Series Ratings

Class 1630

Series Ratings


This page contains UL Tested and Certified series combination ratings for panelboards. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure. NOTE: Where QO(B) GFI circuit breakers are shown above, QO (B) EPD circuit breakers may also be used.

NQOD Series Ratings

Maximum System Voltage AC [1]

Maximum Short Circuit Current Rating (RMS Sym.)

Integral or Remote Main Circuit Breakers and Remote Main Fuses

Branch Circuit Breaker Designations and Allowable Ampere Ranges  [2] [3]

Type

1-pole

2-pole

3-pole

120/240 1Ø

22k

MG

QO (B)

15–30 A

42k

HD, JD

QO (B) PL

15–30 A

15–60 A

15–30 A

65k

HG, JG

100k

HJ, JJ

125k

HL, JL

120/240 1Ø

208Y/120

100k

DJ 400 A

QO (B)

15–70 A

15–125 A

QO (B) GFI

15–30 A

40–60 A

QO (B) VH

150 A

15–150 A

QO (B) AFI

15–20 A

QJ

QO (B)

15–70 A

15–125 A

15–30 A

QO (B) AS

15–30 A

15–30 A

15–30 A

QO (B) GFI

15–30 A

15–60 A

QO (B) PL

15–30 A

15–60 A

15–30 A

QO (B) VH

150 A

35–150 A

QO (B) AFI

15–20 A

208Y/120

18k

LA/LH (L) 34200MC, LA/LH (L) 34225MC,
LA/LH (L) 34250MC, LA/LH (L) 34400MC

QO (B)

15–30 A

15–30 A

15–30 A

240

22k

QO (B) VH

QO (B)

15–70 A

15–125 A

15–100 A

QO (B) AS

15–30 A

15–30 A

15–30 A

QO (B) GFI

15–30 A

15–60 A

QO (B) PL

15–30 A

15–30 A

QO (B) AFI

15–20 A

Q2-H[4]

QO (B)

15–70 A

15–100 A

15–30 A

QO (B) GFI

15–30 A

15–30 A

QO (B) AFI

15–20 A

240

25k

QD

QO (B)

15–70 A

15–125 A

15–30 A

QO (B) AS

15–30 A

15–30 A

15–30 A

QO (B) GFI

15–30 A

15–60 A

QO (B) PL

15–30 A

15–60 A

15–30 A

QO (B) VH

150 A

35–150 A

QO (B) AFI

15–20 A

ED, FD[4]

QO (B)

15–70 A

15–125 A

15–100 A

QO (B) GFI

15–30 A

15–60 A

QO (B) AFI

15–20 A

KD[4]

QO (B)

15–70 A

15–125 A

15–100 A

QO (B) AS

15–30 A

15–30 A

15–30 A

QO (B) GFI

15–30 A

15–60 A

QO (B) AFI

15–20 A

HD, JD

QO (B)

15–70 A

15–125 A

15–100 A

QO (B) VH

35–150 A

QO (B) GFI

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) H

15–100 A

QOB2150VH

150 A

240

42k

LA, MA

Q2L-H[4]

110–225 A

110–225 A

QDL

70–225 A

70–225 A

MG

QO (B) VH

15–30 A

15–30 A

15–30 A

HD, JD

QO (B) PL

15–30 A

15–60 A

15–30 A

LC

600 A Maximum

QO (B)

15–70 A[5]

QO (B) VH

15–30 A

15–125 A

15–100 A (3P 208 V Max.)

QO (B) GFI

15–30 A[6]

15–60 A

QO (B) AFI

15–20 A

240

65k

LC

600 A Maximum

QO (B) VH

15–30 A

15–125 A

15–100 A (3P 208 V Max.)

QO (B) GFI

15–30 A[6]

QO (B) AFI

15–20 A

DJ 400 A

QO (B)

15–70 A

15–125 A

QO (B) VH

150 A

15–150 A

QO (B) H

15–100 A

EG, FG[4], KG[4]

QO (B)

15–70 A

15–125 A

15–100 A

QO (B) GFI

15–30 A

15–60 A

QO (B) AFI

15–20 A

QG

QO (B)

15–70 A

15–125 A

15–30 A

QO (B) AS

15–30 A

15–30 A

15–30 A

QO (B) VH

35–150 A

QG, HG, JG

QO (B) GFI

15–30 A

15–60 A

QO (B) PL

15–30 A

15–60 A

15–30 A

QO (B) AFI

15–30 A

HG, JG

QO (B)

15–70 A

15–125 A

15–100 A

QO (B) VH

35–150 A

QO (B) H

15–100 A

QOB2150VH

150 A

FC22__

QO (B)

15–70 A

15–100 A

15–100 A

KC22__

QO (B) AS

15–30 A

15–30 A

15–30 A

FC32__

QO (B) GFI

15–30 A

15–30 A

KC32__

QO (B) AFI

15–20 A

400 A Max. Class J or T6 Fuses

QO (B) VH

15–30 A

15–125 A

15–100 A

QOB-VH

150 A

QO (B) AFI

15–20 A

240

100k

FC24__

QO (B)

15–70 A

15–100 A

15–100 A

KC24__

QO (B) AS

15–30 A

15–30 A

15–30 A

FC34__

QO (B) GFI

15–30 A

15–30 A

KC34__

QO (B) AFI

15–20 A

200 A Max. Class T3 Fuses

QO (B) AFI

15–20 A

EJ, FJ[4]

QO (B)

15–70 A

15–125 A

15–100 A

QO (B) GFI

15–30 A

15–60 A

QO (B) AFI

15–20 A

HJ, JJ

QO (B)

15–70 A

15–125 A

15–100 A

QO (B) VH

35–150 A

QO (B) GFI

15–30 A

15–60 A

240

125k

HL. JL

QO (B) PL

15–30 A

15–60 A

15–30 A

QO (B) AFI

15–20 A

QO (B) H

15–100 A

QOB2150VH

150 A

240

200k

FI, KI

QO (B)

15–70 A

15–125 A

15–100 A

QO (B) AS

15–30 A

15–30 A

15–30 A

QO (B) GFI

15–30 A

15–60 A

QO (B) AFI

15–20 A

Maximum Fuses 200 A
Class J or T6 400 A Class T3

QO (B)

15–70 A

15–125 A

15–100 A

QO (B) AS

15–30 A

15–30 A

15–30 A

QO (B) GFI

15–30 A

15–60 A

Footnotes

  1. For shown circuit breakers rated less than this maximum voltage, the indicated short circuit current rating also applies, but at the voltage rating of the circuit breaker.
  2. Suffixes HID, SWD and SWN may also be applied to the applicable branch circuit breakers shown above, except suffix SWN may NOT be applied in combination with LC main circuit breakers.
  3. Where QO (B) circuit breakers are shown above, QO (B) H, QO (B) VH, and QH (B) circuit breakers may also be used.
  4. Obsolescent. Contact the Schneider Electric local Field Sales Office for the replacement circuit breaker. One-pole FJ circuit breakers are still available.
  5. Only 15–30 A circuit breakers may be used when the LC circuit breaker is rated 450, 500 or 600 A.
  6. Circuit breakers may not be used when the LC circuit breaker is rated 450, 500 or 600 A.