Upstream and Downstream Protection
The bypass/output disconnect devices are sized based on the nominal current +10%. This is to accommodate either low grid voltage or deviation in length between parallel UPSs. The battery disconnect devices are sized based on end-of-discharge voltage which has been defined as 308 VDC.
Required Upstream Protection for 380/400/415 V (IEC) and Minimum Prospective Phase-To-Earth Short Circuit at the UPS Input/Bypass Terminals
DANGER |
|---|
|
Hazard of electric shock, explosion, or arc flash
The upstream overcurrent protective device (and its settings)
must be sized to ensure a disconnecting time within 0.07 seconds in
case of a short circuit between the input/bypass phase and the UPS.
Failure to follow these instructions will result in death or serious injury.
|
Compliance is assured with the recommended circuit breaker (and its settings) from the table below.
Required 3-Pole Upstream Protection
| UPS rating | 10 kVA | ||||||
|---|---|---|---|---|---|---|---|
| Input | Bypass/Output | Battery | |||||
| Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380-415 |
|
Circuit breaker type |
NSX100B TM25D 3P3D, C10B3TM025 |
NSX100B TM25D 3P3D, C10B3TM025 |
ComPacT NSX100F DC 3P3D+TM40G, C10F3D+C103MG040 | ||||
| In |
25 |
25 |
25 |
25 |
25 |
25 |
40 |
| Ir |
0.8 x In |
0.8 x In |
0.8 x In |
0.7 x In |
0.7 x In |
0.7 x In |
0.9 x In |
| Im |
300 |
300 |
300 |
300 |
300 |
300 |
100 |
| UPS rating | 15 kVA | ||||||
|---|---|---|---|---|---|---|---|
| Input | Bypass/Output | Battery | |||||
| Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380-415 |
|
Circuit breaker type |
NSX100B NSX TM32D 3P3D, C10B3TM032 |
NSX100B TM32D 3P3D, C10B3TM032 | ComPacT NSX100F DC 3P3D+TM63G, C10F3D+C103MG063 | ||||
| In |
32 |
32 |
32 |
32 |
32 |
32 |
63 |
| Ir |
In |
In |
In |
0.9 x In |
0.8 x In |
0.8 x In |
0.8 x In |
| Im | 400 | 400 | 400 | 400 | 400 | 400 | 150 |
| UPS rating | 20 kVA | ||||||
|---|---|---|---|---|---|---|---|
| Input | Bypass/Output | Battery | |||||
| Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380-415 |
|
Circuit breaker type |
NSX100B TM40D 3P3D, C10B3TM040 |
NSX100B TM40D 3P3D, C10B3TM040 | ComPacT NSX100F DC 3P3D+TM80G, C10F3D+C103MG080 | ||||
| In |
40 |
40 |
40 |
40 |
40 |
40 |
80 |
| Ir |
In |
In |
In |
0.9 x In |
0.9 x In |
0.8 x In |
0.9 x In |
| Im | 500 | 500 | 500 | 500 | 500 | 500 | 250 |
| UPS rating | 30 kVA | ||||||
|---|---|---|---|---|---|---|---|
| Input | Bypass/Output | Battery | |||||
| Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380-415 |
|
Circuit breaker type |
NSX100B TM63D 3P3D, C10B3TM063 | NSX100B TM63D 3P3D, C10B3TM063 | ComPacT NSX160F DC 3P3D+TM125G, C16F3D+C163MG125D | ||||
| In |
63 |
63 |
63 |
63 |
63 |
63 |
125 |
| Ir |
In |
In |
In |
0.9 x In |
0.8 x In |
0.8 x In |
0.8 x In |
| Im | 500 | 500 | 500 | 500 | 500 | 500 | 530 |
| UPS rating | 40 kVA | ||||||
|---|---|---|---|---|---|---|---|
| Input | Bypass/Output | Battery | |||||
| Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380-415 |
|
Circuit breaker type |
NSX100B TM63D 3P3D, C10B3TM080 |
NSX100B TM63D 3P3D, C10B3TM080 | ComPacT NSX160F DC 3P3D+TM160G, C16F3D+C163MG160D | ||||
| In |
80 |
80 |
80 |
80 |
80 |
80 |
160 |
| Ir | In | In | In |
0.9 x In |
0.9 x In |
0.8 x In |
0.9 x In |
| Im | 640 | 640 | 640 | 640 | 640 | 640 | 530 |
Required 4-Pole Upstream Protection
| UPS rating | 10 kVA | ||||||
|---|---|---|---|---|---|---|---|
| Input | Bypass/Output | Battery | |||||
| Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380-415 |
|
Circuit breaker type |
NSX100B TM25D 4P3D, C10B6TM025 |
NSX100B TM25D 4P3D, C10B6TM025 |
ComPacT NSX100F DC 3P3D+TM40G, C10F3D+C103MG040 | ||||
| In |
25 |
25 |
25 |
25 |
25 |
25 |
40 |
| Ir |
0.8 x In |
0.8 x In |
0.8 x In |
0.7 x In |
0.7 x In |
0.7 x In |
0.9 x In |
| Im |
300 |
300 |
300 |
300 |
300 |
300 |
100 |
| UPS rating | 15 kVA | ||||||
|---|---|---|---|---|---|---|---|
| Input | Bypass/Output | Battery | |||||
| Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380-415 |
|
Circuit breaker type |
NSX100B TM40D 4P3D, C10B6TM040 |
NSX100B TM40D 4P3D, C10B6TM040 |
ComPacT NSX100F DC 3P3D+TM63G, C10F3D+C103MG063 | ||||
| In |
40 |
40 |
40 |
40 |
40 |
40 |
63 |
| Ir |
0.8 x In |
0.8 x In |
0.8 x In |
0.7 x In |
0.7 x In |
0.7 x In |
0.8 x In |
| Im | 500 | 500 | 500 | 500 | 500 | 500 | 150 |
| UPS rating | 20 kVA | ||||||
|---|---|---|---|---|---|---|---|
| Input | Bypass/Output | Battery | |||||
| Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380-415 |
|
Circuit breaker type |
NSX100B TM63D 4P3D, C10B6TM063 |
NSX100B TM63D 4P3D, C10B6TM063 |
ComPacT NSX100F DC 3P3D+TM80G, C10F3D+C103MG080 | ||||
| In |
63 |
63 |
63 |
63 |
63 |
63 |
80 |
| Ir |
0.7 x In |
0.7 x In |
0.7 x In |
0.7 x In |
0.7 x In |
0.7 x In |
0.9 x In |
| Im | 500 | 500 | 500 | 500 | 500 | 500 | 250 |
| UPS rating | 30 kVA | ||||||
|---|---|---|---|---|---|---|---|
| Input | Bypass/Output | Battery | |||||
| Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380-415 |
|
Circuit breaker type |
NSX100B TM80D 4P3D, C10B6TM080 |
NSX100B TM80D 4P3D, C10B6TM080 |
ComPacT NSX160F DC 3P3D+TM125G, C16F3D+C163MG125D | ||||
| In |
80 |
80 |
80 |
80 |
80 |
80 |
125 |
| Ir |
0.8 x In |
0.8 x In |
0.8 x In |
0.7 x In |
0.7 x In |
0.7 x In |
0.8 x In |
| Im | 640 | 640 | 640 | 640 | 640 | 640 | 530 |
| UPS rating | 40 kVA | ||||||
|---|---|---|---|---|---|---|---|
| Input | Bypass/Output | Battery | |||||
| Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 | 380-415 |
|
Circuit breaker type |
NSX100B TM100D 4P3D, C10B6TM100 |
NSX100B TM100D 4P3D, C10B6TM100 |
ComPacT NSX160F DC 3P3D+TM160G, C16F3D+C163MG160D | ||||
| In |
100 |
100 |
100 |
100 |
100 |
100 |
160 |
| Ir | 0.8 x In | 0.8 x In | 0.8 x In | 0.7 x In | 0.7 x In | 0.7 x In | 0.9 x In |
| Im | 800 | 800 | 800 | 800 | 800 | 800 | 530 |
Recommended Downstream Protection for 380/400/415 V (IEC)
| UPS rating | Circuit breaker type |
| 10 kVA |
IC65N-4P-C 4A / IC65H-4P-C 4A |
| 15 kVA |
IC65N-4P-C 4A / IC65H-4P-C 4A |
| 20 kVA |
IC65N-4P-C 6A / IC65H-4P-C 6A |
| 30 kVA |
IC65N-4P-C 6A / IC65H-4P-C 6A |
| 40 kVA |
IC65N-4P-C 10A / IC65H-4P-C 10A |
DANGER