990-914301A-001

Specifications for ESS Energy Storage System at 480 V (VAC, 3-phase, 50/60Hz)

Arc flash related calculation of the battery system is estimated with the Direct-Current Incident Energy Calculations referenced in Informative Annex D of NFPA 70E Standard for Electrical Safety in the Workplace. The ESS system is assumed to estimate the worst-case scenario of 17 LIBSESMG17UL battery cabinets in parallel. Estimated arc flash: < 0.97 cal/cm2.

ESS Model Name

Max. input current (A) Max. output current (A) Max. energy output (kWh) Max. power input (kVA) Max. power output(kVA)

Ambient temperature range (°C)

Max. short-circuit current (kA)

GVX500K500NGS- 3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX500K500NGS- 4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX500K500NGS- 5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX500K500NGS- 6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX500K500NGS- 7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX500K500NGS- 8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX500K500NGS- 9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX500K500NGS- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX500K500NGS- 11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX500K500NGS- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX500K500NGS- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX500K500NGS- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX500K500NGS- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX500K500NGS- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX500K500NGS- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX500K500NGS- JC4-3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX500K500NGS- JC4-4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX500K500NGS- JC4-5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX500K500NGS- JC4-6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX500K500NGS- JC4-7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX500K500NGS- JC4-8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX500K500NGS- JC4-9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX500K500NGS- JC4- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX500K500NGS- JC4-11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX500K500NGS- JC4- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX500K500NGS- JC4- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX500K500NGS- JC4- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX500K500NGS- JC4- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX500K500NGS- JC4- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX500K500NGS- JC4- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX500K750NGS- 3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX500K750NGS- 4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX500K750NGS- 5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX500K750NGS- 6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX500K750NGS- 7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX500K750NGS- 8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX500K750NGS- 9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX500K750NGS- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX500K750NGS- 11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX500K750NGS- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX500K750NGS- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX500K750NGS- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX500K750NGS- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX500K750NGS- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX500K750NGS- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX500K750NGS- JC4-3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX500K750NGS- JC4-4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX500K750NGS- JC4-5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX500K750NGS- JC4-6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX500K750NGS- JC4-7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX500K750NGS- JC4-8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX500K750NGS- JC4-9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX500K750NGS- JC4- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX500K750NGS- JC4-11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX500K750NGS- JC4- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX500K750NGS- JC4- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX500K750NGS- JC4- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX500K750NGS- JC4- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX500K750NGS- JC4- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX500K750NGS- JC4- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX500K1000NGS- 3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX500K1000NGS- 4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX500K1000NGS- 5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX500K1000NGS- 6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX500K1000NGS- 7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX500K1000NGS- 8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX500K1000NGS- 9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX500K1000NGS- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX500K1000NGS- 11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX500K1000NGS- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX500K1000NGS- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX500K1000NGS- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX500K1000NGS- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX500K1000NGS- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX500K1000NGS- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX500K1000NGS- JC4-3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX500K1000NGS- JC4-4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX500K1000NGS- JC4-5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX500K1000NGS- JC4-6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX500K1000NGS- JC4-7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX500K1000NGS- JC4-8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX500K1000NGS- JC4-9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX500K1000NGS- JC4- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX500K1000NGS- JC4-11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX500K1000NGS- JC4- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX500K1000NGS- JC4- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX500K1000NGS- JC4- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX500K1000NGS- JC4- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX500K1000NGS- JC4- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX500K1000NGS- JC4- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX500K1250GS- 3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX500K1250GS- 4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX500K1250GS- 5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX500K1250GS- 6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX500K1250GS- 7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX500K1250GS- 8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX500K1250GS- 9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX500K1250GS- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX500K1250GS- 11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX500K1250GS- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX500K1250GS- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX500K1250GS- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX500K1250GS- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX500K1250GS- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX500K1250GS- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX500K1250GS-JC4- 3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX500K1250GS-JC4- 4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX500K1250GS-JC4- 5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX500K1250GS-JC4- 6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX500K1250GS-JC4- 7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX500K1250GS-JC4- 8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX500K1250GS-JC4- 9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX500K1250GS-JC4- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX500K1250GS-JC4- 11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX500K1250GS-JC4- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX500K1250GS-JC4- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX500K1250GS-JC4- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX500K1250GS-JC4- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX500K1250GS-JC4- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX500K1250GS-JC4- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX500K1250NGS- 3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX500K1250NGS- 4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX500K1250NGS- 5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX500K1250NGS- 6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX500K1250NGS- 7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX500K1250NGS- 8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX500K1250NGS- 9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX500K1250NGS- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX500K1250NGS- 11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX500K1250NGS- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX500K1250NGS- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX500K1250NGS- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX500K1250NGS- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX500K1250NGS- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX500K1250NGS- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX500K1250NGS- JC4-3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX500K1250NGS- JC4-4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX500K1250NGS- JC4-5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX500K1250NGS- JC4-6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX500K1250NGS- JC4-7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX500K1250NGS- JC4-8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX500K1250NGS- JC4-9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX500K1250NGS- JC4- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX500K1250NGS- JC4-11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX500K1250NGS- JC4- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX500K1250NGS- JC4- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX500K1250NGS- JC4- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX500K1250NGS- JC4- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX500K1250NGS- JC4- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX500K1250NGS- JC4- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX625K625NGS- 3LIBSESMG17UL

946

752

103.8

943

552

23±5

100

GVX625K625NGS- 4LIBSESMG17UL

946

752

138.4

943

625

23±5

100

GVX625K625NGS- 5LIBSESMG17UL

946

752

173

943

625

23±5

100

GVX625K625NGS- 6LIBSESMG17UL

946

752

207.6

943

625

23±5

100

GVX625K625NGS- 7LIBSESMG17UL

946

752

242.2

943

625

23±5

100

GVX625K625NGS- 8LIBSESMG17UL

946

752

276.8

943

625

23±5

100

GVX625K625NGS- 9LIBSESMG17UL

946

752

311.4

943

625

23±5

100

GVX625K625NGS- 10LIBSESMG17UL

946

752

346

943

625

23±5

100

GVX625K625NGS- 11LIBSESMG17UL

946

752

380.6

943

625

23±5

100

GVX625K625NGS- 12LIBSESMG17UL

946

752

415.2

943

625

23±5

100

GVX625K625NGS- 13LIBSESMG17UL

946

752

449.8

943

625

23±5

100

GVX625K625NGS- 14LIBSESMG17UL

946

752

484.4

943

625

23±5

100

GVX625K625NGS- 15LIBSESMG17UL

946

752

519

943

625

23±5

100

GVX625K625NGS- 16LIBSESMG17UL

946

752

553.6

943

625

23±5

100

GVX625K625NGS- 17LIBSESMG17UL

946

752

588.2

943

625

23±5

100

GVX625K625NGS- JC4-3LIBSESMG17UL

946

752

103.8

943

552

23±5

100

GVX625K625NGS- JC4-4LIBSESMG17UL

946

752

138.4

943

625

23±5

100

GVX625K625NGS- JC4-5LIBSESMG17UL

946

752

173

943

625

23±5

100

GVX625K625NGS- JC4-6LIBSESMG17UL

946

752

207.6

943

625

23±5

100

GVX625K625NGS- JC4-7LIBSESMG17UL

946

752

242.2

943

625

23±5

100

GVX625K625NGS- JC4-8LIBSESMG17UL

946

752

276.8

943

625

23±5

100

GVX625K625NGS- JC4-9LIBSESMG17UL

946

752

311.4

943

625

23±5

100

GVX625K625NGS- JC4- 10LIBSESMG17UL

946

752

346

943

625

23±5

100

GVX625K625NGS- JC4-11LIBSESMG17UL

946

752

380.6

943

625

23±5

100

GVX625K625NGS- JC4- 12LIBSESMG17UL

946

752

415.2

943

625

23±5

100

GVX625K625NGS- JC4- 13LIBSESMG17UL

946

752

449.8

943

625

23±5

100

GVX625K625NGS- JC4- 14LIBSESMG17UL

946

752

484.4

943

625

23±5

100

GVX625K625NGS- JC4- 15LIBSESMG17UL

946

752

519

943

625

23±5

100

GVX625K625NGS- JC4- 16LIBSESMG17UL

946

752

553.6

943

625

23±5

100

GVX625K625NGS- JC4- 17LIBSESMG17UL

946

752

588.2

943

625

23±5

100

GVX625K1000NGS- 3LIBSESMG17UL

946

752

103.8

943

552

23±5

100

GVX625K1000NGS- 4LIBSESMG17UL

946

752

138.4

943

625

23±5

100

GVX625K1000NGS- 5LIBSESMG17UL

946

752

173

943

625

23±5

100

GVX625K1000NGS- 6LIBSESMG17UL

946

752

207.6

943

625

23±5

100

GVX625K1000NGS- 7LIBSESMG17UL

946

752

242.2

943

625

23±5

100

GVX625K1000NGS- 8LIBSESMG17UL

946

752

276.8

943

625

23±5

100

GVX625K1000NGS- 9LIBSESMG17UL

946

752

311.4

943

625

23±5

100

GVX625K1000NGS- 10LIBSESMG17UL

946

752

346

943

625

23±5

100

GVX625K1000NGS- 11LIBSESMG17UL

946

752

380.6

943

625

23±5

100

GVX625K1000NGS- 12LIBSESMG17UL

946

752

415.2

943

625

23±5

100

GVX625K1000NGS- 13LIBSESMG17UL

946

752

449.8

943

625

23±5

100

GVX625K1000NGS- 14LIBSESMG17UL

946

752

484.4

943

625

23±5

100

GVX625K1000NGS- 15LIBSESMG17UL

946

752

519

943

625

23±5

100

GVX625K1000NGS- 16LIBSESMG17UL

946

752

553.6

943

625

23±5

100

GVX625K1000NGS- 17LIBSESMG17UL

946

752

588.2

943

625

23±5

100

GVX625K1000NGS- JC4-3LIBSESMG17UL

946

752

103.8

943

552

23±5

100

GVX625K1000NGS- JC4-4LIBSESMG17UL

946

752

138.4

943

625

23±5

100

GVX625K1000NGS- JC4-5LIBSESMG17UL

946

752

173

943

625

23±5

100

GVX625K1000NGS- JC4-6LIBSESMG17UL

946

752

207.6

943

625

23±5

100

GVX625K1000NGS- JC4-7LIBSESMG17UL

946

752

242.2

943

625

23±5

100

GVX625K1000NGS- JC4-8LIBSESMG17UL

946

752

276.8

943

625

23±5

100

GVX625K1000NGS- JC4-9LIBSESMG17UL

946

752

311.4

943

625

23±5

100

GVX625K1000NGS- JC4- 10LIBSESMG17UL

946

752

346

943

625

23±5

100

GVX625K1000NGS- JC4-11LIBSESMG17UL

946

752

380.6

943

625

23±5

100

GVX625K1000NGS- JC4- 12LIBSESMG17UL

946

752

415.2

943

625

23±5

100

GVX625K1000NGS- JC4- 13LIBSESMG17UL

946

752

449.8

943

625

23±5

100

GVX625K1000NGS- JC4- 14LIBSESMG17UL

946

752

484.4

943

625

23±5

100

GVX625K1000NGS- JC4- 15LIBSESMG17UL

946

752

519

943

625

23±5

100

GVX625K1000NGS- JC4- 16LIBSESMG17UL

946

752

553.6

943

625

23±5

100

GVX625K1000NGS- JC4- 17LIBSESMG17UL

946

752

588.2

943

625

23±5

100

GVX750K500NGS- 3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX750K500NGS- 4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX750K500NGS- 5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX750K500NGS- 6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX750K500NGS- 7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX750K500NGS- 8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX750K500NGS- 9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX750K500NGS- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX750K500NGS- 11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX750K500NGS- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX750K500NGS- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX750K500NGS- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX750K500NGS- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX750K500NGS- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX750K500NGS- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX750K500NGS- JC4-3LIBSESMG17UL

757

601

103.8

755

500

23±5

100

GVX750K500NGS- JC4-4LIBSESMG17UL

757

601

138.4

755

500

23±5

100

GVX750K500NGS- JC4-5LIBSESMG17UL

757

601

173

755

500

23±5

100

GVX750K500NGS- JC4-6LIBSESMG17UL

757

601

207.6

755

500

23±5

100

GVX750K500NGS- JC4-7LIBSESMG17UL

757

601

242.2

755

500

23±5

100

GVX750K500NGS- JC4-8LIBSESMG17UL

757

601

276.8

755

500

23±5

100

GVX750K500NGS- JC4-9LIBSESMG17UL

757

601

311.4

755

500

23±5

100

GVX750K500NGS- JC4- 10LIBSESMG17UL

757

601

346

755

500

23±5

100

GVX750K500NGS- JC4-11LIBSESMG17UL

757

601

380.6

755

500

23±5

100

GVX750K500NGS- JC4- 12LIBSESMG17UL

757

601

415.2

755

500

23±5

100

GVX750K500NGS- JC4- 13LIBSESMG17UL

757

601

449.8

755

500

23±5

100

GVX750K500NGS- JC4- 14LIBSESMG17UL

757

601

484.4

755

500

23±5

100

GVX750K500NGS- JC4- 15LIBSESMG17UL

757

601

519

755

500

23±5

100

GVX750K500NGS- JC4- 16LIBSESMG17UL

757

601

553.6

755

500

23±5

100

GVX750K500NGS- JC4- 17LIBSESMG17UL

757

601

588.2

755

500

23±5

100

GVX750K750NGS- 4LIBSESMG17UL

1136

902

138.4

1133

736

23±5

100

GVX750K750NGS- 5LIBSESMG17UL

1136

902

173

1133

750

23±5

100

GVX750K750NGS- 6LIBSESMG17UL

1136

902

207.6

1133

750

23±5

100

GVX750K750NGS- 7LIBSESMG17UL

1136

902

242.2

1133

750

23±5

100

GVX750K750NGS- 8LIBSESMG17UL

1136

902

276.8

1133

750

23±5

100

GVX750K750NGS- 9LIBSESMG17UL

1136

902

311.4

1133

750

23±5

100

GVX750K750NGS- 10LIBSESMG17UL

1136

902

346

1133

750

23±5

100

GVX750K750NGS- 11LIBSESMG17UL

1136

902

380.6

1133

750

23±5

100

GVX750K750NGS- 12LIBSESMG17UL

1136

902

415.2

1133

750

23±5

100

GVX750K750NGS- 13LIBSESMG17UL

1136

902

449.8

1133

750

23±5

100

GVX750K750NGS- 14LIBSESMG17UL

1136

902

484.4

1133

750

23±5

100

GVX750K750NGS- 15LIBSESMG17UL

1136

902

519

1133

750

23±5

100

GVX750K750NGS- 16LIBSESMG17UL

1136

902

553.6

1133

750

23±5

100

GVX750K750NGS- 17LIBSESMG17UL

1136

902

588.2

1133

750

23±5

100

GVX750K750NGS- JC4-4LIBSESMG17UL

1136

902

138.4

1133

736

23±5

100

GVX750K750NGS- JC4-5LIBSESMG17UL

1136

902

173

1133

750

23±5

100

GVX750K750NGS- JC4-6LIBSESMG17UL

1136

902

207.6

1133

750

23±5

100

GVX750K750NGS- JC4-7LIBSESMG17UL

1136

902

242.2

1133

750

23±5

100

GVX750K750NGS- JC4-8LIBSESMG17UL

1136

902

276.8

1133

750

23±5

100

GVX750K750NGS- JC4-9LIBSESMG17UL

1136

902

311.4

1133

750

23±5

100

GVX750K750NGS- JC4- 10LIBSESMG17UL

1136

902

346

1133

750

23±5

100

GVX750K750NGS- JC4-11LIBSESMG17UL

1136

902

380.6

1133

750

23±5

100

GVX750K750NGS- JC4- 12LIBSESMG17UL

1136

902

415.2

1133

750

23±5

100

GVX750K750NGS- JC4- 13LIBSESMG17UL

1136

902

449.8

1133

750

23±5

100

GVX750K750NGS- JC4- 14LIBSESMG17UL

1136

902

484.4

1133

750

23±5

100

GVX750K750NGS- JC4- 15LIBSESMG17UL

1136

902

519

1133

750

23±5

100

GVX750K750NGS- JC4- 16LIBSESMG17UL

1136

902

553.6

1133

750

23±5

100

GVX750K750NGS- JC4- 17LIBSESMG17UL

1136

902

588.2

1133

750

23±5

100

GVX750K1000NGS- 4LIBSESMG17UL

1136

902

138.4

1133

736

23±5

100

GVX750K1000NGS- 5LIBSESMG17UL

1136

902

173

1133

750

23±5

100

GVX750K1000NGS- 6LIBSESMG17UL

1136

902

207.6

1133

750

23±5

100

GVX750K1000NGS- 7LIBSESMG17UL

1136

902

242.2

1133

750

23±5

100

GVX750K1000NGS- 8LIBSESMG17UL

1136

902

276.8

1133

750

23±5

100

GVX750K1000NGS- 9LIBSESMG17UL

1136

902

311.4

1133

750

23±5

100

GVX750K1000NGS- 10LIBSESMG17UL

1136

902

346

1133

750

23±5

100

GVX750K1000NGS- 11LIBSESMG17UL

1136

902

380.6

1133

750

23±5

100

GVX750K1000NGS- 12LIBSESMG17UL

1136

902

415.2

1133

750

23±5

100

GVX750K1000NGS- 13LIBSESMG17UL

1136

902

449.8

1133

750

23±5

100

GVX750K1000NGS- 14LIBSESMG17UL

1136

902

484.4

1133

750

23±5

100

GVX750K1000NGS- 15LIBSESMG17UL

1136

902

519

1133

750

23±5

100

GVX750K1000NGS- 16LIBSESMG17UL

1136

902

553.6

1133

750

23±5

100

GVX750K1000NGS- 17LIBSESMG17UL

1136

902

588.2

1133

750

23±5

100

GVX750K1000NGS- JC4-4LIBSESMG17UL

1136

902

138.4

1133

736

23±5

100

GVX750K1000NGS- JC4-5LIBSESMG17UL

1136

902

173

1133

750

23±5

100

GVX750K1000NGS- JC4-6LIBSESMG17UL

1136

902

207.6

1133

750

23±5

100

GVX750K1000NGS- JC4-7LIBSESMG17UL

1136

902

242.2

1133

750

23±5

100

GVX750K1000NGS- JC4-8LIBSESMG17UL

1136

902

276.8

1133

750

23±5

100

GVX750K1000NGS- JC4-9LIBSESMG17UL

1136

902

311.4

1133

750

23±5

100

GVX750K1000NGS- JC4- 10LIBSESMG17UL

1136

902

346

1133

750

23±5

100

GVX750K1000NGS- JC4-11LIBSESMG17UL

1136

902

380.6

1133

750

23±5

100

GVX750K1000NGS- JC4- 12LIBSESMG17UL

1136

902

415.2

1133

750

23±5

100

GVX750K1000NGS- JC4- 13LIBSESMG17UL

1136

902

449.8

1133

750

23±5

100

GVX750K1000NGS- JC4- 14LIBSESMG17UL

1136

902

484.4

1133

750

23±5

100

GVX750K1000NGS- JC4- 15LIBSESMG17UL

1136

902

519

1133

750

23±5

100

GVX750K1000NGS- JC4- 16LIBSESMG17UL

1136

902

553.6

1133

750

23±5

100

GVX750K1000NGS- JC4- 17LIBSESMG17UL

1136

902

588.2

1133

750

23±5

100

GVX750K1250GS- 4LIBSESMG17UL

1136

902

138.4

1133

736

23±5

100

GVX750K1250GS- 5LIBSESMG17UL

1136

902

173

1133

750

23±5

100

GVX750K1250GS- 6LIBSESMG17UL

1136

902

207.6

1133

750

23±5

100

GVX750K1250GS- 7LIBSESMG17UL

1136

902

242.2

1133

750

23±5

100

GVX750K1250GS- 8LIBSESMG17UL

1136

902

276.8

1133

750

23±5

100

GVX750K1250GS- 9LIBSESMG17UL

1136

902

311.4

1133

750

23±5

100

GVX750K1250GS- 10LIBSESMG17UL

1136

902

346

1133

750

23±5

100

GVX750K1250GS- 11LIBSESMG17UL

1136

902

380.6

1133

750

23±5

100

GVX750K1250GS- 12LIBSESMG17UL

1136

902

415.2

1133

750

23±5

100

GVX750K1250GS- 13LIBSESMG17UL

1136

902

449.8

1133

750

23±5

100

GVX750K1250GS- 14LIBSESMG17UL

1136

902

484.4

1133

750

23±5

100

GVX750K1250GS- 15LIBSESMG17UL

1136

902

519

1133

750

23±5

100

GVX750K1250GS- 16LIBSESMG17UL

1136

902

553.6

1133

750

23±5

100

GVX750K1250GS- 17LIBSESMG17UL

1136

902

588.2

1133

750

23±5

100

GVX750K1250GS-JC4- 4LIBSESMG17UL

1136

902

138.4

1133

736

23±5

100

GVX750K1250GS-JC4- 5LIBSESMG17UL

1136

902

173

1133

750

23±5

100

GVX750K1250GS-JC4- 6LIBSESMG17UL

1136

902

207.6

1133

750

23±5

100

GVX750K1250GS-JC4- 7LIBSESMG17UL

1136

902

242.2

1133

750

23±5

100

GVX750K1250GS-JC4- 8LIBSESMG17UL

1136

902

276.8

1133

750

23±5

100

GVX750K1250GS-JC4- 9LIBSESMG17UL

1136

902

311.4

1133

750

23±5

100

GVX750K1250GS-JC4- 10LIBSESMG17UL

1136

902

346

1133

750

23±5

100

GVX750K1250GS-JC4- 11LIBSESMG17UL

1136

902

380.6

1133

750

23±5

100

GVX750K1250GS-JC4- 12LIBSESMG17UL

1136

902

415.2

1133

750

23±5

100

GVX750K1250GS-JC4- 13LIBSESMG17UL

1136

902

449.8

1133

750

23±5

100

GVX750K1250GS-JC4- 14LIBSESMG17UL

1136

902

484.4

1133

750

23±5

100

GVX750K1250GS-JC4- 15LIBSESMG17UL

1136

902

519

1133

750

23±5

100

GVX750K1250GS-JC4- 16LIBSESMG17UL

1136

902

553.6

1133

750

23±5

100

GVX750K1250GS-JC4- 17LIBSESMG17UL

1136

902

588.2

1133

750

23±5

100

GVX750K1250NGS- 4LIBSESMG17UL

1136

902

138.4

1133

736

23±5

100

GVX750K1250NGS- 5LIBSESMG17UL

1136

902

173

1133

750

23±5

100

GVX750K1250NGS- 6LIBSESMG17UL

1136

902

207.6

1133

750

23±5

100

GVX750K1250NGS- 7LIBSESMG17UL

1136

902

242.2

1133

750

23±5

100

GVX750K1250NGS- 8LIBSESMG17UL

1136

902

276.8

1133

750

23±5

100

GVX750K1250NGS- 9LIBSESMG17UL

1136

902

311.4

1133

750

23±5

100

GVX750K1250NGS- 10LIBSESMG17UL

1136

902

346

1133

750

23±5

100

GVX750K1250NGS- 11LIBSESMG17UL

1136

902

380.6

1133

750

23±5

100

GVX750K1250NGS- 12LIBSESMG17UL

1136

902

415.2

1133

750

23±5

100

GVX750K1250NGS- 13LIBSESMG17UL

1136

902

449.8

1133

750

23±5

100

GVX750K1250NGS- 14LIBSESMG17UL

1136

902

484.4

1133

750

23±5

100

GVX750K1250NGS- 15LIBSESMG17UL

1136

902

519

1133

750

23±5

100

GVX750K1250NGS- 16LIBSESMG17UL

1136

902

553.6

1133

750

23±5

100

GVX750K1250NGS- 17LIBSESMG17UL

1136

902

588.2

1133

750

23±5

100

GVX750K1250NGS- JC4-4LIBSESMG17UL

1136

902

138.4

1133

736

23±5

100

GVX750K1250NGS- JC4-5LIBSESMG17UL

1136

902

173

1133

750

23±5

100

GVX750K1250NGS- JC4-6LIBSESMG17UL

1136

902

207.6

1133

750

23±5

100

GVX750K1250NGS- JC4-7LIBSESMG17UL

1136

902

242.2

1133

750

23±5

100

GVX750K1250NGS- JC4-8LIBSESMG17UL

1136

902

276.8

1133

750

23±5

100

GVX750K1250NGS- JC4-9LIBSESMG17UL

1136

902

311.4

1133

750

23±5

100

GVX750K1250NGS- JC4- 10LIBSESMG17UL

1136

902

346

1133

750

23±5

100

GVX750K1250NGS- JC4-11LIBSESMG17UL

1136

902

380.6

1133

750

23±5

100

GVX750K1250NGS- JC4- 12LIBSESMG17UL

1136

902

415.2

1133

750

23±5

100

GVX750K1250NGS- JC4- 13LIBSESMG17UL

1136

902

449.8

1133

750

23±5

100

GVX750K1250NGS- JC4- 14LIBSESMG17UL

1136

902

484.4

1133

750

23±5

100

GVX750K1250NGS- JC4- 15LIBSESMG17UL

1136

902

519

1133

750

23±5

100

GVX750K1250NGS- JC4- 16LIBSESMG17UL

1136

902

553.6

1133

750

23±5

100

GVX750K1250NGS- JC4- 17LIBSESMG17UL

1136

902

588.2

1133

750

23±5

100

GVX800K800NGS- 4LIBSESMG17UL

1212

962

138.4

1209

736

23±5

100

GVX800K800NGS- 5LIBSESMG17UL

1212

962

173

1209

800

23±5

100

GVX800K800NGS- 6LIBSESMG17UL

1212

962

207.6

1209

800

23±5

100

GVX800K800NGS- 7LIBSESMG17UL

1212

962

242.2

1209

800

23±5

100

GVX800K800NGS- 8LIBSESMG17UL

1212

962

276.8

1209

800

23±5

100

GVX800K800NGS- 9LIBSESMG17UL

1212

962

311.4

1209

800

23±5

100

GVX800K800NGS- 10LIBSESMG17UL

1212

962

346

1209

800

23±5

100

GVX800K800NGS- 11LIBSESMG17UL

1212

962

380.6

1209

800

23±5

100

GVX800K800NGS- 12LIBSESMG17UL

1212

962

415.2

1209

800

23±5

100

GVX800K800NGS- 13LIBSESMG17UL

1212

962

449.8

1209

800

23±5

100

GVX800K800NGS- 14LIBSESMG17UL

1212

962

484.4

1209

800

23±5

100

GVX800K800NGS- 15LIBSESMG17UL

1212

962

519

1209

800

23±5

100

GVX800K800NGS- 16LIBSESMG17UL

1212

962

553.6

1209

800

23±5

100

GVX800K800NGS- 17LIBSESMG17UL

1212

962

588.2

1209

800

23±5

100

GVX800K800NGS- JC4-4LIBSESMG17UL

1212

962

138.4

1209

736

23±5

100

GVX800K800NGS- JC4-5LIBSESMG17UL

1212

962

173

1209

800

23±5

100

GVX800K800NGS- JC4-6LIBSESMG17UL

1212

962

207.6

1209

800

23±5

100

GVX800K800NGS- JC4-7LIBSESMG17UL

1212

962

242.2

1209

800

23±5

100

GVX800K800NGS- JC4-8LIBSESMG17UL

1212

962

276.8

1209

800

23±5

100

GVX800K800NGS- JC4-9LIBSESMG17UL

1212

962

311.4

1209

800

23±5

100

GVX800K800NGS- JC4- 10LIBSESMG17UL

1212

962

346

1209

800

23±5

100

GVX800K800NGS- JC4-11LIBSESMG17UL

1212

962

380.6

1209

800

23±5

100

GVX800K800NGS- JC4- 12LIBSESMG17UL

1212

962

415.2

1209

800

23±5

100

GVX800K800NGS- JC4- 13LIBSESMG17UL

1212

962

449.8

1209

800

23±5

100

GVX800K800NGS- JC4- 14LIBSESMG17UL

1212

962

484.4

1209

800

23±5

100

GVX800K800NGS- JC4- 15LIBSESMG17UL

1212

962

519

1209

800

23±5

100

GVX800K800NGS- JC4- 16LIBSESMG17UL

1212

962

553.6

1209

800

23±5

100

GVX800K800NGS- JC4- 17LIBSESMG17UL

1212

962

588.2

1209

800

23±5

100

GVX1000K1000NGS- 5LIBSESMG17UL

1514

1203

173

1510

920

23±5

100

GVX1000K1000NGS- 6LIBSESMG17UL

1514

1203

207.6

1510

1000

23±5

100

GVX1000K1000NGS- 7LIBSESMG17UL

1514

1203

242.2

1510

1000

23±5

100

GVX1000K1000NGS- 8LIBSESMG17UL

1514

1203

276.8

1510

1000

23±5

100

GVX1000K1000NGS- 9LIBSESMG17UL

1514

1203

311.4

1510

1000

23±5

100

GVX1000K1000NGS- 10LIBSESMG17UL

1514

1203

346

1510

1000

23±5

100

GVX1000K1000NGS- 11LIBSESMG17UL

1514

1203

380.6

1510

1000

23±5

100

GVX1000K1000NGS- 12LIBSESMG17UL

1514

1203

415.2

1510

1000

23±5

100

GVX1000K1000NGS- 13LIBSESMG17UL

1514

1203

449.8

1510

1000

23±5

100

GVX1000K1000NGS- 14LIBSESMG17UL

1514

1203

484.4

1510

1000

23±5

100

GVX1000K1000NGS- 15LIBSESMG17UL

1514

1203

519

1510

1000

23±5

100

GVX1000K1000NGS- 16LIBSESMG17UL

1514

1203

553.6

1510

1000

23±5

100

GVX1000K1000NGS- 17LIBSESMG17UL

1514

1203

588.2

1510

1000

23±5

100

GVX1000K1250GS- 5LIBSESMG17UL

1514

1203

173

1510

920

23±5

100

GVX1000K1250GS- 6LIBSESMG17UL

1514

1203

207.6

1510

1000

23±5

100

GVX1000K1250GS- 7LIBSESMG17UL

1514

1203

242.2

1510

1000

23±5

100

GVX1000K1250GS- 8LIBSESMG17UL

1514

1203

276.8

1510

1000

23±5

100

GVX1000K1250GS- 9LIBSESMG17UL

1514

1203

311.4

1510

1000

23±5

100

GVX1000K1250GS- 10LIBSESMG17UL

1514

1203

346

1510

1000

23±5

100

GVX1000K1250GS- 11LIBSESMG17UL

1514

1203

380.6

1510

1000

23±5

100

GVX1000K1250GS- 12LIBSESMG17UL

1514

1203

415.2

1510

1000

23±5

100

GVX1000K1250GS- 13LIBSESMG17UL

1514

1203

449.8

1510

1000

23±5

100

GVX1000K1250GS- 14LIBSESMG17UL

1514

1203

484.4

1510

1000

23±5

100

GVX1000K1250GS- 15LIBSESMG17UL

1514

1203

519

1510

1000

23±5

100

GVX1000K1250GS- 16LIBSESMG17UL

1514

1203

553.6

1510

1000

23±5

100

GVX1000K1250GS- 17LIBSESMG17UL

1514

1203

588.2

1510

1000

23±5

100

GVX1000K1250GS- JC4-5LIBSESMG17UL

1514

1203

173

1510

920

23±5

100

GVX1000K1250GS- JC4-6LIBSESMG17UL

1514

1203

207.6

1510

1000

23±5

100

GVX1000K1250GS- JC4-7LIBSESMG17UL

1514

1203

242.2

1510

1000

23±5

100

GVX1000K1250GS- JC4-8LIBSESMG17UL

1514

1203

276.8

1510

1000

23±5

100

GVX1000K1250GS- JC4-9LIBSESMG17UL

1514

1203

311.4

1510

1000

23±5

100

GVX1000K1250GS- JC4- 10LIBSESMG17UL

1514

1203

346

1510

1000

23±5

100

GVX1000K1250GS- JC4-11LIBSESMG17UL

1514

1203

380.6

1510

1000

23±5

100

GVX1000K1250GS- JC4- 12LIBSESMG17UL

1514

1203

415.2

1510

1000

23±5

100

GVX1000K1250GS- JC4- 13LIBSESMG17UL

1514

1203

449.8

1510

1000

23±5

100

GVX1000K1250GS- JC4- 14LIBSESMG17UL

1514

1203

484.4

1510

1000

23±5

100

GVX1000K1250GS- JC4- 15LIBSESMG17UL

1514

1203

519

1510

1000

23±5

100

GVX1000K1250GS- JC4- 16LIBSESMG17UL

1514

1203

553.6

1510

1000

23±5

100

GVX1000K1250GS- JC4- 17LIBSESMG17UL

1514

1203

588.2

1510

1000

23±5

100

GVX1000K1250NGS- 5LIBSESMG17UL

1514

1203

173

1510

920

23±5

100

GVX1000K1250NGS- 6LIBSESMG17UL

1514

1203

207.6

1510

1000

23±5

100

GVX1000K1250NGS- 7LIBSESMG17UL

1514

1203

242.2

1510

1000

23±5

100

GVX1000K1250NGS- 8LIBSESMG17UL

1514

1203

276.8

1510

1000

23±5

100

GVX1000K1250NGS- 9LIBSESMG17UL

1514

1203

311.4

1510

1000

23±5

100

GVX1000K1250NGS- 10LIBSESMG17UL

1514

1203

346

1510

1000

23±5

100

GVX1000K1250NGS- 11LIBSESMG17UL

1514

1203

380.6

1510

1000

23±5

100

GVX1000K1250NGS- 12LIBSESMG17UL

1514

1203

415.2

1510

1000

23±5

100

GVX1000K1250NGS- 13LIBSESMG17UL

1514

1203

449.8

1510

1000

23±5

100

GVX1000K1250NGS- 14LIBSESMG17UL

1514

1203

484.4

1510

1000

23±5

100

GVX1000K1250NGS- 15LIBSESMG17UL

1514

1203

519

1510

1000

23±5

100

GVX1000K1250NGS- 16LIBSESMG17UL

1514

1203

553.6

1510

1000

23±5

100

GVX1000K1250NGS- 17LIBSESMG17UL

1514

1203

588.2

1510

1000

23±5

100

GVX1000K1250NGS- JC4-5LIBSESMG17UL

1514

1203

173

1510

920

23±5

100

GVX1000K1250NGS- JC4-6LIBSESMG17UL

1514

1203

207.6

1510

1000

23±5

100

GVX1000K1250NGS- JC4-7LIBSESMG17UL

1514

1203

242.2

1510

1000

23±5

100

GVX1000K1250NGS- JC4-8LIBSESMG17UL

1514

1203

276.8

1510

1000

23±5

100

GVX1000K1250NGS- JC4-9LIBSESMG17UL

1514

1203

311.4

1510

1000

23±5

100

GVX1000K1250NGS- JC4- 10LIBSESMG17UL

1514

1203

346

1510

1000

23±5

100

GVX1000K1250NGS- JC4-11LIBSESMG17UL

1514

1203

380.6

1510

1000

23±5

100

GVX1000K1250NGS- JC4- 12LIBSESMG17UL

1514

1203

415.2

1510

1000

23±5

100

GVX1000K1250NGS- JC4- 13LIBSESMG17UL

1514

1203

449.8

1510

1000

23±5

100

GVX1000K1250NGS- JC4- 14LIBSESMG17UL

1514

1203

484.4

1510

1000

23±5

100

GVX1000K1250NGS- JC4- 15LIBSESMG17UL

1514

1203

519

1510

1000

23±5

100

GVX1000K1250NGS- JC4- 16LIBSESMG17UL

1514

1203

553.6

1510

1000

23±5

100

GVX1000K1250NGS- JC4- 17LIBSESMG17UL

1514

1203

588.2

1510

1000

23±5

100

GVX1000K750NGS- 4LIBSESMG17UL

1136

902

138.4

1133

736

23±5

100

GVX1000K750NGS- 5LIBSESMG17UL

1136

902

173

1133

750

23±5

100

GVX1000K750NGS- 6LIBSESMG17UL

1136

902

207.6

1133

750

23±5

100

GVX1000K750NGS- 7LIBSESMG17UL

1136

902

242.2

1133

750

23±5

100

GVX1000K750NGS- 8LIBSESMG17UL

1136

902

276.8

1133

750

23±5

100

GVX1000K750NGS- 9LIBSESMG17UL

1136

902

311.4

1133

750

23±5

100

GVX1000K750NGS- 10LIBSESMG17UL

1136

902

346

1133

750

23±5

100

GVX1000K750NGS- 11LIBSESMG17UL

1136

902

380.6

1133

750

23±5

100

GVX1000K750NGS- 12LIBSESMG17UL

1136

902

415.2

1133

750

23±5

100

GVX1000K750NGS- 13LIBSESMG17UL

1136

902

449.8

1133

750

23±5

100

GVX1000K750NGS- 14LIBSESMG17UL

1136

902

484.4

1133

750

23±5

100

GVX1000K750NGS- 15LIBSESMG17UL

1136

902

519

1133

750

23±5

100

GVX1000K750NGS- 16LIBSESMG17UL

1136

902

553.6

1133

750

23±5

100

GVX1000K750NGS- 17LIBSESMG17UL

1136

902

588.2

1133

750

23±5

100

GVX1000K750NGS- JC4-4LIBSESMG17UL

1136

902

138.4

1133

736

23±5

100

GVX1000K750NGS- JC4-5LIBSESMG17UL

1136

902

173

1133

750

23±5

100

GVX1000K750NGS- JC4-6LIBSESMG17UL

1136

902

207.6

1133

750

23±5

100

GVX1000K750NGS- JC4-7LIBSESMG17UL

1136

902

242.2

1133

750

23±5

100

GVX1000K750NGS- JC4-8LIBSESMG17UL

1136

902

276.8

1133

750

23±5

100

GVX1000K750NGS- JC4-9LIBSESMG17UL

1136

902

311.4

1133

750

23±5

100

GVX1000K750NGS- JC4- 10LIBSESMG17UL

1136

902

346

1133

750

23±5

100

GVX1000K750NGS- JC4-11LIBSESMG17UL

1136

902

380.6

1133

750

23±5

100

GVX1000K750NGS- JC4- 12LIBSESMG17UL

1136

902

415.2

1133

750

23±5

100

GVX1000K750NGS- JC4- 13LIBSESMG17UL

1136

902

449.8

1133

750

23±5

100

GVX1000K750NGS- JC4- 14LIBSESMG17UL

1136

902

484.4

1133

750

23±5

100

GVX1000K750NGS- JC4- 15LIBSESMG17UL

1136

902

519

1133

750

23±5

100

GVX1000K750NGS- JC4- 16LIBSESMG17UL

1136

902

553.6

1133

750

23±5

100

GVX1000K750NGS- JC4- 17LIBSESMG17UL

1136

902

588.2

1133

750

23±5

100

GVX1100K1100NGS- 5LIBSESMG17UL

1666

1323

173

1662

920

23±5

100

GVX1100K1100NGS- 6LIBSESMG17UL

1666

1323

207.6

1662

1100

23±5

100

GVX1100K1100NGS- 7LIBSESMG17UL

1666

1323

242.2

1662

1100

23±5

100

GVX1100K1100NGS- 8LIBSESMG17UL

1666

1323

276.8

1662

1100

23±5

100

GVX1100K1100NGS- 9LIBSESMG17UL

1666

1323

311.4

1662

1100

23±5

100

GVX1100K1100NGS- 10LIBSESMG17UL

1666

1323

346

1662

1100

23±5

100

GVX1100K1100NGS- 11LIBSESMG17UL

1666

1323

380.6

1662

1100

23±5

100

GVX1100K1100NGS- 12LIBSESMG17UL

1666

1323

415.2

1662

1100

23±5

100

GVX1100K1100NGS- 13LIBSESMG17UL

1666

1323

449.8

1662

1100

23±5

100

GVX1100K1100NGS- 14LIBSESMG17UL

1666

1323

484.4

1662

1100

23±5

100

GVX1100K1100NGS- 15LIBSESMG17UL

1666

1323

519

1662

1100

23±5

100

GVX1100K1100NGS- 16LIBSESMG17UL

1666

1323

553.6

1662

1100

23±5

100

GVX1100K1100NGS- 17LIBSESMG17UL

1666

1323

588.2

1662

1100

23±5

100

GVX1100K1100NGS- JC4-5LIBSESMG17UL

1666

1323

173

1662

920

23±5

100

GVX1100K1100NGS- JC4-6LIBSESMG17UL

1666

1323

207.6

1662

1100

23±5

100

GVX1100K1100NGS- JC4-7LIBSESMG17UL

1666

1323

242.2

1662

1100

23±5

100

GVX1100K1100NGS- JC4-8LIBSESMG17UL

1666

1323

276.8

1662

1100

23±5

100

GVX1100K1100NGS- JC4-9LIBSESMG17UL

1666

1323

311.4

1662

1100

23±5

100

GVX1100K1100NGS- JC4- 10LIBSESMG17UL

1666

1323

346

1662

1100

23±5

100

GVX1100K1100NGS- JC4-11LIBSESMG17UL

1666

1323

380.6

1662

1100

23±5

100

GVX1100K1100NGS- JC4- 12LIBSESMG17UL

1666

1323

415.2

1662

1100

23±5

100

GVX1100K1100NGS- JC4- 13LIBSESMG17UL

1666

1323

449.8

1662

1100

23±5

100

GVX1100K1100NGS- JC4- 14LIBSESMG17UL

1666

1323

484.4

1662

1100

23±5

100

GVX1100K1100NGS- JC4- 15LIBSESMG17UL

1666

1323

519

1662

1100

23±5

100

GVX1100K1100NGS- JC4- 16LIBSESMG17UL

1666

1323

553.6

1662

1100

23±5

100

GVX1100K1100NGS- JC4- 17LIBSESMG17UL

1666

1323

588.2

1662

1100

23±5

100

GVX1250K1000NGS- 5LIBSESMG17UL

1514

1203

173

1510

920

23±5

100

GVX1250K1000NGS- 6LIBSESMG17UL

1514

1203

207.6

1510

1000

23±5

100

GVX1250K1000NGS- 7LIBSESMG17UL

1514

1203

242.2

1510

1000

23±5

100

GVX1250K1000NGS- 8LIBSESMG17UL

1514

1203

276.8

1510

1000

23±5

100

GVX1250K1000NGS- 9LIBSESMG17UL

1514

1203

311.4

1510

1000

23±5

100

GVX1250K1000NGS- 10LIBSESMG17UL

1514

1203

346

1510

1000

23±5

100

GVX1250K1000NGS- 11LIBSESMG17UL

1514

1203

380.6

1510

1000

23±5

100

GVX1250K1000NGS- 12LIBSESMG17UL

1514

1203

415.2

1510

1000

23±5

100

GVX1250K1000NGS- 13LIBSESMG17UL

1514

1203

449.8

1510

1000

23±5

100

GVX1250K1000NGS- 14LIBSESMG17UL

1514

1203

484.4

1510

1000

23±5

100

GVX1250K1000NGS- 15LIBSESMG17UL

1514

1203

519

1510

1000

23±5

100

GVX1250K1000NGS- 16LIBSESMG17UL

1514

1203

553.6

1510

1000

23±5

100

GVX1250K1000NGS- 17LIBSESMG17UL

1514

1203

588.2

1510

1000

23±5

100

GVX1250K1000NGS- JC4-5LIBSESMG17UL

1514

1203

173

1510

920

23±5

100

GVX1250K1000NGS- JC4-6LIBSESMG17UL

1514

1203

207.6

1510

1000

23±5

100

GVX1250K1000NGS- JC4-7LIBSESMG17UL

1514

1203

242.2

1510

1000

23±5

100

GVX1250K1000NGS- JC4-8LIBSESMG17UL

1514

1203

276.8

1510

1000

23±5

100

GVX1250K1000NGS- JC4-9LIBSESMG17UL

1514

1203

311.4

1510

1000

23±5

100

GVX1250K1000NGS- JC4- 10LIBSESMG17UL

1514

1203

346

1510

1000

23±5

100

GVX1250K1000NGS- JC4-11LIBSESMG17UL

1514

1203

380.6

1510

1000

23±5

100

GVX1250K1000NGS- JC4- 12LIBSESMG17UL

1514

1203

415.2

1510

1000

23±5

100

GVX1250K1000NGS- JC4- 13LIBSESMG17UL

1514

1203

449.8

1510

1000

23±5

100

GVX1250K1000NGS- JC4- 14LIBSESMG17UL

1514

1203

484.4

1510

1000

23±5

100

GVX1250K1000NGS- JC4- 15LIBSESMG17UL

1514

1203

519

1510

1000

23±5

100

GVX1250K1000NGS- JC4- 16LIBSESMG17UL

1514

1203

553.6

1510

1000

23±5

100

GVX1250K1000NGS- JC4- 17LIBSESMG17UL

1514

1203

588.2

1510

1000

23±5

100

GVX1250K1250GS- 6LIBSESMG17UL

1514

1203

207.6

1888

1104

23±5

100

GVX1250K1250GS- 7LIBSESMG17UL

1514

1203

242.2

1888

1250

23±5

100

GVX1250K1250GS- 8LIBSESMG17UL

1514

1203

276.8

1888

1250

23±5

100

GVX1250K1250GS- 9LIBSESMG17UL

1514

1203

311.4

1888

1250

23±5

100

GVX1250K1250GS- 10LIBSESMG17UL

1514

1203

346

1888

1250

23±5

100

GVX1250K1250GS- 11LIBSESMG17UL

1514

1203

380.6

1888

1250

23±5

100

GVX1250K1250GS- 12LIBSESMG17UL

1514

1203

415.2

1888

1250

23±5

100

GVX1250K1250GS- 13LIBSESMG17UL

1514

1203

449.8

1888

1250

23±5

100

GVX1250K1250GS- 14LIBSESMG17UL

1514

1203

484.4

1888

1250

23±5

100

GVX1250K1250GS- 15LIBSESMG17UL

1514

1203

519

1888

1250

23±5

100

GVX1250K1250GS- 16LIBSESMG17UL

1514

1203

553.6

1888

1250

23±5

100

GVX1250K1250GS- 17LIBSESMG17UL

1514

1203

588.2

1888

1250

23±5

100

GVX1250K1250GS- JC4-6LIBSESMG17UL

1514

1203

207.6

1888

1104

23±5

100

GVX1250K1250GS- JC4-7LIBSESMG17UL

1514

1203

242.2

1888

1250

23±5

100

GVX1250K1250GS- JC4-8LIBSESMG17UL

1514

1203

276.8

1888

1250

23±5

100

GVX1250K1250GS- JC4-9LIBSESMG17UL

1514

1203

311.4

1888

1250

23±5

100

GVX1250K1250GS- JC4- 10LIBSESMG17UL

1514

1203

346

1888

1250

23±5

100

GVX1250K1250GS- JC4-11LIBSESMG17UL

1514

1203

380.6

1888

1250

23±5

100

GVX1250K1250GS- JC4- 12LIBSESMG17UL

1514

1203

415.2

1888

1250

23±5

100

GVX1250K1250GS- JC4- 13LIBSESMG17UL

1514

1203

449.8

1888

1250

23±5

100

GVX1250K1250GS- JC4- 14LIBSESMG17UL

1514

1203

484.4

1888

1250

23±5

100

GVX1250K1250GS- JC4- 15LIBSESMG17UL

1514

1203

519

1888

1250

23±5

100

GVX1250K1250GS- JC4- 16LIBSESMG17UL

1514

1203

553.6

1888

1250

23±5

100

GVX1250K1250GS- JC4- 17LIBSESMG17UL

1514

1203

588.2

1888

1250

23±5

100

GVX1250K1250NGS- 6LIBSESMG17UL

1893

1504

207.6

1888

1104

23±5

100

GVX1250K1250NGS- 7LIBSESMG17UL

1893

1504

242.2

1888

1250

23±5

100

GVX1250K1250NGS- 8LIBSESMG17UL

1893

1504

276.8

1888

1250

23±5

100

GVX1250K1250NGS- 9LIBSESMG17UL

1893

1504

311.4

1888

1250

23±5

100

GVX1250K1250NGS- 10LIBSESMG17UL

1893

1504

346

1888

1250

23±5

100

GVX1250K1250NGS- 11LIBSESMG17UL

1893

1504

380.6

1888

1250

23±5

100

GVX1250K1250NGS- 12LIBSESMG17UL

1893

1504

415.2

1888

1250

23±5

100

GVX1250K1250NGS- 13LIBSESMG17UL

1893

1504

449.8

1888

1250

23±5

100

GVX1250K1250NGS- 14LIBSESMG17UL

1893

1504

484.4

1888

1250

23±5

100

GVX1250K1250NGS- 15LIBSESMG17UL

1893

1504

519

1888

1250

23±5

100

GVX1250K1250NGS- 16LIBSESMG17UL

1893

1504

553.6

1888

1250

23±5

100

GVX1250K1250NGS- 17LIBSESMG17UL

1893

1504

588.2

1888

1250

23±5

100

GVX1250K1250NGS– JC4–6LIBSESMG17UL

1893

1504

207.6

1888

1104

23±5

100

GVX1250K1250NGS– JC4–7LIBSESMG17UL

1893

1504

242.2

1888

1250

23±5

100

GVX1250K1250NGS– JC4–8LIBSESMG17UL

1893

1504

276.8

1888

1250

23±5

100

GVX1250K1250NGS– JC4–9LIBSESMG17UL

1893

1504

311.4

1888

1250

23±5

100

GVX1250K1250NGS– JC4– 10LIBSESMG17UL

1893

1504

346

1888

1250

23±5

100

GVX1250K1250NGS– JC4– 11LIBSESMG17UL

1893

1504

380.6

1888

1250

23±5

100

GVX1250K1250NGS– JC4– 12LIBSESMG17UL

1893

1504

415.2

1888

1250

23±5

100

GVX1250K1250NGS– JC4– 13LIBSESMG17UL

1893

1504

449.8

1888

1250

23±5

100

GVX1250K1250NGS– JC4– 14LIBSESMG17UL

1893

1504

484.4

1888

1250

23±5

100

GVX1250K1250NGS– JC4– 15LIBSESMG17UL

1893

1504

519

1888

1250

23±5

100

GVX1250K1250NGS– JC4– 16LIBSESMG17UL

1893

1504

553.6

1888

1250

23±5

100

GVX1250K1250NGS– JC4– 17LIBSESMG17UL

1893

1504

588.2

1888

1250

23±5

100

GVX1500K1100NGS- 5LIBSESMG17UL

1666

1323

173

1662

920

23±5

100

GVX1500K1100NGS- 6LIBSESMG17UL

1666

1323

207.6

1662

1100

23±5

100

GVX1500K1100NGS- 7LIBSESMG17UL

1666

1323

242.2

1662

1100

23±5

100

GVX1500K1100NGS- 8LIBSESMG17UL

1666

1323

276.8

1662

1100

23±5

100

GVX1500K1100NGS- 9LIBSESMG17UL

1666

1323

311.4

1662

1100

23±5

100

GVX1500K1100NGS- 10LIBSESMG17UL

1666

1323

346

1662

1100

23±5

100

GVX1500K1100NGS- 11LIBSESMG17UL

1666

1323

380.6

1662

1100

23±5

100

GVX1500K1100NGS- 12LIBSESMG17UL

1666

1323

415.2

1662

1100

23±5

100

GVX1500K1100NGS- 13LIBSESMG17UL

1666

1323

449.8

1662

1100

23±5

100

GVX1500K1100NGS- 14LIBSESMG17UL

1666

1323

484.4

1662

1100

23±5

100

GVX1500K1100NGS- 15LIBSESMG17UL

1666

1323

519

1662

1100

23±5

100

GVX1500K1100NGS- 16LIBSESMG17UL

1666

1323

553.6

1662

1100

23±5

100

GVX1500K1100NGS- 17LIBSESMG17UL

1666

1323

588.2

1662

1100

23±5

100

GVX1500K1100NGS- JC4-5LIBSESMG17UL

1666

1323

173

1662

920

23±5

100

GVX1500K1100NGS- JC4-6LIBSESMG17UL

1666

1323

207.6

1662

1100

23±5

100

GVX1500K1100NGS- JC4-7LIBSESMG17UL

1666

1323

242.2

1662

1100

23±5

100

GVX1500K1100NGS- JC4-8LIBSESMG17UL

1666

1323

276.8

1662

1100

23±5

100

GVX1500K1100NGS- JC4-9LIBSESMG17UL

1666

1323

311.4

1662

1100

23±5

100

GVX1500K1100NGS- JC4- 10LIBSESMG17UL

1666

1323

346

1662

1100

23±5

100

GVX1500K1100NGS- JC4-11LIBSESMG17UL

1666

1323

380.6

1662

1100

23±5

100

GVX1500K1100NGS- JC4- 12LIBSESMG17UL

1666

1323

415.2

1662

1100

23±5

100

GVX1500K1100NGS- JC4- 13LIBSESMG17UL

1666

1323

449.8

1662

1100

23±5

100

GVX1500K1100NGS- JC4- 14LIBSESMG17UL

1666

1323

484.4

1662

1100

23±5

100

GVX1500K1100NGS- JC4- 15LIBSESMG17UL

1666

1323

519

1662

1100

23±5

100

GVX1500K1100NGS- JC4- 16LIBSESMG17UL

1666

1323

553.6

1662

1100

23±5

100

GVX1500K1100NGS- JC4- 17LIBSESMG17UL

1666

1323

588.2

1662

1100

23±5

100

GVX1500K1250GS- 6LIBSESMG17UL

1893

1504

207.6

1888

1104

23±5

100

GVX1500K1250GS- 7LIBSESMG17UL

1893

1504

242.2

1888

1250

23±5

100

GVX1500K1250GS- 8LIBSESMG17UL

1893

1504

276.8

1888

1250

23±5

100

GVX1500K1250GS- 9LIBSESMG17UL

1893

1504

311.4

1888

1250

23±5

100

GVX1500K1250GS- 10LIBSESMG17UL

1893

1504

346

1888

1250

23±5

100

GVX1500K1250GS- 11LIBSESMG17UL

1893

1504

380.6

1888

1250

23±5

100

GVX1500K1250GS- 12LIBSESMG17UL

1893

1504

415.2

1888

1250

23±5

100

GVX1500K1250GS- 13LIBSESMG17UL

1893

1504

449.8

1888

1250

23±5

100

GVX1500K1250GS- 14LIBSESMG17UL

1893

1504

484.4

1888

1250

23±5

100

GVX1500K1250GS- 15LIBSESMG17UL

1893

1504

519

1888

1250

23±5

100

GVX1500K1250GS- 16LIBSESMG17UL

1893

1504

553.6

1888

1250

23±5

100

GVX1500K1250GS- 17LIBSESMG17UL

1893

1504

588.2

1888

1250

23±5

100

GVX1500K1250GS- JC4-6LIBSESMG17UL

1893

1504

207.6

1888

1104

23±5

100

GVX1500K1250GS- JC4-7LIBSESMG17UL

1893

1504

242.2

1888

1250

23±5

100

GVX1500K1250GS- JC4-8LIBSESMG17UL

1893

1504

276.8

1888

1250

23±5

100

GVX1500K1250GS- JC4-9LIBSESMG17UL

1893

1504

311.4

1888

1250

23±5

100

GVX1500K1250GS- JC4- 10LIBSESMG17UL

1893

1504

346

1888

1250

23±5

100

GVX1500K1250GS- JC4-11LIBSESMG17UL

1893

1504

380.6

1888

1250

23±5

100

GVX1500K1250GS- JC4- 12LIBSESMG17UL

1893

1504

415.2

1888

1250

23±5

100

GVX1500K1250GS- JC4- 13LIBSESMG17UL

1893

1504

449.8

1888

1250

23±5

100

GVX1500K1250GS- JC4- 14LIBSESMG17UL

1893

1504

484.4

1888

1250

23±5

100

GVX1500K1250GS- JC4- 15LIBSESMG17UL

1893

1504

519

1888

1250

23±5

100

GVX1500K1250GS- JC4- 16LIBSESMG17UL

1893

1504

553.6

1888

1250

23±5

100

GVX1500K1250GS- JC4- 17LIBSESMG17UL

1893

1504

588.2

1888

1250

23±5

100

GVX1500K1250NGS- 6LIBSESMG17UL

1893

1504

207.6

1888

1104

23±5

100

GVX1500K1250NGS- 7LIBSESMG17UL

1893

1504

242.2

1888

1250

23±5

100

GVX1500K1250NGS- 8LIBSESMG17UL

1893

1504

276.8

1888

1250

23±5

100

GVX1500K1250NGS- 9LIBSESMG17UL

1893

1504

311.4

1888

1250

23±5

100

GVX1500K1250NGS- 10LIBSESMG17UL

1893

1504

346

1888

1250

23±5

100

GVX1500K1250NGS- 11LIBSESMG17UL

1893

1504

380.6

1888

1250

23±5

100

GVX1500K1250NGS- 12LIBSESMG17UL

1893

1504

415.2

1888

1250

23±5

100

GVX1500K1250NGS- 13LIBSESMG17UL

1893

1504

449.8

1888

1250

23±5

100

GVX1500K1250NGS- 14LIBSESMG17UL

1893

1504

484.4

1888

1250

23±5

100

GVX1500K1250NGS- 15LIBSESMG17UL

1893

1504

519

1888

1250

23±5

100

GVX1500K1250NGS- 16LIBSESMG17UL

1893

1504

553.6

1888

1250

23±5

100

GVX1500K1250NGS- 17LIBSESMG17UL

1893

1504

588.2

1888

1250

23±5

100

GVX1500K1250NGS- JC4-6LIBSESMG17UL

1893

1504

207.6

1888

1104

23±5

100

GVX1500K1250NGS- JC4-7LIBSESMG17UL

1893

1504

242.2

1888

1250

23±5

100

GVX1500K1250NGS- JC4-8LIBSESMG17UL

1893

1504

276.8

1888

1250

23±5

100

GVX1500K1250NGS- JC4-9LIBSESMG17UL

1893

1504

311.4

1888

1250

23±5

100

GVX1500K1250NGS- JC4- 10LIBSESMG17UL

1893

1504

346

1888

1250

23±5

100

GVX1500K1250NGS- JC4-11LIBSESMG17UL

1893

1504

380.6

1888

1250

23±5

100

GVX1500K1250NGS- JC4- 12LIBSESMG17UL

1893

1504

415.2

1888

1250

23±5

100

GVX1500K1250NGS- JC4- 13LIBSESMG17UL

1893

1504

449.8

1888

1250

23±5

100

GVX1500K1250NGS- JC4- 14LIBSESMG17UL

1893

1504

484.4

1888

1250

23±5

100

GVX1500K1250NGS- JC4- 15LIBSESMG17UL

1893

1504

519

1888

1250

23±5

100

GVX1500K1250NGS- JC4- 16LIBSESMG17UL

1893

1504

553.6

1888

1250

23±5

100

GVX1500K1250NGS- JC4- 17LIBSESMG17UL

1893

1504

588.2

1888

1250

23±5

100

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?