Anbefalet beskyttelse før indgangen på UPS'en til Easy UPS 3S
Easy UPS 3S – 3:1 UPS-system
UPS-klassifikation | 3+0 parallelt system for kapacitet | 2+0
parallelt system for kapacitet 2+1 parallelt system for redundans |
||||||
---|---|---|---|---|---|---|---|---|
Afbrydertype | Io | Ir | Isd | Afbrydertype | Io | Ir | Isd | |
10 kVA |
Compact NSX160F 160A TM160D (C16F3TM160) |
Fast |
Fast/100 |
/ |
C120H-C-100A/NSX100F 100A TMD (C10F3TM100) |
Fast |
Fast/100 |
/ |
15 kVA |
Compact NSX250F TM250D (C25F3TM250) |
5~10*In |
225 |
/ |
Compact NSX160F 160A TM160D (C16F3TM160) |
Fast |
Fast/160 |
/ |
20 kVA |
NSX400N mic2.3 (C40N32D400) |
280 |
280 |
1,5-10 |
Compact NSX250F TM200D (C25F3TM200) |
5~10*In |
200 |
/ |
30 kVA |
NSX630N mic2.3 (C63N32D630) |
450 |
441 |
1,5-10 |
NSX400N mic2.3 (C40N32D400) |
280 |
280 |
1,5-10 |
Easy UPS 3S – 3:1 UPS-system
UPS-klassifikation | 1+0 enkelt system 1+1 parallelt system for redundans |
|||
---|---|---|---|---|
Afbrydertype | Io | Ir | Isd | |
10 kVA |
iC65H-C-50A/C60H-C-50A |
Fast |
Fast |
/ |
15 kVA |
C120H-C-80A/NSX100F 80A TM100D (C10F3TM080) |
Fast |
Fast/80 |
/ |
20 kVA |
C120H-C-100A/NSX100F 100A TM100D (C10F3TM100) |
Fast |
Fast/100 |
/ |
30 kVA |
Compact NSX160F 160A TM160D (C16F3TM160) |
Fast |
144 |
/ |
Easy UPS 3S – 3:3 UPS-system
UPS-klassifikation | 3+0 parallelt system for kapacitet | 2+0
parallelt system for kapacitet 2+1 parallelt system for redundans |
||||||
---|---|---|---|---|---|---|---|---|
Afbrydertype | Io | Ir | Isd | Afbrydertype | Io | Ir | Isd | |
10 kVA |
iC65H-C-63A / C60H-C-63A /C120H-C-63A |
Fast |
Fast |
Fast |
iC65H-C-40A/C60H-C-40A |
Fast |
Fast |
Fast |
15 kVA |
C120H-C-100A / NSX100F TM100D 100A (C10F3TM100) |
Fast/100 |
Fast/100 |
Fast |
iC65H-C-63A/C60H-C-63A /C120H-C-63A |
Fast |
Fast |
Fast |
20 kVA |
Compact NSX160F TM125D (C16F3TM125) |
Fast |
125 |
Fast |
C120H-C-80A/NSX100F TM80D 80A (C10F3TM080) |
Fast |
Fast/80 |
Fast |
30 kVA |
NSX250N mic2.2 (C25N32D250) |
200 |
200 |
1,5-10 |
Compact NSX160F TM125D (C16F3TM125) |
Fast |
125 |
Fast |
40 kVA |
NSX250N mic2.2 (C25N32D250) |
250 |
225 |
1,5-10 |
Compact NSX160F TM160D (C16F3TM160) |
Fast |
160 |
Fast |
Easy UPS 3S – 3:3 UPS-system
UPS-klassifikation | 1+0 enkelt system 1+1 parallelt system for redundans |
|||
---|---|---|---|---|
Afbrydertype | Io | Ir | Isd | |
10 kVA |
iC65H-C-20A/C60H-C-20A |
Fast |
Fast |
Fast |
15 kVA |
iC65H-C-32A/C60H-C-32A |
Fast |
Fast |
Fast |
20 kVA |
iC65H-C-40A/C60H-C-40A |
Fast |
Fast |
Fast |
30 kVA |
iC65H-C-63A/C60H-C-63A/C120H-C-63A |
Fast |
Fast |
Fast |
40 kVA |
C120H-C-80A/NSX100F TM80D (C10F3TM080) |
Fast |
Fast/80 |
Fast |