---|---|
0 |
125 kBaud (factory setting) |
1 |
250 kBaud |
2 |
500 kBaud |
3 |
Autobaud |
Autobaud automatically detects the baud rate required.
Setting the Configuration Channel
The LTMR configuration can be managed via two different modes:
-
Locally through the HMI port using the TeSys T DTM or the HMI
-
Remotely through the network
To manage the configuration locally, parameter Config Via Network Port Enable must be disabled to prevent overwriting of the configuration through the network.
To manage the configuration remotely, parameter Config Via Network Port Enable must be enabled (factory setting).
Device Profiles and EDS Files
Device Profiles
DeviceNet’s device models define the physical connections and promote interoperability among standard devices.
Devices that implement the same device model must support common identity and communications status data. Device-specific data is contained in device profiles that are defined for various device types. Typically, a device profile defines the device’s:
-
Object model
-
I/O data format
-
Configurable parameters
The above information is made available to other vendors through the device’s EDS (electronic data sheet).
For a full description of the objects in the LTMR device profile, refer to the Object Dictionary.
What’s an EDS?
The EDS is a standardized ASCII file that contains information about a network device’s communications functionality and the contents of its object dictionary Object Dictionary, as defined by ODVA (Open DeviceNet Vendor Association). The EDS also defines device-specific and manufacturer-specific objects.
Using the EDS, you can standardize tools to:
-
Configure DeviceNet devices
-
Design networks for DeviceNet devices
-
Manage project information on different platforms
The parameters of a particular device depend on those objects (parameter, application, communications, emergency, and other objects) that reside on the device.
LTMR Controller EDS Files
EDS files and associated icons that describe the various configurations of the LTMR Controller can be downloaded from www.se.com website ( ).
EDS files and icons are grouped in a single compressed Zip file that you must unzip to a single directory on your hard disk drive.
For information on how to register these EDS files in the RSNetworx's EDS library System, refer to Register the Controller’s EDS.
Configuring the DeviceNet network
Introduction
Use these sample instructions to configure for example a Rockwell Automation® SLC-500 PLC (1747-SDN) with a DeviceNet controller at the head of a TeSys T Motor Management system. The configuration software is RSNetworx for DeviceNet configuration software. The stages of this process are described in the following table:
Before You Begin
Before you begin, make sure:
-
The TeSys T Motor Management system is fully assembled, installed, and powered according to your particular system, application, and network requirements.
-
You have properly set the network port of the controller.
-
You have the basic EDS files and corresponding .ico files that are available at www.se.com), or you have generated an EDS that is specific to the system assembly.
To configure the controller using RSNetWorx, you must have a working familiarity with both the DeviceNet fieldbus protocol and RSNetWorx for DeviceNet. (The described procedures cannot practically anticipate every prompt or option you may encounter during configuration.)
Connection Figure
Before assembling the network, familiarize yourself with the required hardware connections. The following figure shows the DeviceNet network connections between an Allen-Bradley PLC, the controller, and RSNetWorx:

1 Allen-Bradley SLC-500 PLC
2 PLC processor module
3 1747-SDN DeviceNet scanner module
4 DeviceNet network cable
5 LTMR controller
6 PC running RSNetWorx (properly connected to your network)
7 Power tap
8 DeviceNet power supply 24 Vdc
The scanner module is the control mechanism for all network traffic. It reads and writes every piece of I/O data that is moved on the network.
Assemble the Physical Network
The following procedure describes the connections required to construct a physical DeviceNet network.
Step |
Action |
Comment |
||
---|---|---|---|---|
1 |
Install the DeviceNet scanner module in the desired PLC slot. |
The connection figure above shows the scanner in slot 2 of the PLC. |
||
2 |
Check that the desired DeviceNet network node address and baud rate have been correctly set. |
This example uses an address of 4. |
||
3 |
Make connections with DeviceNet network cable and end connectors, manufactured in accordance with ODVA specifications. |
The cable and end connectors are not supplied. |
||
4 |
Place the system on the network by connecting the PLC to the LTMR controller with the DeviceNet cable. |
|||
5 |
Connect the RSNetWorx PC to the network using the DeviceNet cable. |
Register the Controller’s EDS
To register the controller’s EDS in RSNetWorx’s EDS library:
Selection Criteria for TeSys T LTMR Controller Variants
There are four EDS files corresponding to the four possible configurations of the TeSys T Motor Management controller system:
Choose... |
When You Want to Use... |
---|---|
TeSys T MMC L |
A TeSys T Motor Management controller system without an expansion module, configurable via the HMI port. This variant enables you to preserve your local configuration. |
TeSys T MMC L EV40 |
A TeSys T Motor Management controller system with expansion module, configurable via the HMI port. This variant enables you to preserve your local configuration. |
TeSys T MMC R |
A TeSys T Motor Management controller system without expansion module configurable via the network. |
TeSys T MMC R EV40 |
A TeSys T Motor Management controller system with expansion module configurable via the network. |
In local configuration mode, the parameter Config via Network Port Enable must be disabled. This mode preserves the local configuration made using the Magelis XBT or SoMove with the TeSys T DTM through the HMI port and prevents PLC configuration via the network.
In remote configuration mode, the parameter Config via Network Port Enable must be enabled. This enables the PLC to remotely configure the L R controller.
The Config via Network Port Enable parameter is set by default.
Connect Devices to Your Network
This example requires you to add two devices to your project view:
-
An LTMR controller without expansion module configured in remote mode with the address 4.
-
A DeviceNet scanner in PLC slot 2 with the address 1
You can use RSNetWorx to configure the devices in either offline or online mode:
-
Offline-The configuration tool and the physical network are not connected.
-
Online-The configuration tool is connected to the physical network. Build the network using the parameters transferred from devices on the physical network.
Connect to network connections using either the offline or online procedures in the tables that follow. (These are standard RSNetWorx procedures.)
Offline Device Connection
Use this procedure for adding devices to your network when the configuration tool is offline:
Step |
Action |
Comment |
---|---|---|
1 |
From the Hardware list, double-click on the controller EDS named TeSys T MMC R under Schneider Automation, Inc.\Motor Starter. |
The new device appears in the project view. The lowest available MAC ID has been assigned to it, even if that ID is inappropriate. |
2 |
Double-click on the controller graphic. |
The controller’s properties window appears. |
3 |
Change the MAC ID in the Address text field to 4. |
4 is the MAC ID used throughout this example. |
4 |
Click OK. |
|
5 |
Repeat steps 1 to 4 to add the 1747-SDN Scanner Module to the network with MAC ID 00. |
The scanner’s EDS is in the Hardware list at Rockwell Automation - Allen Bradley/Communication Adapter. |
6 |
Save your configuration by choosing Save as from the File menu. |
Save offline configurations for later use. |
Online Device Connection
Use this procedure for adding devices to your network when the DeviceNet network is already assembled and the configuration tool is online:
Step |
Action |
Comment |
---|---|---|
1 |
From the Network menu, select Online. |
The Browse for network screen appears. |
2 |
Set a communication path to select a path, based on your system and application requirements. Click OK. |
When the Browsing network screen finishes, the physically connected devices will appear in the project view. |
3 |
Save your configuration by choosing Save as from the File menu. |
Save the configuration for later use. |
The RSNetWorx Project View
Read and Write LTMR Controller Parameters
To read and write to the controller's parameters:
Step |
Action |
Comment |
---|---|---|
1 |
From the project view, double-click on the controller icon. |
The controller configuration screen appears. |
2 |
Select the Parameter tab. |
The parameter list appears. |
3 |
Select Group View. |
|
4 |
Select configuration group 1, 2, or 3 to access controller configuration parameters. |
For controllers used without expansion modules:
For more details, refer to Register Map - Organization of Communication Variables for a complete list of communication variables. |
5 |
Select the parameter you want to access and read from or write to it. |
Write access to parameters is only available with TeSys T MMC R and TeSys T MMC R EV40. |
The TeSys T MMC R Parameter Screen
Select Data Exchanged via I/O Messaging
To select data exchanged through I/O messaging
Step |
Action |
Comment |
---|---|---|
1 |
In the TeSys T MMC R parameter screen, select DeviceNet Interface Group. |
The parameter list appears. |
2 |
For the PollProdPath parameter, select the input assembly object you want the controller to produce. |
PollProdPath consists of data produced by the controller on polling sent by the scanner. |
3 |
For the PollConsPath parameter, select the output assembly object you want the controller to consume. |
PollConsPath consists of data sent by polling by the scanner and consumed by the controller. |
4 |
For the COSProdPath parameter, select the Input Assembly object you want the controller to produce. |
COSProdPath consists of data produced by the controller on Change-of-State (COS). |
5 |
If you selected Input Assembly object 110 or 113 in steps 2 or 4, adjust the LTMR Monitoring Word 0 to 3 to the register you want the controller to produce. |
Only used with instances 110 and 113. |
Upload and Download Device Configurations
After the online connection of devices, you must transfer the required device information.
Use the following options from the Device menu to transfer the configurations of only selected devices:
-
Download to Device-Transfer the offline configuration from the PC to the device.
-
Upload from Device-Transfer the configuration from the device to the PC.
Use the following options from the Network menu to transfer the configurations of all online devices in the project view:
-
Download to Network-Transfer the offline configurations from the PC to all online devices.
-
Upload from Network-Transfer the configurations of all online devices to the PC.
Add the Controller to the Scanlist
To be recognized on the network, the controller must be added to the primary scanner’s Scanlist using the online procedure in the following table:
Step |
Action |
Comment |
---|---|---|
1 |
From the project view, double-click the scanner icon. |
The scanner configuration screen appears. |
2 |
Select the Scanlist tab. |
The Scanner Configuration Applet screen appears. |
3 |
Select Upload from scanner. |
Wait for the Uploading from Scanner timer to finish. |
4 |
At the Scanlist tab, highlight the controller (at MAC ID 4) in the Available Devices list, and click the right arrow. |
|
5 |
With the controller selected, click the Edit I/O Parameters button. |
The Edit I/O Parameters window appears. |
6 |
Check Polled and enter the correct input size and correct output size (depending on assembly objects previously selected). |
The determination of the controller input and output data sizes is described in the next paragraph. |
7 |
Click OK. |
The Edit I/O Parameters window closes. |
8 |
Click Download to scanner. |
The Downloading Scanlist from Scanner window appears. |
9 |
Click Download. |
Wait for the Downloading to Scanner timer to finish. |
10 |
Click OK. |
The scanner properties window closes. |
The Edit I/O Parameters Screen
Depending on your requirements, you can select one of three transmission modes:
-
Polled
-
Change of State
-
Cyclic
You have to enter the number of input and output bytes produced by the controller. The primary device needs this information to allocate data space for each network node.
The number of input and output bytes the controller produces depends on the instances you select for the DeviceNet Interface object.
The following tables show the byte size of each assembly object you can select for I/O messaging.
Output Assembly data size (consumed by the controller):
Instance |
Name |
Number of Bytes |
---|---|---|
2 |
Basic Overload |
1 |
3 |
Basic Motor Starter |
1 |
4 |
Extended Contactor |
1 |
5 |
Extended Motor Starter |
1 |
100 |
LTMR Control Registers |
6 |
101 |
PKW Request Object |
8 |
102 |
PKW Request and Extended Motor Starter |
10 |
103 |
PKW Request and LTMR Control Registers |
14 |
Input Assembly data size (produced by the controller):
Instance |
Name |
Number of Bytes |
---|---|---|
50 |
Basic Overload |
1 |
51 |
Extended Overload |
1 |
52 |
Basic Motor Starter |
1 |
53 |
Extended Motor Starter 1 |
1 |
54 |
Extended Motor Starter 2 |
1 |
110 |
LTMR Monitoring Registers (with dynamic configuration) |
8 |
111 |
PKW Response Object |
8 |
112 |
PKW Response and Extended Motor Starter |
10 |
113 |
PKW Response and LTMR Monitoring Registers |
16 |
Create an EDS for the Controller
Devices that do not correspond to specific EDS files during online network browsing will appear in the project view as Unrecognized Devices. If your controller is not recognized, you must create an EDS using the following procedure:
Step |
Action |
Comment |
---|---|---|
1 |
In the project view, double-click the controller. |
You will be asked if you want to register the controller with the EDS Wizard. |
2 |
Click Yes. |
The Wizard’s welcome screen appears. |
3 |
Click Next. |
The Options screen appears. |
4 |
Select Create an EDS file and click Next. |
RSNetWorx will upload the controller’s identity information, displayed in the Device Description screen. |
5 |
Record the product name string, LTM1, and click Next. |
The Input/Output screen appears. |
6 |
Check Polled and enter the appropriate values for input and output sizes. Also check COS and enter an input size value of 1. Click Next. |
|
7 |
Change the icon, if you wish, at the Change Graphic Image and click Next. |
The Final Task Summary screen appears. |
8 |
Verify that the controller is to be registered and click Next. |
The completion screen appears. |
9 |
Click Finish. |
The EDS Wizard closes. |
10 |
Add the controller to the Scanlist Add the Controller to the Scanlist. |
Saving the Configuration
Save your configuration by selecting RSNetworx menu. This is a standard Windows command.
from thePKW Objects
Overview
The LTMR controller supports PKW (Periodically Kept in acyclic Words). The PKW feature consists of:
-
4 input words mapped in input assembly objects 111, 112, and 113
-
4 output words mapped in output assembly objects 101, 102, and 103
These 4 words tables enable a DeviceNet scanner to read or write any register using I/O messaging.
PKW OUT Data
PKW OUT data requests from the DeviceNet scanner to the LTMR are mapped in assembly objects 101, 102, and 103.
To access registers, select one of the following function codes:
-
R_REG_16 (0x25) to read 1 register
-
R_REG_32 (0x26) to read 2 registers
-
W_REG_16 (0x2A) to write 1 register
-
W_REG_32 (0x2B) to write 2 registers
Word 1 |
Word 2 |
Word 3 |
Word 4 |
||
---|---|---|---|---|---|
MSB |
LSB |
||||
Register address |
Toggle bit (bit 15) |
Function bits (bits 8 to 14) |
Not used (bits 0 to 7) |
Data to write |
|
Register number |
0/1 |
R_REG_16 Code 0x25 |
0x00 |
_ |
_ |
R_REG_32 Code 0x26 |
_ |
_ |
|||
W_REG_16 Code 0x2A |
Data to write in register |
_ |
|||
W_REG_32 Code 0x2B |
Data to write in register 1 |
Data to write in register 2 |
Any changes in the function code will trigger the handling of the request (unless Function code [bit 8 to 14] = 0x00).
This mechanism enables the request initiator to detect that a response is ready by polling bit 15 of the function code in word 2. When this bit in the OUT data becomes equal to the response emitted toggle bit in the IN data (when starting the request), then the response is ready.
PKW IN Data
PKW IN data response from the LTMR to the DeviceNet scanner are mapped in assembly objects 111, 112, and 113.
The LTMR echoes the same register address and function code or, eventually, a detected error code.
Word 1 |
Word 2 |
Word 3 |
Word 4 |
||
---|---|---|---|---|---|
MSB |
LSB |
||||
Register address |
Toggle bit (bit 15) |
Function bits (bits 8 to 14) |
Not used (bits 0 to 7) |
Data to write |
|
Same register number as in the request |
Same as in the request |
Detected Error Code 0x4E |
0x00 |
Detected Error code |
|
R_REG_16 Code 0x25 |
Data read in register |
_ |
|||
R_REG_32 Code 0x26 |
Data read in register 1 |
Data read in register 2 |
|||
W_REG_16 Code 0x2A |
_ |
_ |
|||
W_REG_32 Code 0x2B |
_ |
_ |
If the initiator tries to write a TeSys T object or register to an unauthorized value, or tries to access an inaccessible register, a detected error code is returned (Function code = toggle bit + 0x4E). The exact code can be found in words 3 and 4. The request is not accepted and the object/register remains at the old value.
To re-trigger exactly the same command, you need to:
-
Reset the Function code to 0x00,
-
Wait for the response frame with the function code equal to 0x00,
-
Reset it to its previous value.
This is useful for a limited primary like an HMI.
Another way of re-triggering exactly the same command is to invert the toggle bit in the function code byte.
The response is valid when the toggle bit of the response is equal to the toggle bit written in the answer (this is a more efficient method, but it requires higher programming capabilities).
PKW Detected Error Codes
Case of a detected write error:
Detected Error Code |
Detected Error Name |
Explanation |
---|---|---|
1 |
FGP_ERR_REQ_STACK_FULL |
external request: sends back a detected error frame |
3 |
FGP_ERR_REGISTER_NOT_FOUND |
register not managed (or the request needs super user access rights) |
4 |
FGP_ERR_ANSWER_DELAYED |
external request: answer postponed |
7 |
FGP_ERR_NOT_ALL_REGISTER_FOUND |
one or both registers cannot be found |
8 |
FGP_ERR_READ_ONLY |
register not authorized to be written |
10 |
FGP_ERR_VAL_1WORD_TOOHIGH |
written value not in the range of the register (word value is too high) |
11 |
FGP_ERR_VAL_1WORD_TOOLOW |
written value not in the range of the register (word value is too low) |
12 |
FGP_ERR_VAL_2BYTES_INF_TOOHIGH |
written value not in the range of the register (MSB value is too high) |
13 |
FGP_ERR_VAL_2BYTES_INF_TOOLOW |
written value not in the range of the register (MSB value is too low) |
16 |
FGP_ERR_VAL_INVALID |
written value not a valid value |
20 |
FGP_ERR_BAD_ANSWER |
external request: sends back a detected error frame |
Case of a detected read error:
Detected Error Code |
Detected Error Name |
Explanation |
---|---|---|
1 |
FGP_ERR_REQ_STACK_FULL |
external request: sends back a detected error frame |
3 |
FGP_ERR_REGISTER_NOT_FOUND |
register not managed (or the request needs super user access rights) |
4 |
FGP_ERR_ANSWER_DELAYED |
external request: answer postponed |
7 |
FGP_ERR_NOT_ALL_REGISTER_FOUND |
one or both registers cannot be found |
Object Dictionary
Overview
The DeviceNet protocol using object modeling. Object modeling organizes related data and procedures into one entity: the object.
An object is a collection of related services and attributes. Services are procedures an object performs. Attributes are characteristics of objects represented by values, which can vary. Typically, attributes provide status information or govern the operation of an object. The value associated with an attribute may or may not affect the behavior of an object. An object’s behavior is an indication of how the object responds to particular events.
Objects within a class are called object instances. An object instance is the actual representation of a particular object within a class. Each instance of a class has the same set of attributes, but has its own set of attribute values, which makes each instance in the class unique. The Object Dictionary describes the attribute values of each object in the device profile.
LTMR Object Dictionary
The general breakdown of the LTMR DeviceNet brick object dictionary is the same for all DeviceNet devices:
Index |
Object |
Description |
---|---|---|
01h |
Identity Object |
Identifiers, such as device type, vendor ID, and serial number. |
02h |
Message Router Object |
Provides a message connection point. |
03h |
DeviceNet Object |
Maintains physical connection to the DeviceNet network; allocates and de-allocates the primary/secondary connection set. |
04h |
Assembly Object |
Provides collection of other object’s attributes (frequently used for I/O messaging). |
05h |
Connection Object |
Allows explicit messaging to be conducted. |
29h |
Control Supervisor Object |
Manages controller functions, operational states, and control. |
2Ch |
Overload Object |
Implements overload behavior. |
C6h |
DeviceNet Interface Object |
Enables I/O messaging data to be selected. |
C5h |
PKW: Periodic Registers Service Objects |
Enables cyclic I/O messaging for manufacturer-specific registers. |
These objects are described in detail in the following pages.
Identity Object
Description
This object, present in all DeviceNet products, provides identification of, and general information about, the device.
Class Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
Revision |
UInt |
01 |
- |
Instance Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
Vendor ID |
UInt |
243 |
243 -> "Schneider Automation Inc." |
2 |
Get |
Device type |
UInt |
16h |
Motor Starter |
3 |
Get |
Product code |
UInt |
Product identification depends on the configuration |
Remote mode:
Local mode:
|
4 |
Get |
Revision |
Struct. of: UInt UInt |
Product configuration |
Product version |
5 |
Get |
Status |
Word |
01 |
See the following table. |
6 |
Get |
Serial number |
UDInt |
01 |
Read from the controller during start-up in registers [70] to [74]: Control Unit Serial Number |
7 |
Get |
Product name |
Struct. of: USInt String |
"LTM1" |
Read from the controller during start-up in registers [64] to [69]: Control Unit Identification |
Bit |
Definition |
Values |
---|---|---|
0 |
Owned by Primary (predefined Primary/Secondary connection) |
Provided by the stack |
1 |
Reserved |
0 |
2 |
Configured |
NOT(Control Unit In Configuration Mode [456.9]) |
3 |
Reserved |
0 |
4, 5, 6, 7 |
Vendor Specific: 4: Alarm 5: Trip 6: Contactor state 7: Reverser contactor state |
[455.3] [455.4] [455.1] & [704=1] [455.1] & [704=2] |
8 |
Minor recoverable trip |
0 |
9 |
Minor unrecoverable trip |
0 |
10 |
Major recoverable trip |
1 ≤ [451] ≤ 15 |
11 |
Major unrecoverable trip |
[451] ≤ 15 |
Class and Instance Service
Service Code |
Service Name |
Description |
---|---|---|
0E hex |
Get_Attribute_Single |
Read 1 attribute |
05 hex |
Reset |
Product reset |
Message Router Object
Description
The Message Router Object provides a messaging connection point through which a Client may address a service to any object class or instance in the physical device.
Class Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
Revision |
UInt |
01 |
- |
Instance Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
Object list:
|
UInt |
List of supported objects Number of supported classes List of supported classes |
|
2 |
Get |
Number available |
UInt |
Maximum number of connections supported |
|
3 |
Get |
Number active |
UInt |
Number of active connections |
|
4 |
Get |
Active connections |
Struct. of: UInt UInt |
List of active connections |
Class and Instance Service
Service Code |
Service Name |
Description |
---|---|---|
0E hex |
Get_Attribute_Single |
Read 1 attribute |
DeviceNet Object
Overview
The DeviceNet Object is used to provide the configuration and status of a physical attachment to the DeviceNet network. A product can support only one DeviceNet Object per physical connection to the DeviceNet communication terminals.
Class Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
Revision |
UInt |
002 |
- |
Instance Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
MAC ID |
USInt |
0 - 63 |
Read-only attribute |
2 |
Get |
Baud rate |
USInt |
0 - 2 |
0: 125 k 1: 250 k 2: 500 k Read-only attribute |
3 |
Get/Set |
BOI (Bus OFF Interrupt) |
Bool |
- |
Upon Bus-Off interrupt: 0: Hold the CAN chip in its bus-OFF state. 1: Reset the CAN chip and continue communicating. |
4 |
Get/Set |
BusOFF counter |
USInt |
0 - 255 |
Number of times CAN was in bus-OFF state |
5 |
Get |
Allocation information |
Byte - USInt |
0 - 63 |
Allocation choice Primary Address (255 not allocated) |
Class Service
Service Code |
Service Name |
Description |
---|---|---|
0E hex |
Get_Attribute_Single |
Read 1 attribute |
Instance Service
Service Code |
Service Name |
Description |
---|---|---|
0E hex |
Get_Attribute_Single |
Read 1 attribute |
19 hex |
Set_AttributesSingle |
Write 1 attribute |
0E hex |
Allocate Primary/Secondary Connection Set |
Requests the use of the predefined Primary/Secondary Connection Set |
0E hex |
Release Primary/Secondary Connection Set |
Indicates that the specified connections within the predefined Primary/Secondary Connection Set are no longer desired. These Connections are to be released (deleted). |
Assembly Object
Description
The Assembly Object binds attributes of multiple objects, which enables each object’s data to be sent or received over a single connection. Assembly objects can be used to bind input data or output data. The terms "input" and "output" are defined from the network's point of view. An input sends (produces) data on the network, and an output receives (consumes) data from the network.
Only static assemblies are supported.
Class Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
Revision |
UInt |
02 |
- |
2 |
Get |
Max instance |
UInt |
13 |
- |
Instance Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
3 |
Get |
Data |
See assembly data description below. |
Class and Instance Service
Service Code |
Service Name |
Description |
---|---|---|
0E hex |
Get_Attribute_Single |
Read 1 attribute |
Output Assembly Data
Instance 2: Basic Overload
Byte |
Bit 7 |
Bit 6 |
Bit 5 |
Bit 4 |
Bit 3 |
Bit 2 |
Bit 1 |
Bit 0 |
---|---|---|---|---|---|---|---|---|
0 |
Reserved |
Reserved |
Reserved |
Reserved |
Reserved |
TripReset |
Reserved |
Reserved |
Instance 3: Basic Motor Starter
Byte |
Bit 7 |
Bit 6 |
Bit 5 |
Bit 4 |
Bit 3 |
Bit 2 |
Bit 1 |
Bit 0 |
---|---|---|---|---|---|---|---|---|
0 |
Reserved |
Reserved |
Reserved |
Reserved |
Reserved |
TripReset |
Reserved |
Run 1 |
Instance 4: Extended Contactor
Byte |
Bit 7 |
Bit 6 |
Bit 5 |
Bit 4 |
Bit 3 |
Bit 2 |
Bit 1 |
Bit 0 |
---|---|---|---|---|---|---|---|---|
0 |
Reserved |
Reserved |
Reserved |
Reserved |
Reserved |
Reserved |
Run 2 |
Run 1 |
Instance 5: Extended Motor Starter
Byte |
Bit 7 |
Bit 6 |
Bit 5 |
Bit 4 |
Bit 3 |
Bit 2 |
Bit 1 |
Bit 0 |
---|---|---|---|---|---|---|---|---|
0 |
Reserved |
Reserved |
Reserved |
Reserved |
Reserved |
TripReset |
Run 2 |
Run 1 |
-
TripReset = Register 704.3
-
Run2 = Register 704.1
-
Run1 = Register 704.0
Instance 100: LTMR Control Registers
This assembly contains several control registers commonly used with an LTMR device.
Byte 0 |
Byte 1 |
Byte 2 |
Byte 3 |
Byte 4 |
Byte 5 |
---|---|---|---|---|---|
path: 6C : 01 : 05 (Register {704]) |
path: 6C : 01 : 04 (Register {703]) |
path: 6C : 01 : 01 (Register {700]) |
|||
LSB (least significant bit) |
MSB (most significant bit) |
LSB |
MSB |
LSB |
MSB |
Instance 101: PKW Request Object
This assembly is vendor specific. It is used to implement the request object of PKW protocol.
Byte 7 |
Byte 6 |
Byte 5 |
Byte 4 |
Byte 3 |
Byte 2 |
Byte 1 |
Byte 0 |
---|---|---|---|---|---|---|---|
For details, refer to PKW Objects. |
Instance 102: PKW Request and Extended Motor Starter
This assembly is vendor specific.
Bytes 0 to 7 |
Byte 8 |
Byte 9 |
---|---|---|
See Instance 101 above. |
Reserved (value = 0) |
See Instance 5 above. |
Instance 103: PKW Request and LTMR Control Registers
This assembly is vendor specific.
Bytes 0 to 7 |
Byte 8 to 13 |
---|---|
See Instance 101 above. |
See Instance 100 above. |
Input Assembly Data
Instance 50: Basic Overload
Byte |
Bit 7 |
Bit 6 |
Bit 5 |
Bit 4 |
Bit 3 |
Bit 2 |
Bit 1 |
Bit 0 |
---|---|---|---|---|---|---|---|---|
0 |
Reserved |
Reserved |
Reserved |
Reserved |
Reserved |
Reserved |
Reserved |
Trip |
Instance 51: Extended Overload
Byte |
Bit 7 |
Bit 6 |
Bit 5 |
Bit 4 |
Bit 3 |
Bit 2 |
Bit 1 |
Bit 0 |
---|---|---|---|---|---|---|---|---|
0 |
Reserved |
Reserved |
Reserved |
Reserved |
Reserved |
TripReset |
Alarm |
Trip |
Instance 52: Basic Motor Starter
Byte |
Bit 7 |
Bit 6 |
Bit 5 |
Bit 4 |
Bit 3 |
Bit 2 |
Bit 1 |
Bit 0 |
---|---|---|---|---|---|---|---|---|
0 |
Reserved |
Reserved |
Reserved |
Reserved |
Reserved |
Running1 |
Reserved |
Trip |
Instance 53: Extended Motor Starter 1
Byte |
Bit 7 |
Bit 6 |
Bit 5 |
Bit 4 |
Bit 3 |
Bit 2 |
Bit 1 |
Bit 0 |
---|---|---|---|---|---|---|---|---|
0 |
Reserved |
Reserved |
CntrlfromNet |
Ready |
Reserved |
Running1 |
Alarm |
Trip |
Instance 54: Extended Motor Starter 2
Byte |
Bit 7 |
Bit 6 |
Bit 5 |
Bit 4 |
Bit 3 |
Bit 2 |
Bit 1 |
Bit 0 |
---|---|---|---|---|---|---|---|---|
0 |
Reserved |
Reserved |
CntrlfromNet |
Ready |
Running2 |
Running1 |
Alarm |
Trip |
-
CntrlfromNet = NOT (Register 455.14)
-
Ready = Register 455.0
-
Running2 = (Register 455.7) AND (Register 704.1)
-
Running1 = (Register 455.7) AND (Register 704.0)
-
Alarm = Register 455.3
-
Trip = (Register 455.2) OR (Register 455.4)
Instance 110: LTMR Monitoring Registers (with dynamic configuration)
This assembly contains several monitoring registers commonly used with an LTMR device. You can choose registers by setting attributes 5-8 of the DeviceNet interface object. For more details, refer to DeviceNet Interface Object.
Byte 0 |
Byte 1 |
Byte 2 |
Byte 3 |
Byte 4 |
Byte 5 |
Byte 6 |
Byte 7 |
---|---|---|---|---|---|---|---|
Register pointed using path: C6 : 01 : 05 |
Register pointed using path: C6: 01 : 06 |
Register pointed using path: C6 : 01 : 07 |
Register pointed using path: C6 : 01 : 08 |
||||
LSB |
MSB |
LSB |
MSB |
LSB |
MSB |
LSB |
MSB |
Instance 111: PKW Response Object
This assembly is vendor specific. It is used to implement the response object of PKW protocol.
Byte 7 |
Byte 6 |
Byte 5 |
Byte 4 |
Byte 3 |
Byte 2 |
Byte 1 |
Byte 0 |
---|---|---|---|---|---|---|---|
For details, refer to PKW Objects. |
Instance 112: PKW Request and Extended Motor Starter
This assembly is vendor specific.
Bytes 0 to 7 |
Byte 8 |
Byte 9 |
---|---|---|
See Instance 111 above. |
Reserved (value = 0) |
See Instance 54 above. |
Instance 113: PKW Request and LTMR Monitoring Registers
This assembly is vendor specific.
Bytes 0 to 7 |
Byte 8 to 15 |
---|---|
See Instance 111 above. |
See Instance 110 above. |
Connection Object
Description
The Connection Object provides for and manages the run-time exchange of messages.
Class Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
Revision |
UInt |
01 |
- |
Instance 1 Attributes: Explicit Message Instance
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
State |
USInt |
- |
0: Non-existent 3: Established 5: Deferred Delete |
2 |
Get |
Instance_type |
USInt |
0 |
Explicit Message |
3 |
Get |
TransportClass_trigger |
USInt |
83h |
Defines behavior of the connection |
4 |
Get |
Produced_connection_id |
UInt |
10xxxxxx011 |
xxxxxx = Node address |
5 |
Get |
Consumed_connection_id |
UInt |
10xxxxxx100 |
xxxxxx = Node address |
6 |
Get |
Initial_comm_characteristics |
USInt |
21h |
Explicit messaging via Group 2 |
7 |
Get |
Produced_connection_size |
UInt |
7 |
- |
8 |
Get |
Consumed_connection_size |
UInt |
7 |
- |
9 |
Get/Set |
Expected_packet_rate |
UInt |
2500 |
2.5 s (TimeOut) |
12 |
Get/Set |
Watchdog_timeout_action |
UInt |
1 or 3 |
1: Auto-Delete (Factory setting) 3: Deferred Delete |
13 |
Get |
Produced connection path length |
UInt |
0 |
- |
14 |
Get |
Produced connection path |
UInt |
Null |
empty |
15 |
Get |
Consumed connection path length |
UInt |
0 |
- |
16 |
Get |
Consumed connection path |
UInt |
Null |
empty |
Instance 2 Attributes: Polled I/O Message Instance
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
State |
USInt |
- |
0: Non-existent 1: Configuring 3: Established 4: TimeOut |
2 |
Get |
Instance_type |
USInt |
1 |
I/O Message |
3 |
Get |
TransportClass_trigger |
USInt |
82h |
Class 2 |
4 |
Get |
Produced_connection_id |
UInt |
01111xxxxxx |
xxxxxx = Node address |
5 |
Get |
Consumed_connection_id |
UInt |
10xxxxxx101 |
xxxxxx = Node address |
6 |
Get |
Initial_comm_characteristics |
USInt |
01h |
Group1/Group 2 |
7 |
Get |
Produced_connection_size |
UInt |
4 |
- |
8 |
Get |
Consumed_connection_size |
UInt |
4 |
- |
9 |
Get/Set |
Expected_packet_rate |
UInt |
0 |
- |
12 |
Get/Set |
Watchdog_timeout_action |
USInt |
0, 1, or 2 |
0: Transition to TimeOut 1: Auto-delete 2: Auto-reset |
13 |
Get |
Produced connection path length |
UInt |
- |
- |
14 |
Get/Set |
Produced connection path |
UInt |
- |
- |
15 |
Get |
Consumed connection path length |
UInt |
- |
- |
16 |
Get/Set |
Consumed connection path |
UInt |
- |
- |
17 |
Get/Set |
Production_inhibit_time |
UInt |
0 |
Minimum time between new data production |
Instance 4 Attributes: Change-of-State/Cyclic Message Instance
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
State |
USInt |
- |
0: Non-existent 1: Configuring 3: Established 4: TimeOut |
2 |
Get |
Instance_type |
USInt |
1 |
I/O Message |
3 |
Get |
TransportClass_trigger |
USInt |
xx |
- |
4 |
Get |
Produced_connection_id |
UInt |
01101xxxxxx |
xxxxxx = Node address |
5 |
Get |
Consumed_connection_id |
UInt |
10xxxxxx101 |
xxxxxx = Node address |
6 |
Get |
Initial_comm_characteristics |
USInt |
01h |
Group1/Group 2 |
7 |
Get |
Produced_connection_size |
UInt |
4 |
- |
8 |
Get |
Consumed_connection_size |
UInt |
4 |
- |
9 |
Get/Set |
Expected_packet_rate |
UInt |
0 |
- |
12 |
Get/Set |
Watchdog_timeout_action |
USInt |
0, 1 or 2 |
0: Transition to TimeOut 1: Auto-delete 2: Auto-reset |
13 |
Get |
Produced connection path length |
UInt |
- |
- |
14 |
Get/Set |
Produced connection path |
UInt |
- |
- |
15 |
Get |
Consumed connection path length |
UInt |
- |
- |
16 |
Get/Set |
Consumed connection path |
UInt |
- |
- |
17 |
Get/Set |
Production_inhibit_time |
UInt |
0 |
Not defined |
Class Service
Service Code |
Service Name |
Description |
---|---|---|
08 hex |
Create |
Used to instantiate a Connection Object |
0E hex |
Get_Attribute_Single |
Read 1 attribute |
Instance Service
Service Code |
Service Name |
Description |
---|---|---|
0E hex |
Get_Attribute_Single |
Read 1 attribute |
10 hex |
Set_Attribute_Single |
Write 1 attribute |
05 hex |
Reset |
Reset Inactivity/Watchdog timer |
Control Supervisor Object
Description
This object models all the management functions for devices within the "Hierarchy of Motor Control Devices".
Class Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
Revision |
UInt |
02 |
- |
2 |
Get |
Max instance |
UInt |
1 |
- |
Instance Attributes
Attribute ID |
Access |
Name |
Data Type |
Description |
---|---|---|---|---|
3 |
Get/Set |
Run Fwd |
Bool |
704.0 |
4 |
Get |
Run Rev |
Bool |
704.1 |
6 |
Get |
State |
USInt |
0 = Vendor Specific 1 = Startup 2 = Not_Ready 3 = Ready 4 = Enabled 5 = Stopping 6 = Trip_Stop 7 = Trip |
7 |
Get |
Running Fwd |
Bool |
455.7 AND 704.0 |
8 |
Get |
Running Rev |
Bool |
455.7 AND 704.1 |
9 |
Get |
Ready |
Bool |
455.0 |
10 |
Get |
Trip |
Bool |
455.2 |
11 |
Get |
Alarm |
Bool |
455.3 |
12 |
Get/Set |
TripRst |
Bool |
704.3 = 0 ->1 (rising edge) |
13 |
Get |
TripCode |
UInt |
451 |
14 |
Get |
AlarmCode |
UInt |
460 |
15 |
Get |
CtrlFromNet |
Bool |
NOT(455.14) |
16 |
Get/Set |
DNTripMode |
UInt |
Action on network loss: 0 = Trip + Stop ' 682 = 2 1 = Ignore ' 682 = 0 2 = Frozen ' 682 = 1 3 = Inchange ' 682 = 3 4 = Force FW ' 682 = 4 5 = Force RV ' 682 = 5 |
17 |
Get/Set |
ForceTrip/Trip |
Bool |
704.12 |
Class Service
Service Code |
Service Name |
Description |
---|---|---|
0E hex |
Get_Attribute_Single |
Read 1 attribute |
Instance Service
Service Code |
Service Name |
Description |
---|---|---|
0E hex |
Get_Attribute_Single |
Read 1 attribute |
10 hex |
Set_Attribute_Single |
Write 1 attribute |
05 hex |
Reset |
Reset Inactivity/Watchdog timer |
Control Supervisor State Event
The following table describes the run/stop event matrix:
Event |
State (N/A = No action) |
|||||||
---|---|---|---|---|---|---|---|---|
Non-exist |
Startup |
Not_Ready |
Ready |
Enabled |
Stopping |
Trip-Stop |
Trip |
|
Switch OFF |
N/A |
Transition to Non-exist |
Transition to Non-exist |
Transition to Non-exist |
Transition to Non-exist |
Transition to Non-exist |
Transition to Non-exist |
Transition to Non-exist |
Switch ON |
Transition to Startup |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
Initialization Complete |
N/A |
Transition to Not_Ready |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
Main Power ON |
N/A |
N/A |
Transition to Ready |
N/A |
N/A |
N/A |
N/A |
N/A |
Run |
N/A |
N/A |
N/A |
Transition to Enable |
N/A |
Transition to Enable |
N/A |
N/A |
Stop |
N/A |
N/A |
N/A |
N/A |
Transition to Stopping |
N/A |
N/A |
N/A |
Stop Complete |
N/A |
N/A |
N/A |
N/A |
N/A |
Transition to Ready |
N/A |
N/A |
Reset |
N/A |
N/A |
Transition to Startup |
Transition to Startup |
Transition to Startup |
Transition to Startup |
Transition to Startup |
Transition to Startup |
Main Power OFF |
N/A |
N/A |
N/A |
Transition to Not_Ready |
Transition to Trip |
Transition to Trip |
Transition to Trip |
N/A |
Trip Detected |
N/A |
Transition to Trip |
Transition to Trip |
Transition to Trip |
Transition to Trip_Stop |
Transition to Trip_Stop |
N/A |
N/A |
Trip_Stop Complete |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
Transition to Trip |
|
Trip Reset |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
Transition to Not_Ready |
Attribute 5 (NetCtrl) is used to request that Run Stop events be controlled from the network. You may inhibit these events, however, if you do not wish to allow Run Stop control from the network under certain circumstances, or if your application does not permit it. Only when attribute 15 (CtrlFromNet) is set to 1 by the device in response to a NetCtrl request, is Run Stop control actually enabled from the network.
If attribute 15 (CtrlFromNet) is 1, then the events Run and Stop are triggered by a combination of the Run1 and Run2 attributes, as shown in the following table. Note that Run1 and Run2 have different contexts for different device types.
The following table shows the Run1 and Run2 contexts for the devices within the motor control hierarchy:
Drives and Servos |
|
---|---|
Run1 |
RunFwd |
Run2 |
RunRev |
If CtrlFromNet is 0, Run and Stop events must be controlled using local input(s) provided by the vendor.
Run1 |
Run2 |
Trigger Event |
Run Type |
---|---|---|---|
0 |
0 |
Stop |
N/A |
0 -> 1 |
0 |
Run |
Run1 |
0 |
0 -> 1 |
Run |
Run2 |
0 -> 1 |
0 -> 1 |
No action |
N/A |
1 |
1 |
No action |
N/A |
1 -> 0 |
1 |
Run |
Run2 |
1 |
1 -> 0 |
Run |
Run1 |
Overload Object
Description
This object models all the functions specific to an AC motor overload protection device.
Class Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
Revision |
UInt |
01 |
- |
2 |
Get |
Max instance |
UInt |
1 |
- |
Instance Attributes
Attribute ID |
Access |
Name |
Data Type |
Value |
Description |
---|---|---|---|---|---|
1 |
Get |
NumAttr |
UInt |
Number of Attributes Supported |
|
3 |
Set/Get |
TripFLCSet |
UInt |
[652] |
% of FLC max |
4 |
Set/Get |
TripClass |
USInt |
[606] |
Trip Class Setting (0 to 200) |
5 |
Get |
AvgCurrent |
Int |
65535x[501]+[500]/10 |
0.1 A |
6 |
Get |
%PhImbal |
USInt |
[471] |
% Phase Imbalance |
7 |
Get |
%Thermal |
USInt |
[465] |
% Thermal Capacity |
8 |
Get |
IL1 Current |
Int |
65535x[503]+[504]/10 |
0.1 A |
9 |
Get |
IL2 Current |
Int |
65535x[505]+[506]/10 |
0.1 A |
10 |
Get |
IL3 Current |
Int |
65535x[507]+[506]/10 |
0.1 A |
11 |
Get |
Ground Current |
Int |
65535x[509]+[508]/10 |
0.1 A |
101 |
Get |
IL1 Current |
Int |
Idem Att. 8 |
0.1 A |
102 |
Get |
IL2 Current |
Int |
Idem Att. 9 |
0.1 A |
103 |
Get |
IL3 Current |
Int |
Idem Att. 10 |
0.1 A |
104 |
Get |
Ground Current |
Int |
Idem Att. 11 |
0.1 A |
105 |
Get |
IL1 Current Ratio |
UInt |
[467] |
% of FLC |
106 |
Get |
IL2 Current Ratio |
UInt |
[468] |
% of FLC |
107 |
Get |
IL3 Current Ratio |
UInt |
[469] |
% of FLC |
108 |
Get |
IAV Average Current Ratio |
UInt |
[466] |
% of FLC |
109 |
Get |
Thermal Capacity Level |
UInt |
[465] |
%TripLevel |
110 |
Get |
Ground Current |
Int |
[Idem Att. 11 |
0.1 A |
111 |
Get |
Current phase imbalance |
UInt |
[471] |
% Imbalance |
112 |
Get |
Time to trip |
UInt |
[511] |
Seconds |
113 |
Get/Set |
Time to Reset |
UInt |
[450] |
Seconds |
127 |
Get/Set |
Single/Three Ph |
Bool |
If [601.14]=1, return 0 If [601.13]=1, return 1 |
0 = Single phase 1 = Three phases |
128 |
Get/Set |
FLC Setting |
UInt |
[652] |
Seconds |
129 |
Get/Set |
Load Class |
UInt |
[606] |
Seconds |
132 |
Get/Set |
Thermal Warn Level |
UInt |
[609] |
%TripLevel |
133 |
Get/Set |
PL Inhibit Time |
USInt |
[613] |
Seconds |
134 |
Get/Set |
PL Trip Delay |
USInt |
[614] |
Seconds |
136 |
Get/Set |
GF Trip Delay |
USInt |
[610] |
0.1...25.0 S |
137 |
Get/Set |
GF Trip Level |
USInt |
[611] |
1.0...5.0 A |
138 |
Get/Set |
GF Warn Level |
USInt |
[612] |
1.0...5.0 A |
139 |
Get/Set |
Stall Enabled Time |
USInt |
[623] |
0...250 S |
140 |
Get/Set |
Stall Trip Level |
UInt |
[624] |
100...600 |
142 |
Get/Set |
Jam Trip Delay |
USInt |
[617] |
0.1...25.0 S |
143 |
Get/Set |
Jam Trip Level |
UInt |
[618] |
0...600 % FLC |
144 |
Get/Set |
Jam Warn Level |
UInt |
[619] |
0...600 % FLC |
146 |
Get/Set |
UL Trip Delay |
USInt |
[620] |
0.1...25.0 S |
147 |
Get/Set |
UL Trip Level |
USInt |
[621] |
10...100 % FLC |
148 |
Get/Set |
UL Warn Level |
USInt |
[622] |
10...100 % FLC |
149 |
Get/Set |
CI Inhibit Time |
USInt |
[613] |
0...250 S |
150 |
Get/Set |
CI Trip Delay |
USInt |
[614] |
0.1...25.0 S |
151 |
Get/Set |
CI Trip Level |
USInt |
[615] |
10...100 % FLC |
152 |
Get/Set |
CI Warn Level |
USInt |
[616] |
10...100 % FLC |
178 |
Get |
CT Ratio |
USInt |
-
PL = Current Phase Loss
-
GF = Ground Current Trip
-
Stall = Long Start
-
UL = Underload
-
CI = Current Phase Imbalance
Class Service
Service Code |
Service Name |
Description |
---|---|---|
0E hex |
Get_Attribute_Single |
Read 1 attribute |
Instance Service
Service Code |
Service Name |
Description |
---|---|---|
0E hex |
Get_Attribute_Single |
Read 1 attribute |
10 hex |
Set_Attribute_Single |
Write 1 attribute |
DeviceNet Interface Object
Description
This object enables you to select the data that will be exchanged on the network through I/O messaging. A single instance (instance 1) of the DeviceNet Interface Object is supported.
Instance Attributes
The following instance attributes are supported:
Attribute ID |
Access |
Name |
Data Type |
Value |
---|---|---|---|---|
1 |
Set/Get |
Poll-produced assembly instance |
Byte (0...7) |
0: Instance 50: Basic Overload 1: Instance 51: Extended Overload 2: Instance 52: Basic Motor Starter 3: Instance 53: Extended Motor Starter 1 (EMS1) 4: Instance 54: Extended Motor Starter 2 (EMS2) (Factory setting) 5: Instance 110: LTM1 Monitoring registers 6: Instance 111: PKW response object 7: Instance 112: PKW response + EMS2 8:Instance 113: PKW response + LTM1 monitoring |
2 |
Set/Get |
Poll-consumed assembly instance |
Byte (0...7) |
0: Instance 2: Basic Overload 1: Instance 3: Basic Motor Starter 2: Instance 4: Extended Contactor 3: Instance 5: Extended Motor Starter (EMS) 4: Instance 5: Extended Motor Starter (EMS) (Factory setting)* 5: Instance 100: LTM1 control registers 6: Instance 101: PKW Request object 7: Instance 102: PKW Request + EMS 8: Instance 103: PKW Request + LTM1 control |
3 |
Set/Get |
COS-produced assembly instance |
Byte (0...7) |
0: Instance 50: Basic Overload 1: Instance 51: Extended Overload 2: Instance 52: Basic Motor Starter 3: Instance 53: Extended Motor Starter 1 (EMS1) 4: Instance 54: Extended Motor Starter 2 (EMS2) (Factory setting) 5: Instance 110: LTM1 Monitoring registers 6: Instance 111: PKW response object 7: Instance 112: PKW response + EMS2 8: Instance 113: PKW response + LTM1 monitoring |
4 |
Set/Get |
AutoBaud enable |
Bool |
0: AutoBaud disable (Factory setting) 1: AutoBaud enable* |
5 |
Set/Get |
LTMR monitoring Word 0 |
UInt |
Register of word 0 (Factory setting: 455)* |
6 |
Set/Get |
LTMR monitoring Word 1 |
UInt |
Register of word 1 (Factory setting: 456)* |
7 |
Set/Get |
LTMR monitoring Word 2 |
UInt |
Register of word 2 (Factory setting: 457)* |
8 |
Set/Get |
LTMR monitoring Word 3 |
UInt |
Register of word 3 (Factory setting: 459)* |
Instance Service
Service Code |
Service Name |
Description |
---|---|---|
0E hex |
Get_Attribute_Single |
Read 1 attribute |
10 hex |
Set_Attribute_Single |
Write 1 attribute |
Register Map - Organization of Communication Variables
Introduction
Communication variables are listed in tables. They belong to groups (identification, statistics, monitoring,...). They are associated with an LTMR Controller, which may or may not have an LTME expansion module attached.
Communication Variable Groups
Communication variables are grouped according to the following criteria:
Variable Groups |
Register |
DeviceNet Addresses |
---|---|---|
Identification variables |
00 to 99 |
64 : 01 : 32 to 64 : 01 : 62 |
Statistics variables |
100 to 449 |
65 : 01 : 01 to 67 : 01 : 82 |
Monitoring variables |
450 to 539 |
68 : 01 : 01 to 68 : 01 : 54 |
Configuration variables |
540 to 699 |
69 : 01 : 01 to 6B : 01 : 32 |
Command variables |
700 to 799 |
6C : 01 : 01 to 6C : 01 : 0F |
Custom Logic variables |
1200 to 1399 |
71 : 01 : 01 to 71 : 01 : 0A |
Table Structure
Communication variables are listed in 5-column tables:
Column 1 Register number (decimal) |
Column 2 DeviceNet address (class : instance : attribute) |
Column 3 Variable type: integer, word, word[n], DT_type Data Types |
Column 4 Variable name and access via Read only or Read/Write requests |
Column 5 Note: code for additional information |
Note
The Note column gives a code for additional information.
Variables without a code are available for all hardware configurations, and without functional restrictions.
The code can be:
-
numerical (1 to 9), for specific hardware combinations
-
alphabetical (A to Z), for specific system behaviors.
If the Note is... |
Then the Variable is... |
---|---|
1 |
available for the LTMR + LTMEV40 combination |
2 |
always available but with a value equal to 0 if no LTMEV40 is connected |
3-9 |
Not used |
If the Note is... |
Then... |
---|---|
A |
the variable can be written only when the motor is OFF |
B |
the variable can be written only in configuration mode |
C |
the variable can be written only with no trip |
D-Z |
the variable is available for future exceptions |
Unused Addresses
Unused addresses fall into three categories:
-
Not significant, in Read only tables, means that you should ignore the value read, whether equal to 0 or not.
-
Reserved, in Read/Write tables, means that you must write 0 in these variables.
-
Forbidden, means that read or write requests are rejected, that these addresses are not accessible at all.
Data Formats
Overview
The data format of a communication variable can be integer, Word, or Word[n], as described below. For more information about a variable size and format, refer to Data Types.
Integer (Int, UInt, DInt, IDInt)
Integers fall into the following categories:
-
Int: signed integer using one register (16 bits)
-
UInt: unsigned integer using one register (16 bits)
-
DInt: signed double integer using two registers (32 bits)
-
UDInt: unsigned double integer using two registers (32 bits)
For all integer-type variables, the variable name is completed with its unit or format, if necessary.
Example:
Address 474, UInt, Frequency (x 0.01 Hz).
Word
Word: Set of 16 bits, where each bit or group of bits represents command, monitoring or configuration data.
Example:
Address 455, Word, System Status Register 1.
bit 0 |
System ready |
bit 1 |
System ON |
bit 2 |
System trip |
bit 3 |
System alarm |
bit 4 |
System tripped |
bit 5 |
Trip reset authorized |
bit 6 |
(Not significant) |
bit 7 |
Motor running |
bits 8-13 |
Motor average current ratio |
bit 14 |
In remote |
bit 15 |
Motor starting (in progress) |
Word[n]
Word[n]: Data encoded on contiguous registers.
Examples:
Addresses 64 to 69, Word[6], Controller Commercial Reference (DT_CommercialReference).
Addresses 655 to 658, Word[4], (DT_DateTime).
Data Types
Overview
Data types are specific variable formats which are used to complement the description of internal formats (for instance, in case of a structure or of an enumeration). The generic format of data types is DT_xxx.
List of Data Types
Here is the list of the most commonly used data types:
-
DT_ACInputSetting
-
DT_CommercialReference
-
DT_DateTime
-
DT_ExtBaudRate
-
DT_ExtParity
-
DT_TripCode
-
DT_FirmwareVersion
-
DT_Language5
-
DT_OutputFallbackStrategy
-
DT_PhaseNumber
-
DT_ResetMode
-
DT_AlarmCode
These data types are described in the following tables.
DT_ACInputSetting
DT_ACInputSetting format is an enumeration that improves AC input detection:
Value |
Description |
---|---|
0 |
None (factory setting) |
1 |
< 170 V 50 Hz |
2 |
< 170 V 60 Hz |
3 |
> 170 V 50 Hz |
4 |
> 170 V 60 Hz |
DT_CommercialReference
DT_CommercialReference format is Word[6] and indicates a Commercial Reference:
Register |
MSB |
LSB |
---|---|---|
Register N |
character 1 |
character 2 |
Register N+1 |
character 3 |
character 4 |
Register N+2 |
character 5 |
character 6 |
Register N+3 |
character 7 |
character 8 |
Register N+4 |
character 9 |
character 10 |
Register N+5 |
character 11 |
character 12 |
Example:
Addresses 64 to 69, Word[6], Controller Commercial Reference.
If Controller Commercial Reference = LTMR:
Register |
MSB |
LSB |
---|---|---|
64 |
L |
T |
65 |
M |
(space) |
66 |
R |
|
67 |
|
|
68 |
|
|
69 |
|
|
DT_DateTime
DT_DateTime format is Word[4] and indicates Date and Time:
Register |
Bits 12-15 |
Bits 8-11 |
Bits 4-7 |
Bits 0-3 |
---|---|---|---|---|
Register N |
S |
S |
0 |
0 |
Register N+1 |
H |
H |
m |
m |
Register N+2 |
M |
M |
D |
D |
Register N+3 |
Y |
Y |
Y |
Y |
Where:
-
S = second
The format is 2 BCD digits.
The value range is [00...59] in BCD.
-
0 = unused
-
H = hour
The format is 2 BCD digits.
The value range is [00...23] in BCD.
-
m = minute
The format is 2 BCD digits.
The value range is [00...59] in BCD.
-
M = month
The format is 2 BCD digits.
The value range is [01...12] in BCD.
-
D = day
The format is 2 BCD digits.
The value range is (in BCD):
[01-31] for months 01, 03, 05, 07, 08, 10, 12
[01-30] for months 04, 06, 09, 11
[01-29] for month 02 in a leap year
[01-28] for month 02 in a non-leap year.
-
Y = year
The format is 4 BCD digits.
The value range is [2006...2099] in BCD.
Data entry format and value range are:
Data Entry Format |
DT#YYYY-MM-DD-HH:mm:ss |
|
---|---|---|
Minimum value |
DT#2006-01-01:00:00:00 |
January 1, 2006 |
Maximum value |
DT#2099-12-31-23:59:59 |
December 31, 2099 |
Note: If you give values outside the limits, the system will return a detected error. |
Example:
Addresses 655 to 658, Word[4], Date and Time setting.
If date is September 4, 2008 at 7 a.m., 50 minutes and 32 seconds:
Register |
15 12 |
11 8 |
7 4 |
3 0 |
---|---|---|---|---|
655 |
3 |
2 |
0 |
0 |
656 |
0 |
7 |
5 |
0 |
657 |
0 |
9 |
0 |
4 |
658 |
2 |
0 |
0 |
8 |
With data entry format: DT#2008-09-04-07:50:32.
DT_ExtBaudRate
DT_ExtbaudRate depends on the bus used:
DT_ModbusExtBaudRate format is an enumeration of possible baud rates with Modbus network:
Value |
Description |
---|---|
1200 |
1200 Baud |
2400 |
2400 Baud |
4800 |
4800 Baud |
9600 |
9600 Baud |
19200 |
19,200 Baud |
65535 |
Autodetection (factory setting) |
DT_ProfibusExtBaudRate format is an enumeration of possible baud rates with PROFIBUS DP network:
Value |
Description |
---|---|
65535 |
Autobaud (factory setting) |
DT_DeviceNetExtBaudRate format is an enumeration of possible baud rates with DeviceNet network:
Value |
Description |
---|---|
0 |
125 kBaud |
1 |
250 kBaud |
2 |
500 kBaud |
3 |
Autobaud (factory setting) |
DT_CANopenExtBaudRate format is an enumeration of possible baud rates with CANopen network:
Value |
Description |
---|---|
0 |
10 kBaud |
1 |
20 kBaud |
2 |
50 kBaud |
3 |
125 kBaud |
4 |
250 kBaud (factory setting) |
5 |
500 kBaud |
6 |
800 kBaud |
7 |
1000 kBaud |
8 |
Autobaud |
9 |
Factory setting |
DT_ExtParity
DT_ExtParity depends on the bus used:
DT_ModbusExtParity format is an enumeration of possible parities with Modbus network:
Value |
Description |
---|---|
0 |
None |
1 |
Even |
2 |
Odd |
DT_TripCode
DT_TripCode format is an enumeration of trip codes:
Trip Code |
Description |
---|---|
0 |
No detected error |
3 |
Ground current |
4 |
Thermal overload |
5 |
Long start |
6 |
Jam |
7 |
Current phase imbalance |
8 |
Undercurrent |
10 |
Test |
11 |
HMI port detected error |
12 |
HMI port communication loss |
13 |
Network port internal detected error |
16 |
External trip |
18 |
ON-OFF diagnostic |
19 |
Wiring diagnostic |
20 |
Overcurrent |
21 |
Current phase loss |
22 |
Current phase reversal |
23 |
Motor temp sensor |
24 |
Voltage phase imbalance |
25 |
Voltage phase loss |
26 |
Voltage phase reversal |
27 |
Undervoltage |
28 |
Overvoltage |
29 |
Underpower |
30 |
Overpower |
31 |
Under power factor |
32 |
Over power factor |
33 |
LTME configuration |
34 |
Temperature sensor short-circuit |
35 |
Temperature sensor open-circuit |
36 |
CT reversal |
37 |
Out of boundary CT ratio |
46 |
Start check |
47 |
Run checkback |
48 |
Stop check |
49 |
Stop checkback |
51 |
Controller internal temperature detected error |
55 |
Controller internal detected error (Stack overflow) |
56 |
Controller internal detected error (RAM detected error) |
57 |
Controller internal detected error (RAM checksum detected error) |
58 |
Controller internal detected error (Hardware watchdog trip) |
60 |
L2 current detected in single-phase mode |
64 |
Non volatile memory detected error |
65 |
Expansion module communication detected error |
66 |
Stuck reset button |
67 |
Logic function detected error |
100-104 |
Network port internal detected error |
109 |
Network port comm detected error |
111 |
Inoperable device replacement trip |
555 |
Network port configuration detected error |
DT_FirmwareVersion
DT_FirmwareVersion format is an XY000 array that describes a firmware revision:
-
X = major revision
-
Y = minor revision.
Example:
Address 76, UInt, Controller firmware version.
DT_Language5
DT_Language5 format is an enumeration used for language display:
Language Code |
Description |
---|---|
1 |
English (factory setting) |
2 |
Français |
4 |
Español |
8 |
Deutsch |
16 |
Italiano |
Example:
Address 650, Word, HMI language.
DT_OutputFallbackStrategy
DT_OutputFallbackStrategy format is an enumeration of motor output states when loosing communication.
Value |
Description |
Motor Modes |
---|---|---|
0 |
Hold LO1 LO2 |
For all modes |
1 |
Run |
For two step mode only |
2 |
LO1, LO2 Off |
For all modes |
3 |
LO1, LO2 On |
Only for overload, independent and custom operating modes |
4 |
LO1 On |
For all modes except two step |
5 |
LO2 On |
For all modes except two step |
DT_PhaseNumber
DT_PhaseNumber format is an enumeration, with only 1 bit activated:
Value |
Description |
---|---|
1 |
1 phase |
2 |
3 phases |
DT_ResetMode
DT_ResetMode format is an enumeration of possible modes for thermal trip reset:
Value |
Description |
---|---|
1 |
Manual or HMI |
2 |
Remote by network |
4 |
Automatic |
DT_AlarmCode
DT_AlarmCode format is an enumeration of alarm codes:
Alarm Code |
Description |
---|---|
0 |
No alarm |
3 |
Ground current |
4 |
Thermal overload |
5 |
Long start |
6 |
Jam |
7 |
Current phase imbalance |
8 |
Undercurrent |
10 |
HMI port |
11 |
LTMR internal temperature |
18 |
Diagnostic |
19 |
Wiring |
20 |
Overcurrent |
21 |
Current phase loss |
23 |
Motor temp sensor |
24 |
Voltage phase imbalance |
25 |
Voltage phase loss |
27 |
Undervoltage |
28 |
Overvoltage |
29 |
Underpower |
30 |
Overpower |
31 |
Under power factor |
32 |
Over power factor |
33 |
LTME configuration |
46 |
Start check |
47 |
Run checkback |
48 |
Stop check |
49 |
Stop checkback |
109 |
Network port comm loss |
555 |
Network port configuration |
Identification Variables
Identification Variables
Identification variables are described in the following table:
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
0-34 |
64 : 01 : 03 - 64 : 01 : 23 |
(Not significant) |
||
35-40 |
64 : 01 : 24 - 64 : 01 : 29 |
Word[6] |
Expansion commercial reference DT_CommercialReference |
1 |
41-45 |
64 : 01 :2A - 64 : 01 : 2E |
Word[5] |
Expansion serial number |
1 |
46 |
64 : 01 : 2F |
UInt |
Expansion ID code |
1 |
47 |
64 : 01 : 30 |
UInt |
Expansion firmware version DT_FirmwareVersion |
1 |
48 |
64 : 01 : 31 |
UInt |
Expansion compatibility code |
1 |
49-60 |
64 : 01 : 32 - 64 : 01 : 3D |
(Not significant) |
||
61 |
64 : 01 : 3E |
Ulnt |
Network port ID code |
|
62 |
64 : 01 : 3F |
Ulnt |
Network port firmware version DT_FirmwareVersion |
|
63 |
64 : 01 : 40 |
Ulnt |
Network port compatibility code |
|
64-69 |
64 : 01 : 41 - 64 : 01 : 46 |
Word[6] |
Controller commercial reference DT_CommercialReference |
|
70-74 |
64 : 01 : 47 - 64 : 01 : 4B |
Word[5] |
Controller serial number |
|
75 |
64 : 01 :4 C |
Ulnt |
Controller ID code |
|
76 |
64 : 01 : 4D |
Ulnt |
Controller firmware version DT_FirmwareVersion |
|
77 |
64 : 01 :4E |
Ulnt |
Controller compatibility code |
|
78 |
64 : 01 : 4F |
Ulnt |
Current scale ratio (0.1 %) |
|
79 |
64 : 01 : 50 |
Ulnt |
Current sensor max |
|
80 |
64 : 01 : 51 |
(Not significant) |
||
81 |
64 : 01 : 52 |
Ulnt |
Current range max (x 0.1 A) |
|
82-94 |
64 : 01 : 53 - 64 : 01 : 5D |
(Not significant) |
||
95 |
64 : 01 : 60 |
Ulnt |
Load CT ratio (x 0.1 A) |
|
96 |
64 : 01 : 61 |
Ulnt |
Full load current max (maximum FLC range, FLC = Full Load Current) (x 0.1 A) |
|
97-99 |
64 : 01 : 62 - 64 : 01 : 64 |
(Forbidden) |
Statistics Variables
Statistics Overview
Statistics variables are grouped according to the following criteria. Trip statistics are described in a main table and in an extension table.
Statistics Variable Groups |
Register |
DeviceNet Addresses |
---|---|---|
Global statistics |
100 to 121 |
65 : 1 : 1 to 65 : 1 : 16 |
LTM monitoring statistics |
122 to 149 |
65 : 1 : 17 to 65 : 1 : 32 |
Last trip statistics and extension |
150 to 179 300 to 309 |
66 : 1 : 1 to 66 : 1 : 1E 67 : 1 : 1 to 67 : 1 : 0A |
Trip n-1 statistics and extension |
180 to 209 330 to 339 |
66 : 1 : 1F to 66 : 1 : 3C 67 : 1 : 1F to 67 : 1 : 28 |
Trip n-2 statistics and extension |
210 to 239 360 to 369 |
66 : 1 : 3D to 66 : 1 : 5A 67 : 1 : 3D to 67 : 1 : 46 |
Trip n-3 statistics and extension |
240 to 269 390 to 399 |
66 : 1 : 5B to 66 : 1 : 78 67 : 1 : 5B to 67 : 1 : 64 |
Trip n-4 statistics and extension |
270 to 299 420 to 429 |
66 : 1 : 79 to 66 : 1 : 96 67 : 1 : 79 to 67 : 1 : 82 |
Global Statistics
The global statistics are described in the following table:
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
100-101 |
65 : 01 : 01 - 65 : 01 : 02 |
(Not significant) |
||
102 |
65 : 01 : 03 |
Ulnt |
Ground current trips count |
|
103 |
65 : 01 : 04 |
Ulnt |
Thermal overload trips count |
|
104 |
65 : 01 : 05 |
Ulnt |
Long start trips count |
|
105 |
65 : 01 : 06 |
Ulnt |
Jam trips count |
|
106 |
65 : 01 : 07 |
Ulnt |
Current phase imbalance trips count |
|
107 |
65 : 01 : 08 |
Ulnt |
Undercurrent trips count |
|
109 |
65 : 01 : 0A |
Ulnt |
HMI port trips count |
|
110 |
65 : 01 : 0B |
Ulnt |
Controller internal trips count |
|
111 |
65 : 01 : 0C |
Ulnt |
Internal port trips count |
|
112 |
65 : 01 : 0D |
(Not significant) |
||
113 |
65 : 01 : 0E |
Ulnt |
Network port config trips count |
|
114 |
65 : 01 : 0F |
Ulnt |
Network port trips count |
|
115 |
65 : 01 : 10 |
Ulnt |
Auto-resets count |
|
116 |
65 : 01 : 11 |
Ulnt |
Thermal overload alarms count |
|
117-118 |
65 : 01 : 12 - 65 : 01 : 13 |
UDlnt |
Motor starts count |
|
119-120 |
65 : 01 : 14 - 65 : 01 : 15 |
UDlnt |
Operating time (s) |
|
121 |
65 : 01 : 16 |
lnt |
Controller internal temperature max (°C) |
LTM Monitoring Statistics
The LTM monitoring statistics are described in the following table:
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
122 |
65 : 01 : 17 |
Ulnt |
Trips count |
|
123 |
65 : 01 : 18 |
Ulnt |
Alarms count |
|
124-125 |
65 : 01 : 14 - 65 : 01 : 1A |
UDlnt |
Motor LO1 closings count |
|
126-127 |
65 : 01 : 1B - 65 : 01 : 1C |
UDlnt |
Motor LO2 closings count |
|
128 |
65 : 01 : 1C |
Ulnt |
Diagnostic trips count |
|
129 |
65 : 01 : 1E |
(Reserved) |
||
130 |
65 : 01 : 1F |
Ulnt |
Overcurrent trips count |
|
131 |
65 : 01 : 20 |
Ulnt |
Current phase loss trips count |
|
132 |
65 : 01 : 21 |
Ulnt |
Motor temperature sensor trips count |
|
133 |
65 : 01 : 22 |
Ulnt |
Voltage phase imbalance trips count |
1 |
134 |
65 : 01 : 23 |
Ulnt |
Voltage phase loss trips count |
1 |
135 |
65 : 01 : 24 |
Ulnt |
Wiring trips count |
1 |
136 |
65 : 01 : 25 |
Ulnt |
Undervoltage trips count |
1 |
137 |
65 : 01 : 26 |
Ulnt |
Overvoltage trips count |
1 |
138 |
65 : 01 : 27 |
Ulnt |
Underpower trips count |
1 |
139 |
65 : 01 : 28 |
Ulnt |
Overpower trips count |
1 |
140 |
65 : 01 : 29 |
Ulnt |
Under power factor trips count |
1 |
141 |
65 : 01 : 2A |
Ulnt |
Over power factor trips count |
1 |
142 |
65 : 01 : 2B |
Ulnt |
Load sheddings count |
1 |
143-144 |
65 : 01 : 2C - 65 : 01 : 2D |
UDlnt |
Active power consumption (x 0.1kWh) |
1 |
145-146 |
65 : 01 : 2E - 65 : 01 : 2F |
UDlnt |
Reactive power consumption (x 0.1 kVARh) |
1 |
147 |
65 : 01 : 30 |
Ulnt |
Auto restart immediate count |
|
148 |
65 : 01 : 31 |
Ulnt |
Auto restart delayed count |
|
149 |
65 : 01 : 32 |
Ulnt |
Auto restart manual count |
Last Trip (n-0) Statistics
The last trip statistics are completed by variables at addresses 300 to 309.
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
150 |
66 : 01 : 01 |
Ulnt |
Trip code n-0 |
|
151 |
66 : 01 : 02 |
Ulnt |
Motor full load current ratio n-0 (% FLC max) |
|
152 |
66 : 01 : 03 |
Ulnt |
Thermal capacity level n-0 (% trip level) |
|
153 |
66 : 01 : 04 |
Ulnt |
Average current ratio n-0 (% FLC) |
|
154 |
66 : 01 : 05 |
Ulnt |
L1 current ratio n-0 (% FLC) |
|
155 |
66 : 01 : 06 |
Ulnt |
L2 current ratio n-0 (% FLC) |
|
156 |
66 : 01 : 07 |
Ulnt |
L3 current ratio n-0 (% FLC) |
|
157 |
66 : 01 : 08 |
Ulnt |
Ground current ratio n-0 (x 0.1 % FLC min) |
|
158 |
66 : 01 : 09 |
Ulnt |
Full load current max n-0 (x 0.1 A) |
|
159 |
66 : 01 : 0A |
Ulnt |
Current phase imbalance n-0 (%) |
|
160 |
66 : 01 : 0B |
Ulnt |
Frequency n-0 (x 0.1 Hz) |
2 |
161 |
66 : 01 : 0C |
Ulnt |
Motor temperature sensor n-0 (x 0.1 Ω) |
|
162-165 |
65 : 01 : 2D - 65 : 01 : 10 |
Word[4] |
Date and time n-0 DT_DateTime |
|
166 |
66 : 01 : 11 |
Ulnt |
Average voltage n-0 (V) |
1 |
167 |
66 : 01 : 12 |
Ulnt |
L3-L1 voltage n-0 (V) |
1 |
168 |
66 : 01 : 13 |
Ulnt |
L1-L2 voltage n-0 (V) |
1 |
169 |
66 : 01 : 14 |
Ulnt |
L2-L3 voltage n-0 (V) |
1 |
170 |
66 : 01 : 15 |
Ulnt |
Voltage phase imbalance n-0 (%) |
1 |
171 |
66 : 01 : 16 |
Ulnt |
Active power n-0 (x 0.1 kWh) |
1 |
172 |
66 : 01 : 17 |
Ulnt |
Power factor n-0 (x 0.01) |
1 |
173-179 |
66 : 01 : 18 - 66 : 01 : 1E |
(Not significant) |
N-1 Trip Statistics
The n-1 trip statistics are completed by variables at addresses 330 to 339.
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
180 |
66 : 01 : 1F |
Ulnt |
Trip code n-1 |
|
181 |
66 : 01 : 20 |
Ulnt |
Motor full load current ratio n-1 (% FLC max) |
|
182 |
66 : 01 : 21 |
Ulnt |
Thermal capacity level n-1 (% trip level) |
|
183 |
66 : 01 : 22 |
Ulnt |
Average current ratio n-1 (% FLC) |
|
184 |
66 : 01 : 23 |
Ulnt |
L1 current ratio n-1 (% FLC) |
|
185 |
66 : 01 : 24 |
Ulnt |
L2 current ratio n-1 (% FLC) |
|
186 |
66 : 01 : 25 |
Ulnt |
L3 current ratio n-1 (% FLC) |
|
187 |
66 : 01 : 26 |
Ulnt |
Ground current ratio n-1 (x 0.1 % FLC min) |
|
188 |
66 : 01 : 27 |
Ulnt |
Full load current max n-1 (x 0.1 A) |
|
189 |
66 : 01 : 28 |
Ulnt |
Current phase imbalance n-1 (%) |
|
190 |
66 : 01 : 29 |
Ulnt |
Frequency n-1 (x 0.1 Hz) |
2 |
191 |
66 : 01 : 2A |
Ulnt |
Motor temperature sensor n-1 (x 0.1 Ω) |
|
192-195 |
66 : 01 : 2B - 66 : 01 : 2E |
Word[4] |
Date and time n-1 DT_DateTime |
|
196 |
66 : 01 : 2F |
Ulnt |
Average voltage n-1 (V) |
1 |
197 |
66 : 01 : 30 |
Ulnt |
L3-L1 voltage n-1 (V) |
1 |
198 |
66 : 01 : 31 |
Ulnt |
L1-L2 voltage n-1 (V) |
1 |
199 |
66 : 01 : 32 |
Ulnt |
L2-L3 voltage n-1 (V) |
1 |
200 |
66 : 01 : 33 |
Ulnt |
Voltage phase imbalance n-1 (%) |
1 |
201 |
66 : 01 : 34 |
Ulnt |
Active power n-1 (x 0.1 kWh) |
1 |
202 |
66 : 01 : 35 |
Ulnt |
Power factor n-1 (x 0.01) |
1 |
203-209 |
66 : 01 : 36 - 66 : 01 : 3C |
(Not significant) |
N-2 Trip Statistics
The n-2 trip statistics are completed by variables at addresses 360 to 369.
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
210 |
66 : 01 : 3D |
Ulnt |
Trip code n-2 |
|
211 |
66 : 01 : 3E |
Ulnt |
Motor full load current ratio n-2 (% FLC max) |
|
212 |
66 : 01 : 3F |
Ulnt |
Thermal capacity level n-2 (% trip level) |
|
213 |
66 : 01 : 40 |
Ulnt |
Average current ratio n-2 (% FLC) |
|
214 |
66 : 01 : 41 |
Ulnt |
L1 current ratio n-2 (% FLC) |
|
215 |
66 : 01 : 42 |
Ulnt |
L2 current ratio n-2 (% FLC) |
|
216 |
66 : 01 : 43 |
Ulnt |
L3 current ratio n-2 (% FLC) |
|
217 |
66 : 01 : 44 |
Ulnt |
Ground current ratio n-2 (x 0.1% FLC min) |
|
218 |
66 : 01 : 45 |
Ulnt |
Full load current max n-2 (x 0.1 A) |
|
219 |
66 : 01 : 46 |
Ulnt |
Current phase imbalance n-2 (%) |
|
220 |
66 : 01 : 47 |
Ulnt |
Frequency n-2 (x 0.1 Hz) |
2 |
221 |
66 : 01 : 48 |
Ulnt |
Motor temperature sensor n-2 (x 0.1 Ω) |
|
222-225 |
66 : 01 : 49 - 66 : 01 : 4C |
Word[4] |
Date and time n-2 DT_DateTime |
|
226 |
66 : 01 : 4D |
Ulnt |
Average voltage n-2 (V) |
1 |
227 |
66 : 01 : 4E |
Ulnt |
L3-L1 voltage n-2 (V) |
1 |
228 |
66 : 01 : 4F |
Ulnt |
L1-L2 voltage n-2 (V) |
1 |
229 |
66 : 01 : 50 |
Ulnt |
L2-L3 voltage n-2 (V) |
1 |
230 |
66 : 01 : 51 |
Ulnt |
Voltage phase imbalance n-2 (%) |
1 |
231 |
66 : 01 : 52 |
Ulnt |
Active power n-2 (x 0.1 kWh) |
1 |
232 |
66 : 01 : 53 |
Ulnt |
Power factor n-2 (x 0.01) |
1 |
233-239 |
66 : 01 : 54 - 66 : 01 : 5A |
(Not significant) |
N-3 Trip Statistics
The n-3 trip statistics are completed by variables at addresses 390 to 399.
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
240 |
66 : 01 : 5B |
Ulnt |
Trip code n-3 |
|
241 |
66 : 01 : 5C3 |
Ulnt |
Motor full load current ratio n-3 (% FLC max) |
|
242 |
66 : 01 : 5D |
Ulnt |
Thermal capacity level n-3 (% trip level) |
|
243 |
66 : 01 : 5E |
Ulnt |
Average current ratio n-3 (% FLC) |
|
244 |
66 : 01 : 5F |
Ulnt |
L1 current ratio n-3 (% FLC) |
|
245 |
66 : 01 : 60 |
Ulnt |
L2 current ratio n-3 (% FLC) |
|
246 |
66 : 01 : 61 |
Ulnt |
L3 current ratio n-3 (% FLC) |
|
247 |
66 : 01 : 62 |
Ulnt |
Ground current ratio n-3 (x 0.1 % FLC min) |
|
248 |
66 : 01 : 63 |
Ulnt |
Full load current max n-3 (0.1 A) |
|
249 |
66 : 01 : 64 |
Ulnt |
Current phase imbalance n-3 (%) |
|
250 |
66 : 01 : 65 |
Ulnt |
Frequency n-3 (x 0.1 Hz) |
2 |
251 |
66 : 01 : 66 |
Ulnt |
Motor temperature sensor n-3 (x 0.1 Ω) |
|
252-255 |
66 : 01 : 67 - 66 : 01 : 6A |
Word[4] |
Date and time n-3 DT_DateTime |
|
256 |
66 : 01 : 6B |
Ulnt |
Average voltage n-3 (V) |
1 |
257 |
66 : 01 : 6C |
Ulnt |
L3-L1 voltage n-3 (V) |
1 |
258 |
66 : 01 : 6D |
Ulnt |
L1-L2 voltage n-3 (V) |
1 |
259 |
66 : 01 : 6E |
Ulnt |
L2-L3 voltage n-3 (V) |
1 |
260 |
66 : 01 : 6F |
Ulnt |
Voltage phase imbalance n-3 (%) |
1 |
261 |
66 : 01 : 70 |
Ulnt |
Active power n-3 (x 0.1 kWh) |
1 |
262 |
66 : 01 : 71 |
Ulnt |
Power factor n-3 (x 0.01) |
1 |
263-269 |
66 : 01 : 72 - 66 : 01 : 78 |
(Not significant) |
N-4 Trip Statistics
The n-4 trip statistics are completed by variables at addresses 420 to 429.
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
270 |
66 : 01 : 79 |
Ulnt |
Trip code n-4 |
|
271 |
66 : 01 : 7A |
Ulnt |
Motor full load current ratio n-4 (% FLC max) |
|
272 |
66 : 01 : 7B |
Ulnt |
Thermal capacity level n-4 (% trip level) |
|
273 |
66 : 01 : 7C |
Ulnt |
Average current ratio n-4 (% FLC) |
|
274 |
66 : 01 : 7D |
Ulnt |
L1 current ratio n-4 (% FLC) |
|
275 |
66 : 01 : 7E |
Ulnt |
L2 current ratio n-4 (% FLC)) |
|
276 |
66 : 01 : 7F |
Ulnt |
L3 current ratio n-4 (% FLC) |
|
277 |
66 : 01 : 80 |
Ulnt |
Ground current ratio n-4 (x 0.1 % FLC min) |
|
278 |
66 : 01 : 81 |
Ulnt |
Full load current max n-4 (x 0.1 A) |
|
279 |
66 : 01 : 82 |
Ulnt |
Current phase imbalance n-4 (%) |
|
280 |
66 : 01 : 83 |
Ulnt |
Frequency n-4 (x 0.1 Hz) |
2 |
281 |
66 : 01 : 84 |
Ulnt |
Motor temperature sensor n-4 (x 0.1 Ω) |
|
282-285 |
66 : 01 : 85 - 66 : 01 : 88 |
Word[4] |
Date and time n-4 DT_DateTime |
|
286 |
66 : 01 : 89 |
Ulnt |
Average voltage n-4 (V) |
1 |
287 |
66 : 01 : 8A |
Ulnt |
L3-L1 voltage n-4 (V) |
1 |
288 |
66 : 01 : 8B |
Ulnt |
L1-L2 voltage n-4 (V) |
1 |
289 |
66 : 01 : 8C |
Ulnt |
L2-L3 voltage n-4 (V) |
1 |
290 |
66 : 01 : 8D |
Ulnt |
Voltage phase imbalance n-4 (x 1%) |
1 |
291 |
66 : 01 : 8E |
Ulnt |
Active power n-4 (x 0.1 kWh) |
1 |
292 |
66 : 01 : 8F |
Ulnt |
Power factor n-4 (x 0.01) |
1 |
293-299 |
66 : 01 : 90 - 66 : 01 : 96 |
(Not significant) |
Last Trip (n-0) Statistics Extension
The last trip main statistics are listed at addresses 150 to 179.
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
300-301 |
67 : 01 : 01 - 67 : 01 : 02 |
UDlnt |
Average current n-0 (x 0.01 A) |
|
302-303 |
67 : 01 : 03 - 67 : 01 : 04 |
UDlnt |
L1 current n-0 (x 0.01 A) |
|
304-305 |
67 : 01 : 05 - 67 : 01 : 06 |
UDlnt |
L2 current n-0 (x 0.01 A) |
|
306-307 |
67 : 01 : 07 - 67 : 01 : 08 |
UDlnt |
L3 current n-0 (x 0.01 A) |
|
308-309 |
67 : 01 : 09 - 67 : 01 : 0A |
UDlnt |
Ground current n-0 (mA) |
|
310 |
67 : 01 : 0B |
Ulnt |
Motor temperature sensor degree n-0 (°C) |
N-1 Trip Statistics Extension
The n-1 trip main statistics are listed at addresses 180 to 209.
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
330-331 |
67 : 01 : 1F - 67 : 01 : 20 |
UDlnt |
Average current n-1 (x 0.01 A) |
|
332-333 |
67 : 01 : 21 - 67 : 01 : 22 |
UDlnt |
L1 current n-1 (x 0.01 A) |
|
334-335 |
67 : 01 : 23 - 67 : 01 : 24 |
UDlnt |
L2 current n-1 (x 0.01 A) |
|
336-337 |
67 : 01 : 25 - 67 : 01 : 26 |
UDlnt |
L3 current n-1 (x 0.01 A) |
|
338-339 |
67 : 01 : 27 - 67 : 01 : 28 |
UDlnt |
Ground current n-1 (mA) |
|
340 |
67 : 01 : 29 |
Ulnt |
Motor temperature sensor degree n-1 (°C) |
N-2 Trip Statistics Extension
The n-2 trip main statistics are listed at addresses 210 to 239.
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
360-361 |
67 : 01 : 3D - 67 : 01 : 3E |
UDlnt |
Average current n-2 (x 0.01 A) |
|
362-363 |
67 : 01 : 3F - 67 : 01 : 40 |
UDlnt |
L1 current n-2 (x 0.01 A) |
|
364-365 |
67 : 01 : 41 - 67 : 01 : 42 |
UDlnt |
L2 current n-2 (x 0.01 A) |
|
366-367 |
67 : 01 : 43 - 67 : 01 : 44 |
UDlnt |
L3 current n-2 (x 0.01 A) |
|
368-369 |
67 : 01 : 45 - 67 : 01 : 46 |
UDlnt |
Ground current n-2 (mA) |
|
370 |
67 : 01 : 47 |
Ulnt |
Motor temperature sensor degree n-2 (°C) |
N-3 Trip Statistics Extension
The n-3 trip main statistics are listed at addresses 240 to 269.
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
390-391 |
67 : 01 : 5B - 67 : 01 : 5C |
UDlnt |
Average current n-3 (x 0.01 A) |
|
392-393 |
67 : 01 : 5D - 67 : 01 : 5E |
UDlnt |
L1 current n-3 (x 0.01 A) |
|
394-395 |
67 : 01 : 5F - 67 : 01 : 60 |
UDlnt |
L2 current n-3 (x 0.01 A) |
|
396-397 |
67 : 01 : 61 - 67 : 01 : 62 |
UDlnt |
L3 current n-3 (x 0.01 A) |
|
398-399 |
67 : 01 : 63 - 67 : 01 : 64 |
UDlnt |
Ground current n-3 (mA) |
|
400 |
67 : 01 : 65 |
Ulnt |
Motor temperature sensor degree n-3 (°C) |
N-4 Trip Statistics Extension
The n-4 trip main statistics are listed at addresses 270 to 299.
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
420-421 |
67 : 01 : 79 - 67 : 01 : 7A |
UDlnt |
Average current n-4 (x 0.01 A) |
|
422-423 |
67 : 01 : 7B - 67 : 01 : 7C |
UDlnt |
L1 current n-4 (x 0.01 A) |
|
424-425 |
67 : 01 : 7D - 67 : 01 : 7E |
UDlnt |
L2 current n-4 (x 0.01 A) |
|
426-427 |
67 : 01 : 7F - 67 : 01 : 80 |
UDlnt |
L3 current n-4 (x 0.01 A) |
|
428-429 |
67 : 01 : 81 - 67 : 01 : 82 |
UDlnt |
Ground current n-4 (mA) |
|
430 |
67 : 01 : 83 |
Ulnt |
Motor temperature sensor degree n-4 (°C) |
Monitoring Variables
Monitoring Overview
Monitoring variables are grouped according to the following criteria:
Monitoring Variable Groups |
Registers |
DeviceNet Addresses |
---|---|---|
Monitoring of trips |
450 to 454 |
68 : 01 : 01 to 68 : 01 : 05 |
Monitoring of status |
455 to 459 |
68 : 01 : 06 to 68 : 01 : 0A |
Monitoring of alarms |
460 to 464 |
68 : 01 : 0B to 68 : 01 : 0F |
Monitoring of measurements |
465 to 539 |
68 : 01 : 10 to 68 : 01 : 5A |
Monitoring of Trips
Variables for monitoring of trips are described in the following table:
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
450 |
68 : 01 : 01 |
Ulnt |
Minimum wait time (s) |
|
451 |
68 : 01 : 02 |
Ulnt |
Trip code (code of the last trip, or of the trip that takes priority) DT_TripCode |
|
452 |
68 : 01 : 03 |
Word |
Trip register 1 |
|
bits 0-1 (Reserved) |
||||
bit 2 Ground current trip |
||||
bit 3 Thermal overload trip |
||||
bit 4 Long start trip |
||||
bit 5 Jam trip |
||||
bit 6 Current phase imbalance trip |
||||
bit 7 Undercurrent trip |
||||
bit 8 (Reserved) |
||||
bit 9 Test trip |
||||
bit 10 HMI port trip |
||||
bit 11 Controller internal trip |
||||
bit 12 Internal port trip |
||||
bit 13 (Not significant) |
||||
bit 14 Network port config trip |
||||
bit 15 Network port trip |
||||
453 |
68 : 01 : 04 |
Word
|
Trip register 2 |
|
bit 0 External system trip |
||||
bit 1 Diagnostic trip |
||||
bit 2 Wiring trip |
||||
bit 3 Overcurrent trip |
||||
bit 4 Current phase loss trip |
||||
bit 5 Current phase reversal trip |
||||
bit 6 Motor temperature sensor trip |
1 |
|||
bit 7 Voltage phase imbalance trip |
1 |
|||
bit 8 Voltage phase loss trip |
1 |
|||
bit 9 Voltage phase reversal trip |
1 |
|||
bit 10 Undervoltage trip |
1 |
|||
bit 11 Overvoltage trip |
1 |
|||
bit 12 Underpower trip |
1 |
|||
bit 13 Overpower trip |
1 |
|||
bit 14 Under power factor trip |
1 |
|||
bit 15 Over power factor trip |
1 |
|||
454 |
68 : 01 : 05 |
Word |
Trip register 3 |
|
bit 0 LTME configuration trip |
||||
bits 1-15 (Reserved) |
Monitoring of Status
Variables for monitoring of status are described in the following table:
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
455 |
68 : 01 : 06 |
Word
|
System status register 1 |
|
bit 0 System ready |
||||
bit 1 System on |
||||
bit 2 System trip |
||||
bit 3 System alarm |
||||
bit 4 System tripped |
||||
bit 5 Trip reset authorized |
||||
bit 6 Controller power |
||||
bit 7 Motor running (with detection of a current, if greater than 10% FLC) |
||||
bits 8-13 Motor average current ratio 32 = 100% FLC - 63 = 200% FLC |
||||
bit 14 In remote |
||||
bit 15 Motor starting (start in progress) 0 = descending current is less than 150% FLC 1 = ascending current is greater than 10% FLC |
||||
456 |
68 : 01 : 07 |
Word |
System status register 2 |
|
bit 0 Auto-reset active |
||||
bit 1 (Not significant) |
||||
bit 2 Trip power cycle requested |
||||
bit 3 Motor restart time undefined |
||||
bit 4 Rapid cycle lockout |
||||
bit 5 Load shedding |
1 |
|||
bit 6 Motor speed 0 = FLC1 setting is used 1 = FLC2 setting is used |
||||
bit 7 HMI port comm loss |
||||
bit 8 Network port comm loss |
||||
bit 9 Motor transition lockout |
||||
bits 10-15 (Not significant) |
||||
457 |
68 : 01 : 08 |
Word |
Logic inputs status |
|
bit 0 Logic input 1 |
||||
bit 1 Logic input 2 |
||||
bit 2 Logic input 3 |
||||
bit 3 Logic input 4 |
||||
bit 4 Logic input 5 |
||||
bit 5 Logic input 6 |
||||
bit 6 Logic input 7 |
||||
bit 7 Logic input 8 |
1 |
|||
bit 8 Logic input 9 |
1 |
|||
bit 9 Logic input 10 |
1 |
|||
bit 10 Logic input 11 |
1 |
|||
bit 11 Logic input 12 |
1 |
|||
bit 12 Logic input 13 |
1 |
|||
bit 13 Logic input 14 |
1 |
|||
bit 14 Logic input 15 |
1 |
|||
bit 15 Logic input 16 |
1 |
|||
458 |
68 : 01 : 09 |
Word |
Logic outputs status |
|
bit 0 Logic output 1 |
||||
bit 1 Logic output 2 |
||||
bit 2 Logic output 3 |
||||
bit 3 Logic output 4 |
||||
bit 4 Logic output 5 |
1 |
|||
bit 5 Logic output 6 |
1 |
|||
bit 6 Logic output 7 |
1 |
|||
bit 7 Logic output 8 |
1 |
|||
bits 8-15 (Reserved) |
||||
459 |
68 : 01 : 0A |
Word |
I/O status |
|
bit 0 Input 1 |
||||
bit 1 Input 2 |
||||
bit 2 Input 3 |
||||
bit 3 Input 4 |
||||
bit 4 Input 5 |
||||
bit 5 Input 6 |
||||
bit 6 Input 7 |
||||
bit 7 Input 8 |
||||
bit 8 Input 9 |
||||
bit 9 Input 10 |
||||
bit 10 Input 11 |
||||
bit 11 Input 12 |
||||
bit 12 Output 1 (13-14) |
||||
bit 13 Output 2 (23-24) |
||||
bit 14 Output 3 (33-34) |
||||
bit 15 Output 4 (95-96, 97-98) |
Monitoring of Alarms
Variables for monitoring of alarms are described in the following table:
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
460 |
68 : 01 : 0B |
UInt |
Alarm code DT_AlarmCode |
|
461 |
68 : 01 : 0C |
Word |
Alarm register 1 |
|
bits 0-1 (Not significant) |
||||
bit 2 Ground current alarm |
||||
bit 3 Thermal overload alarm |
||||
bit 4 (Not significant) |
||||
bit 5 Jam alarm |
||||
bit 6 Current phase imbalance alarm |
||||
bit 7 Undercurrent alarm |
||||
bits 8-9 (Not significant) |
||||
bit 10 HMI port alarm |
||||
bit 11 Controller internal temperature alarm |
||||
bits 12-14 (Not significant) |
||||
bit 15 Network port alarm |
||||
462 |
68 : 01 : 0D |
Word
|
Alarm register 2 |
|
bit 0 (Not significant) |
||||
bit 1 Diagnostic alarm |
||||
bit 2 (Reserved) |
||||
bit 3 Overcurrent alarm |
||||
bit 4 Current phase loss alarm |
||||
bit 5 Current phase reversal alarm |
||||
bit 6 Motor temperature sensor alarm |
||||
bit 7 Voltage phase imbalance alarm |
1 |
|||
bit 8 Voltage phase loss alarm |
1 |
|||
bit 9 (Not significant) |
||||
bit 10 Undervoltage alarm |
1 |
|||
bit 11 Overvoltage alarm |
1 |
|||
bit 12 Underpower alarm |
1 |
|||
bit 13 Overpower alarm |
1 |
|||
bit 14 Under power factor alarm |
1 |
|||
bit 15 Over power factor alarm |
1 |
|||
463 |
68 : 01 : 0E |
Word |
Alarm register 3 |
|
bit 0 LTME configuration alarm |
||||
bits 1-15 (Reserved) |
||||
464 |
68 : 01 : 0F |
Ulnt |
Motor temperature sensor degree (°C) |
Monitoring of Measurements
Variables for monitoring of measurements are described in the following table:
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
465 |
68 : 01 : 10 |
UInt |
Thermal capacity level (% trip level) |
|
466 |
68 : 01 : 11 |
UInt |
Average current ratio (% FLC) |
|
467 |
68 : 01 : 12 |
UInt |
L1 current ratio (% FLC) |
|
468 |
68 : 01 : 13 |
UInt |
L2 current ratio (% FLC) |
|
469 |
68 : 01 : 14 |
UInt |
L3 current ratio (% FLC) |
|
470 |
68 : 01 : 15 |
UInt |
Ground current ratio (x 0.1 % FLC min) |
|
471 |
68 : 01 : 16 |
UInt |
Current phase imbalance (%) |
|
472 |
68 : 01 : 17 |
Int |
Controller internal temperature (°C) |
|
473 |
68 : 01 : 18 |
UInt |
Controller config checksum |
|
474 |
68 : 01 : 19 |
UInt |
Frequency (x 0.01 Hz) |
2 |
475 |
68 : 01 : 1A |
UInt |
Motor temperature sensor (x 0.1 Ω) |
|
476 |
68 : 01 : 1B |
UInt |
Average voltage (V) |
1 |
477 |
68 : 01 : 1C |
UInt |
L3-L1 voltage (V) |
1 |
478 |
68 : 01 : 1D |
UInt |
L1-L2 voltage (V) |
1 |
479 |
68 : 01 : 1E |
UInt |
L2-L3 voltage (V) |
1 |
480 |
68 : 01 : 1F |
UInt |
Voltage phase imbalance (%) |
1 |
481 |
68 : 01 : 20 |
UInt |
Power factor (x 0.01) |
1 |
482 |
68 : 01 : 21 |
UInt |
Active power (x 0.1 kW) |
1 |
483 |
68 : 01 : 22 |
UInt |
Reactive power (x 0.1 kVAR) |
1 |
484 |
68 : 01 : 23 |
Word |
Auto restart status register |
|
bit 0 Voltage dip occurred |
||||
bit 1 Voltage dip detection |
||||
bit 2 Auto restart immediate condition |
||||
bit 3 Auto restart delayed condition |
||||
bit 4 Auto restart manual condition |
||||
bits 5-15 (Not significant) |
||||
485 |
68 : 01 : 24 |
Word |
Controller last power OFF duration |
|
486-489 |
68 : 01 : 25 - 68 : 01 : 28 |
(Not significant) |
||
490 |
68 : 01 : 29 |
Word |
Network port monitoring |
|
bit 0 Network port communicating |
||||
bit 1 Network port connected |
||||
bit 2 Network port self-testing |
||||
bit 3 Network port self-detecting |
||||
bit 4 Network port bad config |
||||
bits 5-15 (Not significant) |
||||
491 |
68 : 01 : 2A |
UInt |
Network port baud rate DT_ExtBaudRate |
|
492 |
68 : 01 : 2B |
(Not significant) |
||
493 |
68 : 01 : 2C |
UInt |
Network port parity DT_ExtParity |
|
494-499 |
68 : 01 : 2D - 68 : 01 : 32 |
(Not significant) |
||
500-501 |
68 : 01 : 33 - 68 : 01 : 34 |
UDInt |
Average current (x 0.01 A) |
|
502-503 |
68 : 01 : 35 - 68 : 01 : 36 |
UDInt |
L1 current (x 0.01 A) |
|
504-505 |
68 : 01 : 37 - 68 : 01 : 38 |
UDInt |
L2 current (x 0.01 A) |
|
506-507 |
68 : 01 : 39 - 68 : 01 : 3A |
UDInt |
L3 current (x 0.01 A) |
|
508-509 |
68 : 01 : 3B - 68 : 01 : 3C |
UDInt |
Ground current (mA) |
|
510 |
68 : 01 : 3D |
UInt |
Controller port ID |
|
511 |
68 : 01 : 3E |
UInt |
Time to trip (x 1 s) |
|
512 |
68 : 01 : 3F |
UInt |
Motor last start current ratio (% FLC) |
|
513 |
68 : 01 : 40 |
UInt |
Motor last start duration (s) |
|
514 |
68 : 01 : 41 |
UInt |
Motor starts per hour count |
|
515 |
68 : 01 : 42 |
Word
|
Phase imbalances register |
|
bit 0 L1 current highest imbalance |
||||
bit 1 L2 current highest imbalance |
||||
bit 2 L3 current highest imbalance |
||||
bit 3 L1-L2 voltage highest imbalance |
1 |
|||
bit 4 L2-L3 voltage highest imbalance |
1 |
|||
bit 5 L3-L1 voltage highest imbalance |
1 |
|||
bits 6-15 (Not significant) |
||||
516-523 |
68 : 01 : 43 - 68 : 01 : 5A |
(Reserved) |
||
524-539 |
68 : 01 : 4B - 68 : 01 : 5A |
(Forbidden) |
Configuration Variables
Configuration Overview
Configuration variables are grouped according to the following criteria
Configuration Variable Groups |
Registers |
DeviceNet Addresses |
---|---|---|
Configuration |
540 to 649 |
69 : 01 : 01 to 6A : 01 : 32 |
Setting |
650 to 699 |
6B : 01 : 01 to 6B : 01 : 32 |
Configuration Variables
The configuration variables are described in the following tables:
Register |
DeviceNet Address |
Variable Type |
Read/Write Variables |
|
---|---|---|---|---|
540 |
69 : 01 : 01 |
UInt |
Motor operating mode 2 = 2-wire overload 3 = 3-wire overload 4 = 2-wire independent 5 = 3-wire independent 6 = 2-wire reverser 7 = 3-wire reverser 8 = 2-wire 2-step 9 = 3-wire 2-step 10 = 2-wire 2-speed 11 = 3-wire 2-speed 256-511 = Custom logic program (0-255) |
B |
541 |
69 : 01 : 02 |
UInt |
Motor transition timeout (s) DT_ACInputSetting |
|
542-544 |
69 : 01 : 03 - 6A : 01 : 05 |
(Reserved) |
||
545 |
69 : 01 : 06 |
Word |
Controller AC inputs setting register |
|
bits 0-3 Controller AC logic inputs configuration DT_ACInputSetting |
||||
bits 4-15 (Reserved) |
||||
546 |
69 : 01 : 07 |
UInt |
Thermal overload setting |
B |
bits 0-2 Motor temperature sensor type: 0 = None 1 = PTC binary 2 = PT100 3 = PTC analog 4 = NTC analog |
||||
bits 3-4 Thermal overload mode: 0 = Definite 2 = Inverse thermal |
||||
bits 5-15 (Reserved) |
||||
547 |
69 : 01 : 08 |
UInt |
Thermal overload trip definite timeout (s) |
|
548 |
6A : 01 : 09 |
(Reserved) |
||
549 |
69 : 01 : 0A |
UInt |
Motor temperature sensor trip threshold (x 0.1 Ω) |
|
550 |
69 : 01 : 0B |
UInt |
Motor temperature sensor alarm threshold (x 0.1 Ω) |
|
551 |
69 : 01 : 0C |
UInt |
Motor temperature sensor trip threshold degree (°C) |
|
552 |
6A : 01 : 0D |
UInt |
Motor temperature sensor alarm threshold degree (°C) |
|
553 |
69 : 01 : 0E |
UInt |
Rapid cycle lockout timeout (s) |
|
554 |
69 : 01 : 0F |
(Reserved) |
||
555 |
69 : 01 : 10 |
UInt |
Current phase loss timeout (x 0.1 s) |
|
556 |
69 : 01 : 11 |
UInt |
Overcurrent trip timeout (s) |
|
557 |
69 : 01 : 12 |
UInt |
Overcurrent trip threshold (% FLC) |
|
558 |
69 : 01 : 13 |
UInt |
Overcurrent alarm threshold (% FLC) |
|
559 |
69 : 01 : 14 |
Word |
Ground current trip configuration |
B |
bit 0 Ground current mode |
||||
bits 1-15 (Reserved) |
||||
560 |
69 : 01 : 15 |
UInt |
Ground current sensor primary |
|
561 |
69 : 01 : 16 |
UInt |
Ground current sensor secondary |
|
562 |
69 : 01 : 17 |
UInt |
External ground current trip timeout (x 0.01 s) |
|
563 |
69 : 01 : 18 |
UInt |
External ground current trip threshold (x 0.01 A) |
|
564 |
69 : 01 : 19 |
UInt |
External ground current alarm threshold (x 0.01 A) |
|
565 |
69 : 01 : 1A |
UInt |
Motor nominal voltage (V) |
1 |
566 |
69 : 01 : 1B |
UInt |
Voltage phase imbalance trip timeout starting (x 0.1 s) |
1 |
567 |
69 : 01 : 1C |
UInt |
Voltage phase imbalance trip timeout running (x 0.1 s) |
1 |
568 |
69 : 01 : 1D |
UInt |
Voltage phase imbalance trip threshold (% imb) |
1 |
569 |
69 : 01 : 1E |
UInt |
Voltage phase imbalance alarm threshold (% imb) |
1 |
570 |
69 : 01 : 1F |
UInt |
Overvoltage trip timeout (x 0.1 s) |
1 |
571 |
69 : 01 : 20 |
UInt |
Overvoltage trip threshold (% Vnom) |
1 |
572 |
69 : 01 : 21 |
UInt |
Overvoltage alarm threshold (% Vnom) |
1 |
573 |
69 : 01 : 22 |
UInt |
Undervoltage trip timeout (x 0.1 s) |
1 |
574 |
69 : 01 : 23 |
UInt |
Undervoltage trip threshold (% Vnom) |
1 |
575 |
69 : 01 : 24 |
UInt |
Undervoltage alarm threshold (% Vnom) |
1 |
576 |
69 : 01 : 25 |
UInt |
Voltage phase loss trip timeout (x 0.1 s) |
1 |
577 |
69 : 01 : 26 |
Word |
Voltage dip setting |
1 |
bit 0 Load shedding enable |
||||
bit 1 Auto-restart enable |
||||
bits 2-15 (Reserved) |
||||
578 |
69 : 01 : 27 |
UInt |
Load shedding timeout (s) |
1 |
579 |
69 : 01 : 28 |
UInt |
Voltage dip threshold (% Vnom) |
1 |
580 |
69 : 01 : 29 |
UInt |
Voltage dip restart timeout (s) |
1 |
581 |
69 : 01 : 2A |
UInt |
Voltage dip restart threshold (% Vnom) |
1 |
582 |
69 : 01 : 2B |
Ulnt |
Auto restart immediate timeout (x 0.1 s) |
|
583 |
69 : 01 : 2C |
UInt |
Motor nominal power (x 0.1 kW) |
1 |
584 |
69 : 01 : 2D |
UInt |
Overpower trip timeout (s) |
1 |
585 |
69 : 01 : 2E |
UInt |
Overpower trip threshold (% Pnom) |
1 |
586 |
69 : 01 : 2F |
UInt |
Overpower alarm threshold (% Pnom) |
1 |
587 |
69 : 01 : 30 |
UInt |
Underpower trip timeout (s) |
1 |
588 |
69 : 01 : 31 |
UInt |
Underpower trip threshold (% Pnom) |
1 |
589 |
69 : 01 : 32 |
UInt |
Underpower alarm threshold (% Pnom) |
1 |
590 |
69 : 01 : 33 |
UInt |
Under power factor trip timeout (x 0.1 s) |
1 |
591 |
69 : 01 : 34 |
UInt |
Under power factor trip threshold (x 0.01 PF) |
1 |
592 |
69 : 01 : 35 |
UInt |
Under power factor alarm threshold (x 0.01 PF) |
1 |
593 |
69 : 01 : 36 |
UInt |
Over power factor trip timeout (x 0.1 s) |
1 |
594 |
69 : 01 : 37 |
UInt |
Over power factor trip threshold (x 0.01 PF) |
1 |
595 |
69 : 01 : 38 |
UInt |
Over power factor alarm threshold (x 0.01 PF) |
1 |
596 |
69 : 01 : 39 |
UInt |
Auto restart delayed timeout (s) |
|
597-599 |
69 : 01 : 3A - 69 : 01 : 3C |
(Reserved) |
||
600 |
6A : 01 : 01 |
(Not significant) |
||
601 |
6A : 01 : 02 |
Word |
General configuration register 1 |
|
bit 0 Controller system config required: 0 = exit the configuration menu 1 = go to the configuration menu |
A |
|||
bits 1-7 (Reserved) |
||||
Control mode configuration, bits 8-10 (one bit is set to 1): |
||||
bit 8 Config via HMI keypad enable |
||||
bit 9 Config via HMI engineering tool enable |
||||
bit 10 Config via network port enable |
||||
bit 11 Motor star-delta |
B |
|||
bit 12 Motor phases sequence: 0 = A B C 1 = A C B |
||||
bits 13-14 Motor phases DT_PhaseNumber |
B |
|||
bit 15 Motor auxiliary fan cooled (factory setting = 0) |
||||
602 |
6A : 01 : 03 |
Word |
General configuration register 2 |
|
bits 0-2 Trip reset mode DT_ResetMode |
C |
|||
bit 3 HMI port parity setting: 0 = none 1 = even (factory setting) |
||||
bits 4-8 (Reserved) |
||||
bit 9 HMI port endian setting |
||||
bit 10 Network port endian setting |
||||
bit 11 HMI motor status LED color |
||||
bits 12-15 (Reserved) |
||||
603 |
6A : 01 : 04 |
Ulnt |
HMI port address setting |
|
604 |
6A : 01 : 05 |
Ulnt |
HMI port baud rate setting (Baud) |
|
605 |
6A : 01 : 06 |
(Reserved) |
||
606 |
6A : 01 : 07 |
Ulnt |
Motor trip class (s) |
|
607 |
6A : 01 : 08 |
(Reserved) |
||
608 |
6A : 01 : 09 |
Ulnt |
Thermal overload trip reset threshold (% trip level) |
|
609 |
6A : 01 : 0A |
Ulnt |
Thermal overload alarm threshold (% trip level) |
|
610 |
6A : 01 : 0B |
UInt |
Internal ground current trip timeout (x 0.1 s) |
|
611 |
6A : 01 : 0C |
UInt |
Internal ground current trip threshold (% FLCmin) |
|
612 |
6A : 01 : 0D |
UInt |
Internal ground current alarm threshold (% FLCmin) |
|
613 |
6A : 01 : 0E |
UInt |
Current phase imbalance trip timeout starting (x 0.1 s) |
|
614 |
6A : 01 : 0F |
UInt |
Current phase imbalance trip timeout running (x 0.1 s) |
|
615 |
6A : 01 : 10 |
UInt |
Current phase imbalance trip threshold (% imb) |
|
616 |
6A : 01 : 11 |
UInt |
Current phase imbalance alarm threshold (% imb) |
|
617 |
6A : 01 : 12 |
UInt |
Jam trip timeout (s) |
|
618 |
6A : 01 : 13 |
UInt |
Jam trip threshold (% FLC) |
|
619 |
6A : 01 : 14 |
UInt |
Jam alarm threshold (% FLC) |
|
620 |
6A : 01 : 15 |
UInt |
Undercurrent trip timeout (s) |
|
621 |
6A : 01 : 16 |
UInt |
Undercurrent trip threshold (% FLC) |
|
622 |
6A : 01 : 17 |
UInt |
Undercurrent alarm threshold (% FLC) |
|
623 |
6A : 01 : 18 |
UInt |
Long start trip timeout (s) |
|
624 |
6A : 01 : 19 |
UInt |
Long start trip threshold (% FLC) |
|
625 |
6A : 01 : 1A |
(Reserved) |
||
626 |
6A : 01 : 1B |
UInt |
HMI display contrast setting |
|
bits 0-7 HMI display contrast setting |
||||
HMI display brightness setting |
||||
627 |
6A : 01 : 1C |
UInt |
Contactor rating (0.1 A) |
|
628 |
6A : 01 : 1D |
UInt |
Load CT primary |
B |
629 |
6A : 01 : 1E |
UInt |
Load CT secondary |
B |
630 |
6A : 01 : 1F |
UInt |
Load CT multiple passes (passes) |
B |
631 |
6A : 01 : 20 |
Word |
Trip enable register 1 |
|
bits 0-1 (Reserved) |
||||
bit 2 Ground current trip enable |
||||
bit 3 Thermal overload trip enable |
||||
bit 4 Long start trip enable |
||||
bit 5 Jam trip enable |
||||
bit 6 Current phase imbalance trip enable |
||||
bit 7 Undercurrent trip enable |
||||
bit 8 (Reserved) |
||||
bit 9 Self test enable 0 = disable 1 = enable (factory setting) |
||||
bit 10 HMI port trip enable |
||||
bits 11-14 (Reserved) |
||||
bit 15 Network port trip enable |
||||
632 |
6A : 01 : 21 |
Word |
Alarm enable register 1 |
|
bit 0 (Not significant) |
||||
bit 1 (Reserved) |
||||
bit 2 Ground current alarm enable |
||||
bit 3 Thermal overload alarm enable |
||||
bit 4 (Reserved) |
||||
bit 5 Jam alarm enable |
||||
bit 6 Current phase imbalance alarm enable |
||||
bit 7 Undercurrent alarm enable |
||||
bits 8-9 (Reserved) |
||||
bit 10 HMI port alarm enable |
||||
bit 11 Controller internal temperature alarm enable |
||||
bits 12-14 (Reserved) |
||||
bit 15 Network port alarm enable |
||||
633 |
6A : 01 : 22 |
Word |
Trip enable register 2 |
|
bit 0 (Reserved) |
||||
bit 1 Diagnostic trip enable |
||||
bit 2 Wiring trip enable |
||||
bit 3 Overcurrent trip enable |
||||
bit 4 Current phase loss trip enable |
||||
bit 5 Current phase reversal trip enable |
||||
bit 6 Motor temperature sensor trip enable |
||||
bit 7 Voltage phase imbalance trip enable |
1 |
|||
bit 8 Voltage phase loss trip enable |
1 |
|||
bit 9 Voltage phase reversal trip enable |
1 |
|||
bit 10 Undervoltage trip enable |
1 |
|||
bit 11 Overvoltage trip enable |
1 |
|||
bit 12 Underpower trip enable |
1 |
|||
bit 13 Overpower trip enable |
1 |
|||
bit 14 Under power factor trip enable |
1 |
|||
bit 15 Over power factor trip enable |
1 |
|||
634 |
6A : 01 : 23 |
Word |
Alarm enable register 2 |
|
bit 0 (Reserved) |
||||
bit 1 Diagnostic alarm enable |
||||
bit 2 (Reserved) |
||||
bit 3 Overcurrent alarm enable |
||||
bit 4 Current phase loss alarm enable |
||||
bit 5 (Reserved) |
||||
bit 6 Motor temperature sensor alarm enable |
||||
bit 7 Voltage phase imbalance alarm enable |
1 |
|||
bit 8 Voltage phase loss alarm enable |
1 |
|||
bit 9 (Reserved) |
1 |
|||
bit 10 Undervoltage alarm enable |
1 |
|||
bit 11 Overvoltage alarm enable |
1 |
|||
bit 12 Underpower alarm enable |
1 |
|||
bit 13 Overpower alarm enable |
1 |
|||
bit 14 Under power factor alarm enable |
1 |
|||
bit 15 Over power factor alarm enable |
1 |
|||
635-6 |
6A : 01 : 24 - 6A : 01 : 25 |
(Reserved) |
||
637 |
6A : 01 : 26 |
UInt |
Auto-reset attempts group 1 setting |
|
638 |
6A : 01 : 27 |
UInt |
Auto-reset group 1 timeout |
|
639 |
6A : 01 : 28 |
UInt |
Auto-reset attempts group 2 setting |
|
640 |
6A : 01 : 29 |
UInt |
Auto-reset group 2 timeout |
|
641 |
6A : 01 : 2A |
UInt |
Auto-reset attempts group 3 setting |
|
642 |
6A : 01 : 2B |
UInt |
Auto-reset group 3 timeout |
|
643 |
6A : 01 : 2C |
UInt |
Motor step 1 to 2 timeout |
|
644 |
6A : 01 : 2D |
UInt |
Motor step 1 to 2 threshold |
|
645 |
6A : 01 : 2E |
UInt |
HMI port fallback setting DT_OutputFallbackStrategy |
|
646-649 |
6A : 01 : 2F - 6A : 01 : 32 |
(Reserved) |
Setting Variables
The setting variables are described in the following table:
Register |
DeviceNet Address |
Variable Type |
Read/Write Variables |
|
---|---|---|---|---|
650 |
6B : 01 : 01 |
Word |
HMI language setting register: |
|
bit 0-4 HMI language setting DT_Language5 |
||||
bits 5-15 (Not significant) |
||||
651 |
6B : 01 : 02 |
Word |
HMI display items register 1 |
|
bit 0 HMI display average current enable |
||||
bit 1 HMI display thermal capacity level enable |
||||
bit 2 HMI display L1 current enable |
||||
bit 3 HMI display L2 current enable |
||||
bit 4 HMI display L3 current enable |
||||
bit 5 HMI display ground current enable |
||||
bit 6 HMI display motor status enable |
||||
bit 7 HMI display current phase imbalance enable |
||||
bit 8 HMI display operating time enable |
||||
bit 9 HMI display I/O status enable |
||||
bit 10 HMI display reactive power enable |
||||
bit 11 HMI display frequency enable |
||||
bit 12 HMI display starts per hour enable |
||||
bit 13 HMI display control mode enable |
||||
bit 14 HMI display start statistics enable |
||||
bit 15 HMI motor temperature sensor enable |
||||
652 |
6B : 01 : 03 |
Ulnt |
Motor full load current ratio, FLC1 (% FLCmax) |
|
653 |
6B : 01 : 04 |
Ulnt |
Motor high speed full load current ratio, FLC2 (% FLCmax) |
|
654 |
6B : 01 : 05 |
Word |
HMI display items register 2 |
|
bit 0 HMI display L1-L2 voltage enable |
1 |
|||
bit 1 HMI display L2-L3 voltage enable |
1 |
|||
bit 2 HMI display L3-L1 voltage enable |
1 |
|||
bit 3 HMI display average voltage enable |
1 |
|||
bit 4 HMI display active power enable |
1 |
|||
bit 5 HMI display power consumption enable |
1 |
|||
bit 6 HMI display power factor enable |
1 |
|||
bit 7 HMI display average current ratio enable |
||||
bit 8 HMI display L1 current ratio enable |
1 |
|||
bit 9 HMI display L2 current ratio enable |
1 |
|||
bit 10 HMI display L3 current ratio enable |
1 |
|||
bit 11 HMI display thermal capacity remaining enable |
||||
bit 12 HMI display time to trip enable |
||||
bit 13 HMI display voltage phase imbalance enable |
1 |
|||
bit 14 HMI display date enable |
||||
bit 15 HMI display time enable |
||||
655-658 |
6B : 01 : 06 - 6B : 01 : 09 |
Word[4] |
Date and time setting DT_DateTime |
|
659 |
6B : 01 : 0A |
Word[4] |
HMI display items register 3 |
|
bit 0 HMI display temperature sensor degree CF |
||||
bits 1-15 (Reserved) |
||||
660-681 |
6B : 01 : 0B - 6B : 01 : 20 |
(Reserved) |
||
682 |
6B : 01 : 21 |
Ulnt |
Network port fallback setting DT_OutputFallbackStrategy |
|
683 |
6B : 01 : 22 |
Word |
Control setting register |
|
bits 0-1 (Reserved) |
||||
bits 2 Control remote local default mode (with LTMCU) 0 = remote 1 = local |
||||
bit 3 (Reserved) |
||||
bit 4 Control remote local buttons enable (with LTMCU) 0 = disable 1 = enable |
||||
bits 5-6 Control remote channel setting (with LTMCU) 0 = network 1 = terminal strip 2 = HMI |
||||
bit 7 (Reserved) |
||||
bit 8 Control local channel setting 0 = terminal strip 1 = HMI |
||||
bit 9 Control direct transition 0 = stop required during transition 1 = stop not required during transition |
||||
bit 10 Control transfer mode 0 = bump 1 = bumpless |
||||
bit 11 Stop terminal strip disable 0 = enable 1 = disable |
||||
bit 12 Stop HMI disable 0 = enable 1 = disable |
||||
bits 13-15 (Reserved) |
||||
684-694 |
6B : 01 : 23 - 6B : 01 : 2D |
(Reserved) |
||
695 |
6B : 01 : 2E |
Ulnt |
Network port baud rate setting (Baud) DT_ExtBaudRate |
|
696 |
6B : 01 : 2F |
Ulnt |
Network port address setting |
|
697-699 |
6B : 01 : 30 - 6B : 01 : 32 |
(Not significant) |
Command Variables
Command Variables
Command variables are described in the following table:
Register |
DeviceNet Address |
Variable Type |
Read/Write Variables |
|
---|---|---|---|---|
700 |
6C : 01 : 01 |
Word |
Register available to remotely write commands that can be processed in a specific custom logic |
|
701-703 |
6C : 01 : 02 - 6C : 01 : 04 |
(Reserved) |
||
704 |
6C : 01 : 05 |
Word |
Control register 1 |
|
bit 0 Motor run forward command* |
||||
bit 1 Motor run reverse command* |
||||
bit 2 (Reserved) |
||||
bit 3 Trip reset command |
||||
bit 4 (Reserved) |
||||
bit 5 Self test command |
||||
bit 6 Motor low speed command |
||||
bits 7-15 (Reserved) |
||||
705 |
6C : 01 : 06 |
Word |
Control register 2 |
|
bit 0 Clear all command Clear all parameters, except:
|
||||
bit 1 Clear statistics command |
||||
bit 2 Clear thermal capacity level command |
||||
bit 3 Clear controller settings command |
||||
bit 4 Clear network port settings command |
||||
bits 5-15 (Reserved) |
||||
706-709 |
6C : 01 : 07 - 6C : 01 : 0A |
(Reserved) |
||
710-799 |
6C : 01 : 08 - 6C : 01 : 64 |
(Forbidden) |
Custom Logic Variables
Custom Logic Variables
Custom logic variables are described in the following tables:
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
1200 |
71 : 01 : 01 |
Word |
Custom logic status register |
|
bit 0 Custom logic run |
||||
bit 1 Custom logic stop |
||||
bit 2 Custom logic reset |
||||
bit 3 Custom logic second step |
||||
bit 4 Custom logic transition |
||||
bit 5 Custom logic phase reverse |
||||
bit 6 Custom logic network control |
||||
bit 7 Custom logic FLC selection |
||||
bit 8 (Reserved) |
||||
bit 9 Custom logic auxiliary 1 LED |
||||
bit 10 Custom logic auxiliary 2 LED |
||||
bit 11 Custom logic stop LED |
||||
bit 12 Custom logic LO1 |
||||
bit 13 Custom logic LO2 |
||||
bit 14 Custom logic LO3 |
||||
bit 15 Custom logic LO4 |
||||
1201 |
71 : 01 : 02 |
Word |
Custom logic version |
|
1202 |
71 : 01 : 03 |
Word |
Custom logic memory space |
|
1203 |
71 : 01 : 04 |
Word |
Custom logic memory used |
|
1204 |
71 : 01 : 05 |
Word |
Custom logic temporary space |
|
1205 |
71 : 01 : 06 |
Word |
Custom logic non volatile space |
|
1206-1249 |
71 : 01 : 0C - 71 : 01 : 32 |
(Reserved) |
Register |
DeviceNet Address |
Variable Type |
Read/Write Variables |
|
---|---|---|---|---|
1250 |
71 : 01 : 33 |
Word |
Custom logic setting register 1 |
|
bit 0 (Reserved) |
||||
bit 1 Logic input 3 external ready enable |
||||
bits 2-15 (Reserved) |
||||
1251-1269 |
71 : 01 : 34 - 71 : 01 : 46 |
|
(Reserved) |
|
1270 |
71 : 01 : 47 |
Word |
Custom logic command register 1 |
|
bit 0 Custom logic external trip command |
||||
bits 1-15 (Reserved) |
||||
1271-1279 |
71 : 01 : 48 - 71 : 01 : 50 |
|
(Reserved) |
Register |
DeviceNet Address |
Variable Type |
Read-only Variables |
|
---|---|---|---|---|
1280 |
71 : 01 : 51 |
Word |
Custom logic monitoring register 1 |
|
bit 0 (Reserved) |
||||
bit 1 Custom logic system ready |
||||
bits 2-15 (Reserved) |
||||
1281-1300 |
71 : 01 : 52 - 71 : 01 : 65 |
(Reserved) |
Register |
DeviceNet Address |
Variable Type |
Read/Write Variables |
|
---|---|---|---|---|
1301-1399 |
71 : 01 : 66 - 71 : 01 : C8 |
Word[99] |
General purpose registers for logic functions |