Kortslutningskapacitet hos växelriktaren (Bypass inte tillgänglig)
IK1 – kortslutning mellan fas och neutral
IK1 400 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
33/11 |
33/22 |
33/33 |
29/104 |
23/603 |
15 |
50/25 |
50/50 |
50/75 |
44/235 |
34/1 356 |
20 |
67/45 |
67/89 |
67/134 |
58/418 |
46/2 411 |
30 |
100/100 |
100/200 |
100/300 |
87/940 |
68/5 420 |
40 |
133/180 |
133/360 |
133/530 |
116/1 670 |
91/9 640 |
50 |
167/280 |
167/560 |
167/830 |
145/2 610 |
114/15 070 |
60 |
200/400 |
200/800 |
200/1 200 |
174/3 760 |
137/21 700 |
80 |
267/710 |
267/1 420 |
267/2 140 |
232/6 690 |
182/38 580 |
100 |
334/1 110 |
334/2 230 |
334/3 340 |
291/10 450 |
228/60 270 |
120 |
400/1 600 |
400/3 210 |
400/4 810 |
349/15 050 |
274/86 800 |
150 |
500/2 500 |
500/5 010 |
500/7 510 |
436/23 510 |
342/135 620 |
IK1 480 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
28/8 |
28/15 |
28/23 |
24/73 |
19/419 |
15 |
42/17 |
42/35 |
42/52 |
36/163 |
29/942 |
20 |
56/31 |
56/62 |
56/93 |
48/290 |
38/1 674 |
30 |
83/70 |
83/140 |
83/210 |
73/650 |
57/3 770 |
40 |
111/120 |
111/250 |
111/370 |
97/1 160 |
76/6 700 |
50 |
139/190 |
139/390 |
139/580 |
121/1 810 |
95/10 460 |
60 |
167/280 |
167/560 |
167/830 |
145/2 610 |
114/15 070 |
80 |
222/490 |
222/990 |
222/1 480 |
194/4 640 |
152/26 790 |
100 |
278/770 |
278/1 550 |
278/2 320 |
242/7 260 |
190/4 1860 |
120 |
334/1 110 |
334/2 230 |
334/3 340 |
291/10 450 |
228/60 270 |
150 |
417/1 740 |
417/3 480 |
417/5 220 |
363/16 330 |
285/94 180 |
IK1 208 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
64/41 |
64/82 |
64/123 |
56/386 |
44/2 229 |
15 |
96/93 |
96/185 |
96/278 |
84/869 |
66/5 015 |
20 |
128/160 |
128/330 |
128/490 |
112/1 550 |
88/8 920 |
25 |
160/260 |
160/510 |
160/770 |
140/2 420 |
110/13 930 |
30 |
192/370 |
192/740 |
192/1 110 |
168/3 480 |
132/20 060 |
40 |
257/660 |
257/1 320 |
257/1 980 |
224/6 180 |
175/35 670 |
50 |
321/1 030 |
321/2 060 |
321/3 090 |
279/9 660 |
219/55 730 |
60 |
385/1 480 |
385/2 960 |
385/4 450 |
335/13 910 |
263/80 250 |
75 |
481/2 320 |
481/4 630 |
481/6 950 |
419/21 740 |
329/125 390 |
IK2 – kortslutning mellan två faser
IK2 400 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
34/11 |
33/23 |
33/34 |
28/99 |
22/571 |
15 |
50/26 |
50/51 |
50/76 |
42/223 |
33/1 285 |
20 |
67/45 |
67/90 |
67/135 |
56/397 |
44/2 284 |
30 |
101/100 |
100/200 |
100/300 |
84/890 |
67/5 140 |
40 |
135/180 |
134/360 |
134/540 |
112/1 590 |
89/9 140 |
50 |
168/280 |
167/570 |
167/840 |
141/2 480 |
111/14 280 |
60 |
202/410 |
201/810 |
201/1 210 |
169/3 570 |
133/20 560 |
80 |
269/730 |
268/1 450 |
268/2 150 |
225/6 350 |
178/36 550 |
100 |
336/1 130 |
335/2 260 |
335/3 370 |
281/9 920 |
222/57 110 |
120 |
404/1 630 |
401/3 250 |
401/4 850 |
337/14 280 |
266/82 230 |
150 |
505/2 550 |
502/5 090 |
502/7 580 |
422/22 320 |
333/128 490 |
IK2 480 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
28/8 |
28/16 |
28/23 |
23/69 |
18/397 |
15 |
42/18 |
42/35 |
42/53 |
35/155 |
28/892 |
20 |
56/31 |
56/63 |
56/94 |
47/276 |
37/1 586 |
30 |
84/70 |
84/140 |
84/210 |
70/620 |
55/3 570 |
40 |
112/130 |
112/250 |
112/370 |
94/1 100 |
74/6 350 |
50 |
140/200 |
139/390 |
139/580 |
117/1 720 |
92/9 910 |
60 |
168/280 |
167/570 |
167/840 |
141/2 480 |
111/14 280 |
80 |
224/500 |
223/1 000 |
223/1 500 |
187/4 410 |
148/25 380 |
100 |
280/790 |
279/1 570 |
279/2 340 |
234/6 890 |
185/39 660 |
120 |
336/1 130 |
335/2 260 |
335/3 370 |
281/9 920 |
222/57 110 |
150 |
421/1 770 |
418/3 530 |
418/5 260 |
351/15 500 |
277/89 230 |
IK2 208 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
65/42 |
64/84 |
64/125 |
54/367 |
43/2 112 |
15 |
97/94 |
96/188 |
96/280 |
81/825 |
64/4 752 |
20 |
129/170 |
129/330 |
129/500 |
108/1 470 |
85/8 450 |
25 |
162/260 |
161/520 |
161/780 |
135/2 290 |
107/13 200 |
30 |
194/380 |
193/750 |
193/1 120 |
162/3 300 |
128/19 010 |
40 |
259/670 |
257/1 340 |
257/1 990 |
216/5 870 |
171/33 790 |
50 |
323/1 050 |
322/2 090 |
322/3 110 |
270/9 170 |
213/52 800 |
60 |
388/1 510 |
386/3 010 |
386/4 480 |
324/13 210 |
256/76 030 |
75 |
485/2 360 |
482/4 700 |
482/7 000 |
406/20 630 |
320/118 790 |
IK3 – kortslutning mellan tre faser
IK3 400 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
30/9 |
30/18 |
30/27 |
29/88 |
23/574 |
15 |
45/20 |
45/40 |
45/60 |
43/198 |
34/1 290 |
20 |
60/36 |
60/71 |
60/107 |
57/351 |
45/2 294 |
30 |
90/80 |
90/160 |
90/240 |
86/790 |
68/5 160 |
40 |
119/140 |
119/290 |
119/430 |
115/1 400 |
90/9 180 |
50 |
149/220 |
149/450 |
149/670 |
143/2 200 |
113/14 340 |
60 |
179/320 |
179/640 |
179/960 |
172/3 160 |
136/20 650 |
80 |
239/570 |
239/1 140 |
239/1 710 |
229/5 620 |
181/36 710 |
100 |
298/890 |
298/1 780 |
298/2 670 |
287/8 780 |
226/57 350 |
120 |
358/1 280 |
358/2 570 |
358/3 850 |
344/12 640 |
271/82 590 |
150 |
448/2 000 |
448/4 010 |
448/6 010 |
430/19 760 |
339/129 040 |
IK3 480 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
25/6 |
25/12 |
25/19 |
24/61 |
19/398 |
15 |
37/14 |
37/28 |
37/42 |
36/137 |
28/896 |
20 |
50/25 |
50/49 |
50/74 |
48/244 |
38/1 593 |
30 |
75/60 |
75/110 |
75/170 |
72/550 |
57/3 580 |
40 |
99/100 |
99/200 |
99/300 |
96/980 |
75/6 370 |
50 |
124/150 |
124/310 |
124/460 |
119/1 520 |
94/9 960 |
60 |
149/220 |
149/450 |
149/670 |
143/2 200 |
113/14 340 |
80 |
199/400 |
199/790 |
199/1 190 |
191/3 900 |
151/25 490 |
100 |
249/620 |
249/1 240 |
249/1 860 |
239/6 100 |
188/39 830 |
120 |
298/890 |
298/1 780 |
298/2 670 |
287/8 780 |
226/57 350 |
150 |
373/1 390 |
373/2 780 |
373/4 180 |
358/13 720 |
283/89 610 |
IK3 208 V
S [kVA] |
10 ms; I[A]/I2t [A2t] |
20 ms; I[A]/I2t [A2t] |
30 ms; I[A]/I2t [A2t] |
100 ms; I[A]/I2t [A2t] |
1 s; I[A]/I2t [A2t] |
---|---|---|---|---|---|
10 |
57/33 |
57/66 |
57/99 |
55/325 |
43/2 121 |
15 |
86/74 |
86/148 |
86/222 |
83/731 |
65/4 772 |
20 |
115/130 |
115/260 |
115/400 |
110/1 300 |
87/8 480 |
25 |
143/210 |
143/410 |
143/620 |
138/2 030 |
109/13 260 |
30 |
172/300 |
172/590 |
172/890 |
165/2 920 |
130/19 090 |
40 |
230/530 |
230/1 050 |
230/1 580 |
220/5 200 |
174/33 940 |
50 |
287/820 |
287/1 650 |
287/2 470 |
276/8 120 |
217/53 020 |
60 |
344/1 190 |
344/2 370 |
344/3 560 |
331/11 690 |
261/76 360 |
75 |
430/1 850 |
430/3 710 |
430/5 560 |
413/18 270 |
326/119 310 |