Cross References to Modbus Registers
General Description
The following table gives cross references to the Modbus registers used by the communication modules. The registers are listed in ascending order.
Cross References Table
Address |
Register |
Module |
Description |
Page |
---|---|---|---|---|
0x0226 |
551 |
BSCM module |
Product identification |
|
0x0227–0x022C |
552–557 |
BSCM module |
BSCM module identifier |
|
0x0232 |
563 |
BSCM module |
Circuit breaker status |
|
0x0233 |
564 |
BSCM module |
Communicating motor mechanism status |
|
0x023A–0x0245 |
571–582 |
BSCM module |
BSCM module counters |
|
0x0259–0x028B |
602-652 |
BSCM module |
BSCM module event history |
|
0x03E7–0x03EE |
1000–1007 |
MicroLogic |
Voltage (real-time measurements) |
|
0x03EF–0x03F6 |
1008–1015 |
MicroLogic |
Voltage unbalance (real-time measurements) |
|
0x03F7–0x0402 |
1016–1027 |
MicroLogic |
Current (real-time measurements) |
|
0x0403–0x0407 |
1028–1032 |
MicroLogic |
Current unbalance (real-time measurements) |
|
0x0409–0x040C |
1034–1037 |
MicroLogic |
Active power (real-time measurements) |
|
0x040D–0x0410 |
1038–1041 |
MicroLogic |
Reactive power (real-time measurements) |
|
0x0411–0x0414 |
1042–1045 |
MicroLogic |
Apparent power (real-time measurements) |
|
0x0415–0x0418 |
1046–1049 |
MicroLogic |
Power factor (real-time measurements) |
|
0x0419–0x041C |
1050–1053 |
MicroLogic |
Fundamental power factor (real-time measurements) |
|
0x041D |
1054 |
MicroLogic |
Frequency (real-time measurements) |
|
0x0437–0x043A |
1080–1083 |
MicroLogic |
Fundamental reactive power (real-time measurements) |
|
0x043F–0x0442 |
1088–1091 |
MicroLogic |
Distortion power (real-time measurements) |
|
0x0443–0x044B |
1092–1100 |
MicroLogic |
Total harmonic distortion (THD) (real-time measurements) |
|
0x0477 |
1144 |
MicroLogic |
Thermal image of motor (real-time measurements) |
|
0x0478–0x0479 |
1145–1146 |
MicroLogic |
Voltage (real-time measurements) |
|
0x0513–0x0522 |
1300–1315 |
MicroLogic |
Voltage (minimum of real-time measurement) |
|
0x0523–0x0533 |
1316–1332 |
MicroLogic |
Current (minimum of real-time measurement) |
|
0x07CF–0x07EE |
2000–2031 |
MicroLogic |
Energy measurements |
|
0x0897–0x08BC |
2200–2237 |
MicroLogic |
Demand measurements |
|
0x08C1–0x08C2 |
2242–2243 |
MicroLogic |
Quadrant total |
|
0x0B53–0x0B70 |
2900–2929 |
MicroLogic |
Minimum/maximum measurements reset time |
|
0x0BB7–0x0BB9 |
3000–3002 |
MicroLogic |
Current date and time |
|
0x0CF1 |
3314 |
MicroLogic |
System type |
|
0x0CF3 |
3316 |
MicroLogic |
Power flow sign |
|
0x0CF5 |
3318 |
MicroLogic |
Power factor sign |
|
0x0CFB |
3324 |
MicroLogic |
Energy accumulation mode |
|
0x0D17–0x0D1A |
3352–3355 |
MicroLogic |
Demand time |
|
0x1647 |
5704 |
MicroLogic |
Alarms status |
|
0x1663–0x1694 |
5732–5781 |
MicroLogic |
Alarm history |
|
0x19F9–0x1A02 |
6650–6659 |
MicroLogic |
Long-time protection pre-alarm |
|
0x1A03–0x1A0C |
6660–6669 |
MicroLogic |
Ground-fault protection pre-alarm |
|
0x1A0D–0x1A16 |
6670–6679 |
MicroLogic |
Earth-leakage protection pre-alarm |
|
0x1A71–0x1AE8 |
6770–6889 |
MicroLogic |
User-defined alarms |
|
0x1F3F–0x1FD4 |
8000–8149 |
MicroLogic |
Command interface |
|
0x21FB–0x2200 |
8700–8705 |
MicroLogic |
Serial number |
|
0x220B |
8716 |
MicroLogic |
Product identification |
|
0x2212 |
8723 |
MicroLogic |
Hardware revision |
|
0x2223 |
8740 |
MicroLogic |
Protection type |
|
0x2224 |
8741 |
MicroLogic |
Metering type (A, E) |
|
0x222A |
8747 |
MicroLogic |
Application |
|
0x222B |
8748 |
MicroLogic |
Standard |
|
0x222D |
8750 |
MicroLogic |
Nominal current |
|
0x222E |
8751 |
MicroLogic |
Pole |
|
0x222F |
8752 |
MicroLogic |
16 Hz 2/3 |
|
0x2231–0x223A |
8754–8763 |
MicroLogic |
Long-time protection |
|
0x223B–0x2244 |
8764–8773 |
MicroLogic |
Short-time protection |
|
0x2245–0x224E |
8774–8783 |
MicroLogic |
Instantaneous protection |
|
0x224F–0x2258 |
8784–8793 |
MicroLogic |
Ground-fault protection |
|
0x2259–0x2262 |
8794–8803 |
MicroLogic |
Earth leakage protection |
|
0x2292 |
8851 |
MicroLogic |
Temperature |
|
0x2298 |
8857 |
MicroLogic |
SDx module status |
|
0x22A0 |
8865 |
MicroLogic |
Time remaining until long-time tripping |
|
0x22A7 |
8872 |
MicroLogic |
Phase rotation |
|
0x22C3–0x22C6 |
8900–8903 |
MicroLogic |
Jam protection |
|
0x22C7–0x22CA |
8904–8907 |
MicroLogic |
Unbalance protection |
|
0x22CB–0x22CE |
8908–8911 |
MicroLogic |
Underload protection |
|
0x22CF–0x22D2 |
8912–8915 |
MicroLogic |
Long-start protection |
|
0x22D3–0x22D6 |
8916–8919 |
MicroLogic |
Neutral protection |
|
0x22E1 |
8930 |
MicroLogic |
Thermal memory inhibition |
|
0x238B–0x2401 |
9100–9218 |
MicroLogic |
Trip history |
|
0x258F |
9616 |
MicroLogic |
Nominal voltage Vn |
|
0x2648–0x2651 |
9801–9810 |
MicroLogic |
SDx module outputs |
|
0x270F |
10000 |
MicroLogic |
Trip status |
|
0x27FF–0x29FE |
10240–11751 |
IFE interface |
IP network parameters |
|
0x2DFF–0x2E06 |
11776–11783 |
IFM interface |
Firmware revision |
|
0x2DFF–0x2E06 |
11776–11783 |
IFE interface |
Firmware revision |
|
0x2E07–0x2E0C |
11784–11789 |
IFM interface |
Serial number |
|
0x2E07–0x2E0C |
11784–11789 |
IFE interface |
Hardware revision |
|
0x2E18–0x2E2E |
11801–11823 |
IFM interface |
IMU name |
|
0x2E18–0x2E2E |
11801–11823 |
IFE interface |
IMU name |
|
0x2E45–0x2E5B |
11846–11868 |
IFM interface |
IMU location |
|
0x2E45–0x2E5B |
11846–11868 |
IFE interface |
IMU location |
|
0x2E72 |
11891 |
IFM interface |
Modbus locking pad position |
|
0x2E72 |
11891 |
IFE interface |
Locking pad position |
|
0x2E77–0x2E7A |
11896–11899 |
IFE interface |
Current date and time |
|
0x2E7C |
11901 |
IFM interface |
Product identification |
|
0x2E7C |
11901 |
IFE interface |
Product identification |
|
0x2E7D–0x02E7F |
11902–11904 |
IFE interface |
IFE interface MAC address |
|
0x2E89–0x2E8C |
11914–11917 |
IFE interface |
Manufacturing date and time |
|
0x2E91–0x02E9A |
11922–11931 |
IFE interface |
Serial number |
|
0x2EDF–0x2F82 |
12000–12163 |
IFM interface |
Legacy dataset |
|
0x2EDF–0x2F84 |
12000–12165 |
IFE interface |
Legacy dataset |
|
0x306E |
12399 |
IFM interface |
Auto-Speed sensing state |
|
0x306F |
12400 |
IFM interface |
IFM interface Modbus address |
|
0x306F |
12400–12403 |
IFE interface |
IFE interface Modbus parameters |
|
0x3070 |
12401 |
IFM interface |
Modbus parity |
|
0x3071 |
12402 |
IFM interface |
Modbus Baud rate |
|
0x3072 |
12403 |
IFM interface |
Number of stop bits |
|
0x35FF–0x3668 |
13824–13929 |
IO module |
Analog input of IO 1 |
|
0x3669–0x3848 |
13930–14409 |
IO module |
Digital input of IO 1 |
|
0x3849–0x38FC |
14410–14589 |
IO module |
Digital output of IO 1 |
|
0x38FD–0x3902 |
14590–14595 |
IO module |
Hardware setting of IO 1 |
|
0x3905–0x3908 |
14598–14601 |
IO module |
Digital input and output status of IO 1 |
|
0x392F–0x3976 |
14640–14711 |
IO module |
IO 1 identification |
|
0x3989–0x39A4 |
14730–14759 |
IO module |
Alarm and status of IO 1 |
|
0x3BC3–0x3BE0 |
15300–15329 |
IO module |
Cradle management |
|
0x3BE1–0x3BFE |
15330–15359 |
IO module |
Drawer management |
|
0x3C27–3C30 |
15400–15409 |
IO module |
Light control |
|
0x3C31–3EEC |
15410–16109 |
IO module |
Load control |
|
0x41B8–0x4220 |
16824–16929 |
IO module |
Analog input of IO 2 |
|
0x4221–0x4400 |
16930–17409 |
IO module |
Digital input of IO 2 |
|
0x4401–0x44B4 |
17410–17589 |
IO module |
Digital output of IO 2 |
|
0x44B5–0x44BA |
17590–17595 |
IO module |
Hardware setting of IO 2 |
|
0x44BD–0x44C0 |
17598–17601 |
IO module |
Digital input and output status of IO 2 |
|
0x44E7–0x452F |
17640–17711 |
IO module |
IO 2 identification |
|
0x4541–0x455E |
17730–17759 |
IO module |
Alarm and status of IO 2 |
|
0x72CD |
29390 |
MicroLogic |
Failure status |
|
0x733B–0x733F |
29500–29504 |
MicroLogict |
Maintenance operation record |
|
0x733B–0x736C |
29500–29549 |
MicroLogic |
Maintenance operation number |
|
0x739F–0x73AE |
29600–29615 |
MicroLogic |
Previous long-time protection setup |
|
0x73AF–0x73BA |
29616–29627 |
MicroLogic |
Previous short-time protection setup |
|
0x73BB–0x73BE |
29628–29631 |
MicroLogic |
Previous instantaneous protection setup |
|
0x73BF–0x73CA |
29632–29643 |
MicroLogic |
Previous ground-fault protection setup |
|
0x73CB–0x73D2 |
29644–29651 |
MicroLogic |
Previous earth-leakage protection setup |
|
0x73D3–0x73DE |
29652–29663 |
MicroLogic |
Previous jam protection setup |
|
0x73DF–0x73E6 |
29664–29671 |
MicroLogic |
Previous unbalance protection setup |
|
0x73E6–0x73F2 |
29672–29683 |
MicroLogic |
Previous underload protection setup |
|
0x73F3–0x73FE |
29684–29695 |
MicroLogic |
Previous long-start protection setup |
|
0x73FF–0x7402 |
29696–29699 |
MicroLogic |
Previous neutral protection setup |
|
0x7453–0x745A |
29780–29787 |
MicroLogic |
Minimum/maximum V12 voltage measurements |
|
0x745B–0x7462 |
29788–29795 |
MicroLogic |
Minimum/maximum V23 voltage measurements |
|
0x7463–0x746A |
29796–29803 |
MicroLogic |
Minimum/maximum V31 voltage measurements |
|
0x746B–0x746E |
29804–29807 |
MicroLogic |
Maximum I1 current measurement |
|
0x746F–0x7472 |
29808–29811 |
MicroLogic |
Maximum I2 current measurement |
|
0x7473–0x7476 |
29812–29815 |
MicroLogic |
Maximum I3 current measurement |
|
0x7477–0x747A |
29816–29819 |
MicroLogic |
Maximum IN current measurement |
|
0x747B–0x747E |
29820–29823 |
MicroLogic |
Minimum system frequency |
|
0x747F–0x7482 |
29824–29827 |
MicroLogic |
Maximum system frequency |
|
0x7483–0x7486 |
29828–29831 |
MicroLogic |
I1 peak demand measurement |
|
0x7487–0x748A |
29832–29835 |
MicroLogic |
I2 peak demand measurement |
|
0x748B–0x748E |
29836–29839 |
MicroLogic |
I3 peak demand measurement |
|
0x748F–0x7492 |
29840–29843 |
MicroLogic |
IN peak demand measurement |
|
0x7493–0x7496 |
29844–29847 |
MicroLogic |
P peak demand measurement |
|
0x749A–0x749B |
29851–29852 |
MicroLogic |
Time of use counter |
|
0x749C |
29853 |
MicroLogic |
Rate of wear counter |
|
0x749D |
29854 |
MicroLogic |
Boot counter |
|
0x749E–0x749F |
29885–29886 |
MicroLogic |
EEPROM writing counter |
|
0x74B7–0x74BE |
29880–29887 |
MicroLogic |
Load profile counters |
|
0x74C1–0x74CC |
29890–29901 |
MicroLogic |
Temperature profile counters |
|
0x74D5–0x74DD |
29910–29918 |
MicroLogic |
Protection trips counters |
|
0x74F3–0x74FF |
29940–29952 |
MicroLogic |
Alarms counters |
|
0x751B–0x7520 |
29980–29985 |
MicroLogic |
Maintenance operation counters |
|
0x7525–0x7526 |
29990–29991 |
MicroLogic |
MicroLogic trip unit rotary switches |
|
0x7527 |
29992 |
MicroLogic |
MicroLogic trip unit locking pad status |
|
0x7528 |
29993 |
MicroLogic |
Auxiliary 24 Vdc power supply |
|
0x7529–0x752D |
29994–29998 |
MicroLogic |
Firmware revision |
|
0x752F–0x7532 |
30000–30003 |
MicroLogic |
Part number |
|
0x7534 |
30005 |
MicroLogic |
MicroLogic trip unit LED |
|
0x7CFF–0x7EFE |
32000–32335 |
IFE interface |
Standard dataset |