効率
500 kW
通常運転 | ECOモード運転 | eConversion | バッテリー運転 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
電圧(V) | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 |
負荷25% |
97.00% |
96.90% |
96.80% |
99.20% |
99.30% |
99.20% |
98.60% |
98.70% |
98.50% |
96.3% |
96.1% |
96.1% |
負荷50% |
97.40% |
97.40% |
97.40% |
99.40% |
99.50% |
99.50% |
99.10% |
99.20% |
99.20% |
96.8% |
96.7% |
96.6% |
負荷75% |
97.30% |
97.40% |
97.40% |
99.50% |
99.60% |
99.50% |
99.30% |
99.40% |
99.30% |
96.4% |
96.5% |
96.4% |
負荷100% |
97.00% |
97.20% |
97.20% |
99.50% |
99.60% |
99.50% |
99.40% |
99.40% |
99.40% |
96.0% |
96.1% |
96.0% |
600 kW
通常運転 | ECOモード運転 | eConversion | バッテリー運転 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
電圧(V) | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 |
負荷25% |
96.90% |
96.80% |
96.70% |
99.20% |
99.20% |
99.20% |
98.60% |
98.80% |
98.10% |
96.4% |
96.3% |
96.2% |
負荷50% |
97.50% |
97.40% |
97.40% |
99.40% |
99.40% |
99.40% |
99.10% |
99.20% |
99.00% |
96.8% |
96.8% |
96.7% |
負荷75% |
97.40% |
97.30% |
97.40% |
99.40% |
99.50% |
99.50% |
99.30% |
99.30% |
99.20% |
96.5% |
96.6% |
96.5% |
負荷100% |
97.10% |
97.10% |
97.20% |
99.40% |
99.50% |
99.50% |
99.30% |
99.40% |
99.30% |
96.0% |
96.1% |
96.1% |
625 kW
通常運転 | ECOモード運転 | eConversion | バッテリー運転 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
電圧(V) | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 |
負荷25% |
97.00% |
96.90% |
96.80% |
99.20% |
99.30% |
99.30% |
98.70% |
98.90% |
98.40% |
96.5% |
96.3% |
96.3% |
負荷50% |
97.50% |
97.40% |
97.50% |
99.40% |
99.40% |
99.50% |
99.10% |
99.20% |
99.10% |
96.8% |
96.7% |
96.6% |
負荷75% |
97.30% |
97.30% |
97.50% |
99.40% |
99.50% |
99.50% |
99.30% |
99.30% |
99.30% |
96.4% |
96.5% |
96.4% |
負荷100% |
97.00% |
97.10% |
97.20% |
99.40% |
99.50% |
99.50% |
99.30% |
99.30% |
99.30% |
95.9% |
96.0% |
95.9% |
750 kW
通常運転 | ECOモード運転 | eConversion | バッテリー運転 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
電圧(V) | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 |
負荷25% |
97.00% |
96.80% |
96.90% |
99.30% |
99.30% |
99.30% |
98.70% |
98.70% |
98.70% |
96.4% |
96.3% |
96.2% |
負荷50% |
97.50% |
97.40% |
97.40% |
99.40% |
99.40% |
99.40% |
99.10% |
99.10% |
99.00% |
96.8% |
96.7% |
96.6% |
負荷75% |
97.30% |
97.30% |
97.40% |
99.40% |
99.50% |
99.50% |
99.30% |
99.30% |
99.30% |
96.4% |
96.5% |
96.4% |
負荷100% |
96.90% |
97.10% |
97.20% |
99.40% |
99.50% |
99.50% |
99.30% |
99.30% |
99.30% |
95.9% |
96.0% |
96.0% |
875 kW
通常運転 | ECOモード運転 | eConversion | バッテリー運転 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
電圧(V) | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 |
負荷25% |
97.00% |
96.80% |
96.90% |
99.30% |
99.30% |
99.30% |
98.70% |
98.70% |
98.70% |
96.5% |
96.3% |
96.2% |
負荷50% |
97.40% |
97.40% |
97.40% |
99.40% |
99.40% |
99.40% |
99.10% |
99.20% |
99.10% |
96.8% |
96.7% |
96.6% |
負荷75% |
97.30% |
97.40% |
97.40% |
99.40% |
99.50% |
99.50% |
99.30% |
99.30% |
99.30% |
96.4% |
96.5% |
96.4% |
負荷100% |
96.90% |
97.10% |
97.20% |
99.40% |
99.50% |
99.50% |
99.30% |
99.30% |
99.30% |
95.9% |
96.0% |
96.0% |
1000 kW
通常運転 | ECOモード運転 | eConversion | バッテリー運転 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
電圧(V) | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 |
負荷25% |
96.90% |
96.80% |
96.80% |
99.30% |
99.30% |
99.30% |
98.70% |
98.90% |
98.70% |
96.5% |
96.4% |
96.3% |
負荷50% |
97.40% |
97.40% |
97.40% |
99.40% |
99.40% |
99.40% |
99.10% |
99.30% |
99.20% |
96.8% |
96.8% |
96.7% |
負荷75% |
97.20% |
97.30% |
97.40% |
99.40% |
99.50% |
99.40% |
99.30% |
99.30% |
99.30% |
96.5% |
96.5% |
96.5% |
負荷100% |
96.90% |
97.00% |
97.20% |
99.40% |
99.50% |
99.40% |
99.30% |
99.30% |
99.30% |
96.0% |
96.1% |
96.0% |
1125 kW
通常運転 | ECOモード運転 | eConversion | バッテリー運転 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
電圧(V) | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 |
負荷25% |
96.90% |
96.90% |
96.80% |
99.30% |
99.30% |
99.30% |
98.70% |
98.80% |
98.80% |
96.5% |
96.4% |
96.3% |
負荷50% |
97.30% |
97.40% |
97.40% |
99.40% |
99.40% |
99.40% |
99.10% |
99.20% |
99.20% |
96.7% |
96.7% |
96.6% |
負荷75% |
97.20% |
97.30% |
97.30% |
99.40% |
99.40% |
99.40% |
99.30% |
99.30% |
99.30% |
96.4% |
96.5% |
96.4% |
負荷100% |
96.80% |
97.00% |
97.10% |
99.40% |
99.40% |
99.40% |
99.20% |
99.30% |
99.30% |
96.0% |
96.0% |
96.0% |
1250 kW
通常運転 | ECOモード運転 | eConversion | バッテリー運転 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
電圧(V) | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 | 380 | 400 | 415 |
負荷25% |
96.90% |
96.90% |
96.80% |
99.30% |
99.40% |
99.40% |
98.90% |
98.70% |
98.80% |
96.5% |
96.4% |
96.3% |
負荷50% |
97.30% |
97.30% |
97.40% |
99.50% |
99.50% |
99.50% |
99.30% |
99.20% |
99.20% |
96.8% |
96.8% |
96.7% |
負荷75% |
97.20% |
97.40% |
97.40% |
99.50% |
99.50% |
99.50% |
99.30% |
99.40% |
99.40% |
96.5% |
96.5% |
96.5% |
負荷100% |
96.80% |
96.90% |
97.10% |
99.40% |
99.50% |
99.50% |
99.30% |
99.40% |
99.40% |
95.9% |
96.0% |