IO Module Events and Alarms
IO 1 Events and Alarms
Code |
Application |
Description |
Type |
Priority |
Reset Mode |
---|---|---|---|---|---|
1537 (0x0601) |
General |
IO1 Watchdog reset |
Event |
Medium |
– |
1538 (0x0602) |
General |
IO1 reset to factory setting |
Event |
Medium |
– |
1539 (0x0603) |
General |
IO1 failure (STOP mode) |
Alarm |
High |
Manual or Remote |
1540 (0x0604) |
General |
IO1 failure (ERROR mode) |
Alarm |
Medium |
Manual or Remote |
1541 (0x0605) |
General |
IO1 functional rotary switch position change |
Event |
Medium |
– |
1542 (0x0606) |
General |
IO1 setting locking pad rotary switch position change |
Event |
Medium |
– |
1543 (0x0607) |
General |
IO1 source address dip switch position change |
Event |
Medium |
– |
1552 (0x0610) |
General |
IO1 O1 rising edge (OFF/ON change) |
Event |
Low |
– |
1553 (0x0611) |
General |
IO1 O2 rising edge (OFF/ON change) |
Event |
Low |
– |
1554 (0x0612) |
General |
IO1 O3 rising edge (OFF/ON change) |
Event |
Low |
– |
1555 (0x0613) |
General |
IO1 I1 rising edge (OFF/ON change) |
Event |
Low |
– |
1556 (0x0614) |
General |
IO1 I2 rising edge (OFF/ON change) |
Event |
Low |
– |
1557 (0x0615) |
General |
IO1 I3 rising edge (OFF/ON change) |
Event |
Low |
– |
1558 (0x0616) |
General |
IO1 I4 rising edge (OFF/ON change) |
Event |
Low |
– |
1559 (0x0617) |
General |
IO1 I5 rising edge (OFF/ON change) |
Event |
Low |
– |
1560 (0x0618) |
General |
IO1 I6 rising edge (OFF/ON change) |
Event |
Low |
– |
1561 (0x0619) |
General |
IO1 threshold overrun on I1 counter |
Alarm |
Medium |
Manual or Remote |
1562 (0x061A) |
General |
IO1 threshold overrun on I2 counter |
Alarm |
Medium |
Manual or Remote |
1563 (0x061B) |
General |
IO1 threshold overrun on I3 counter |
Alarm |
Medium |
Manual or Remote |
1564 (0x061C) |
General |
IO1 threshold overrun on I4 counter |
Alarm |
Medium |
Manual or Remote |
1565 (0x061D) |
General |
IO1 threshold overrun on I5 counter |
Alarm |
Medium |
Manual or Remote |
1566 (0x061E) |
General |
IO1 threshold overrun on I6 counter |
Alarm |
Medium |
Manual or Remote |
1567 (0x061F) |
General |
IO1 threshold overrun on O1 counter |
Alarm |
Medium |
Manual or Remote |
1568 (0x0620) |
General |
IO1 threshold overrun on O2 counter |
Alarm |
Medium |
Manual or Remote |
1569 (0x0621) |
General |
IO1 threshold overrun on O3 counter |
Alarm |
Medium |
Manual or Remote |
1570 (0x0622) |
General |
IO1 I1 unforced/forced change |
Event |
Low |
– |
1571 (0x0623) |
General |
IO1 I2 unforced/forced change |
Event |
Low |
– |
1572 (0x0624) |
General |
IO1 I3 unforced/forced change |
Event |
Low |
– |
1573 (0x0625) |
General |
IO1 I4 unforced/forced change |
Event |
Low |
– |
1574 (0x0626) |
General |
IO1 I5 unforced/forced change |
Event |
Low |
– |
1575 (0x0627) |
General |
IO1 I6 unforced/forced change |
Event |
Low |
– |
1576 (0x0628) |
General |
IO1 O1 unforced/forced change |
Event |
Low |
– |
1577 (0x0629) |
General |
IO1 O2 unforced/forced change |
Event |
Low |
– |
1578 (0x062A) |
General |
IO1 O3 unforced/forced change |
Event |
Low |
– |
1579 (0x062B) |
User-defined input acquisition |
IO1 user-defined input 1 |
Alarm |
Medium |
Manual or Remote |
1580 (0x062C) |
User-defined input acquisition |
IO1 user-defined input 2 |
Alarm |
Medium |
Manual or Remote |
1581 (0x062D) |
User-defined input acquisition |
IO1 user-defined input 3 |
Alarm |
Medium |
Manual or Remote |
1582 (0x062E) |
User-defined input acquisition |
IO1 user-defined input 4 |
Alarm |
Medium |
Manual or Remote |
1583 (0x062F) |
User-defined input acquisition |
IO1 user-defined input 5 |
Alarm |
Medium |
Manual or Remote |
1584 (0x0630) |
User-defined input acquisition |
IO1 user-defined input 6 |
Alarm |
Medium |
Manual or Remote |
1585 (0x0631) |
Cooling system |
IO1 switchboard temperature threshold 1 overrun |
Alarm |
Low |
Auto |
1586 (0x0632) |
Cooling system |
IO1 switchboard temperature threshold 2 overrun |
Alarm |
Medium |
Manual or Remote |
1587 (0x0633) |
Cooling system |
IO1 switchboard temperature threshold 3 overrun |
Alarm |
High |
Manual or Remote |
IO 2 Events and Alarms
Code |
Application |
Description |
Type |
Priority |
Reset Mode |
---|---|---|---|---|---|
1793 (0x0701) |
General |
IO2 watchdog reset |
Event |
Medium |
– |
1794 (0x0702) |
General |
IO2 reset to factory settings |
Event |
Medium |
– |
1795 (0x0703) |
General |
IO2 module failure (STOP mode) |
Alarm |
High |
Manual or Remote |
1796 (0x0704) |
General |
IO2 module failure (ERROR mode) |
Alarm |
Medium |
Manual or Remote |
1797 (0x0705) |
General |
IO2 functional rotary switch position change |
Event |
Medium |
– |
1798 (0x0706) |
General |
IO2 setting locking pad rotary switch position change |
Event |
Medium |
– |
1799 (0x0707) |
General |
IO2 source address dip switch position change |
Event |
– |
– |
1808 (0x0710) |
General |
IO2 O1 rising edge (OFF/ON change) |
Event |
Low |
– |
1809 (0x0711) |
General |
IO2 O2 rising edge (OFF/ON change) |
Event |
Low |
– |
1810 (0x0712) |
General |
IO2 O3 rising edge (OFF/ON change) |
Event |
Low |
– |
1811 (0x0713) |
General |
IO2 I1 rising edge (OFF/ON change) |
Event |
Low |
– |
1812 (0x0714) |
General |
IO2 I2 rising edge (OFF/ON change) |
Event |
Low |
– |
1813 (0x0715) |
General |
IO2 I3 rising edge (OFF/ON change) |
Event |
Low |
– |
1814 (0x0716) |
General |
IO2 I4 rising edge (OFF/ON change) |
Event |
Low |
– |
1815 (0x0717) |
General |
IO2 I5 rising edge (OFF/ON change) |
Event |
Low |
– |
1816 (0x0718) |
General |
IO2 I6 rising edge (OFF/ON change) |
Event |
Low |
– |
1817 (0x0719) |
General |
IO2 threshold overrun on I1 counter |
Alarm |
Medium |
Manual or Remote |
1818 (0x071A) |
General |
IO2 threshold overrun on I2 counter |
Alarm |
Medium |
Manual or Remote |
1819 (0x071B) |
General |
IO2 threshold overrun on I3 counter |
Alarm |
Medium |
Manual or Remote |
1820 (0x071C) |
General |
IO2 threshold overrun on I4 counter |
Alarm |
Medium |
Manual or Remote |
1821 (0x071D) |
General |
IO2 threshold overrun on I5 counter |
Alarm |
Medium |
Manual or Remote |
1822 (0x071E) |
General |
IO2 threshold overrun on I6 counter |
Alarm |
Medium |
Manual or Remote |
1823 (0x071F) |
General |
IO2 threshold overrun on O1 counter |
Alarm |
Medium |
Manual or Remote |
1824 (0x0720) |
General |
IO2 threshold overrun on O2 counter |
Alarm |
Medium |
Manual or Remote |
1825 (0x0721) |
General |
IO2 threshold overrun on O3 counter |
Alarm |
Medium |
Manual or Remote |
1826 (0x0722) |
General |
IO2 I1 unforced/forced change |
Event |
Low |
– |
1827 (0x0723) |
General |
IO2 I2 unforced/forced change |
Event |
Low |
– |
1828 (0x0724) |
General |
IO2 I3 unforced/forced change |
Event |
Low |
– |
1829 (0x0725) |
General |
IO2 I4 unforced/forced change |
Event |
Low |
– |
1830 (0x0726) |
General |
IO2 I5 unforced/forced change |
Event |
Low |
– |
1831 (0x0727) |
General |
IO2 I6 unforced/forced change |
Event |
Low |
– |
1832 (0x0728) |
General |
IO2 O1 unforced/forced change |
Event |
Low |
– |
1833 (0x0729) |
General |
IO2 O2 unforced/forced change |
Event |
Low |
– |
1834 (0x072A) |
General |
IO2 O3 unforced/forced change |
Event |
Low |
– |
1835 (0x072B) |
User-defined input acquisition |
IO2 user-defined input 1 |
Alarm |
Medium |
Manual or Remote |
1836 (0x072C) |
User-defined input acquisition |
IO2 user-defined input 2 |
Alarm |
Medium |
Manual or Remote |
1837 (0x072D) |
User-defined input acquisition |
IO2 user-defined input 3 |
Alarm |
Medium |
Manual or Remote |
1838 (0x072E) |
User-defined input acquisition |
IO2 user-defined input 4 |
Alarm |
Medium |
Manual or Remote |
1839 (0x072F) |
User-defined input acquisition |
IO2 user-defined input 5 |
Alarm |
Medium |
Manual or Remote |
1840 (0x0730 |
User-defined input acquisition |
IO2 user-defined input 6 |
Alarm |
Medium |
Manual or Remote |
1841 (0x0731) |
Cooling system |
IO2 switchboard temperature threshold 1 overrun |
Alarm |
Low |
Auto |
1842 (0x0732) |
Cooling system |
IO2 switchboard temperature threshold 2 overrun |
Alarm |
Medium |
Manual or Remote |
1843 (0x0733) |
Cooling system |
IO2 switchboard temperature threshold 3 overrun |
Alarm |
High |
Manual or Remote |
IO 1 and IO 2 Events and Alarms
Code |
Application |
Description |
Type |
Priority |
Reset Mode |
---|---|---|---|---|---|
2304 (0x0900) |
Cradle management |
Cradle position discrepancy |
Alarm |
Medium |
Manual or Remote |
2305 (0x0901) |
Cradle management |
Cradle connected contact change |
Alarm |
Low |
Manual or Remote |
2306 (0x0902) |
Cradle management |
Cradle disconnected contact change |
Alarm |
Low |
Manual or Remote |
2307 (0x0903) |
Cradle management |
Cradle test contact change |
Alarm |
Low |
Manual or Remote |
2308 (0x0904) |
Cradle management |
Remove device from cradle and put it back |
Alarm |
Medium |
Manual or Remote |
2309 (0x0905) |
Cradle management |
Cradle has reached its maximum number of operations |
Alarm |
High |
Manual or Remote |
2310 (0x0906) |
Cradle management |
Remaining service life of cradle is below alarm threshold |
Alarm |
Medium |
Manual or Remote |
2311 (0x0907) |
Cradle management |
New MicroLogic control unit has been detected. |
Alarm |
High |
Manual or Remote |
2432 (0x0980 |
Drawer management |
Drawer position discrepancy |
Alarm |
Medium |
Manual or Remote |
2560 (0x0A00) |
Load control |
Auxiliary contact of the load contactor 1 is not closed |
Alarm |
Medium |
Manual or Remote |
2561 (0x0A01) |
Load control |
Auxiliary contact of the load contactor 1 is not opened |
Alarm |
Medium |
Manual or Remote |
2816 (0x0B00) |
Predefined input acquisition |
Earth leakage trip signal contact (SDV) |
Alarm |
Medium |
Manual or Remote |
2817 (0x0B01) |
Predefined input acquisition |
Control voltage presence contact |
Alarm |
Medium |
Manual or Remote |
2818 (0x0B02) |
Predefined input acquisition |
Surge protection status contact |
Alarm |
Medium |
Manual or Remote |
2819 (0x0B03) |
Predefined input acquisition |
Surge failure contact |
Alarm |
Medium |
Manual or Remote |
2820 (0x0B04) |
Predefined input acquisition |
Switch-disconnector ON/OFF indication contact (OF) |
Alarm |
Medium |
Manual or Remote |
2821 (0x0B05) |
Predefined input acquisition |
Fuse blown indication contact |
Alarm |
Medium |
Manual or Remote |
2822 (0x0B06) |
Predefined input acquisition |
Emergency stop |
Alarm |
High |
Manual or Remote |
2823 (0x0B07) |
Cooling system |
Switchboard temperature contact |
Alarm |
Medium |
Manual or Remote |
2824 (0x0B08) |
Cooling system |
Switchboard ventilation contact |
Alarm |
Medium |
Manual or Remote |
2825 (0x0B09) |
Cooling system |
Switchboard door contact |
Alarm |
Medium |
Manual or Remote |
3072 (0x0C00) |
Protection settings |
Discrepancy with ERMS OFF order and ERMS ON order (MasterPact NT/NW and ComPact NS only) |
Alarm |
High |
Manual or Remote |
3328 (0x0D00) |
General |
Critical hardware modules discrepancy |
Alarm |
High |
Auto |
3329 (0x0D01) |
General |
Critical firmware modules discrepancy |
Alarm |
High |
Auto |
3330 (0x0D02) |
General |
Non-critical hardware modules discrepancy |
Alarm |
Medium |
Auto |
3331 (0x0D03) |
General |
Non-critical firmware modules discrepancy |
Alarm |
Medium |
Auto |