Environment
Operating | Storage | |
---|---|---|
Temperature | 0
°C to 40 °C without load derating. 40 °C to 50 °C when derated to 75% power. |
-25 °C to 55 °C for systems without batteries. |
Relative humidity | 5-90% non-condensing | 0-95% non-condensing |
Elevation | Designed for operation in 0-3000 m elevation. Derating required from 1000-3000 m with forced air cooling: 0 to 1000 m: 1.000 1000 to 1500 m: 0.975 1500 to 2000 m: 0.950 2000 to 2500 m: 0.925 2500 to 3000 m: 0.900 |
|
Audible noise one meter from unit | 69
dB at 70% load 78 dB at 100% load NOTE: The noise level can be higher during charging/battery operation.
Use appropriate hearing protection per local regulations.
|
|
Protection class | IP20 | |
Color | RAL 9003, gloss level 85% |
Heat Dissipation in BTU/hr
500 kW
Normal operation | ECO mode | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
12 799 |
13 225 |
13 652 |
3 413 |
2 986 |
3 413 |
50% load |
22 184 |
22 184 |
22 184 |
5 119 |
4 266 |
4 266 |
75% load |
34 556 |
33 276 |
33 276 |
6 399 |
5 119 |
6 399 |
100% load |
51 195 |
47 782 |
47 782 |
8 532 |
6 826 |
8 532 |
eConversion | Battery operation | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
5 973 |
5 546 |
6 399 |
15 785 |
15 785 |
16 212 |
50% load |
7 679 |
6 826 |
6 826 |
28 157 |
28 157 |
28 157 |
75% load |
8 959 |
7 679 |
8 959 |
44 795 |
44 795 |
44 795 |
100% load |
10 239 |
10 239 |
10 239 |
68 259 |
66 553 |
66 553 |
600 kW
Normal operation | ECO mode | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
15 870 |
16 382 |
16 894 |
4 096 |
4 096 |
4 096 |
50% load |
25 597 |
26 621 |
26 621 |
6 143 |
6 143 |
6 143 |
75% load |
39 932 |
41 468 |
39 932 |
9 215 |
7 679 |
7 679 |
100% load |
59 386 |
59 386 |
57 338 |
12 287 |
10 239 |
10 239 |
eConversion | Battery operation | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
7 167 |
6 143 |
9 727 |
18 430 |
18 430 |
19 454 |
50% load |
9 215 |
8 191 |
10 239 |
32 765 |
31 741 |
33 788 |
75% load |
10 751 |
10 751 |
12 287 |
53 754 |
50 683 |
53 754 |
100% load |
14 334 |
12 287 |
14 334 |
81 911 |
77 816 |
79 863 |
625 kW
Normal operation | ECO mode | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
15 998 |
16 532 |
17 065 |
4 266 |
3 733 |
3 733 |
50% load |
26 664 |
27 730 |
26 664 |
6 399 |
6 399 |
5 333 |
75% load |
43 195 |
43 195 |
39 996 |
9 599 |
7 999 |
7 999 |
100% load |
63 993 |
61 860 |
59 727 |
12 799 |
10 666 |
10 666 |
eConversion | Battery operation | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
6 933 |
5 866 |
8 532 |
19 731 |
19 731 |
21 331 |
50% load |
9 599 |
8 532 |
9 599 |
35 196 |
35 196 |
36 263 |
75% load |
11 199 |
11 199 |
11 199 |
55 994 |
55 994 |
57 594 |
100% load |
14 932 |
14 932 |
14 932 |
85 324 |
85 324 |
87 457 |
750 kW
Normal operation | ECO mode | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
19 198 |
20 478 |
19 838 |
4 480 |
4 480 |
4 480 |
50% load |
31 997 |
33 276 |
33 276 |
7 679 |
7 679 |
7 679 |
75% load |
51 834 |
51 834 |
49 915 |
11 519 |
9 599 |
9 599 |
100% load |
79 352 |
74 232 |
71 672 |
15 358 |
12 799 |
12 799 |
eConversion | Battery operation | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
8 319 |
8 319 |
8 319 |
23 677 |
23 677 |
24 317 |
50% load |
11 519 |
11 519 |
12 799 |
42 235 |
42 235 |
42 235 |
75% load |
13 439 |
13 439 |
13 439 |
67 193 |
69 113 |
65 273 |
100% load |
17 918 |
17 918 |
17 918 |
102 389 |
102 389 |
99 829 |
875 kW
Normal operation | ECO mode | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
22 398 |
23 891 |
23 144 |
5 226 |
5 226 |
5 226 |
50% load |
38 823 |
38 823 |
38 823 |
8 959 |
8 959 |
8 959 |
75% load |
60 474 |
58 234 |
58 234 |
13 439 |
11 199 |
11 199 |
100% load |
92 577 |
86 604 |
83 618 |
17 918 |
14 932 |
14 932 |
eConversion | Battery operation | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
9 706 |
9 706 |
9 706 |
29 117 |
27 624 |
29 117 |
50% load |
13 439 |
11 945 |
13 439 |
52 261 |
49 275 |
50 768 |
75% load |
15 678 |
15 678 |
15 678 |
82 871 |
78 392 |
80 631 |
100% load |
20 904 |
20 904 |
20 904 |
125 427 |
116 468 |
119 454 |
1000 kW
Normal operation | ECO mode | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
26 451 |
27 304 |
27 304 |
5 973 |
5 973 |
5 973 |
50% load |
44 369 |
44 369 |
44 369 |
10 239 |
10 239 |
10 239 |
75% load |
71 672 |
69 113 |
66 553 |
15 358 |
12 799 |
15 358 |
100% load |
105 802 |
102 389 |
95 563 |
20 478 |
17 065 |
20 478 |
eConversion | Battery operation | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
11 092 |
9 386 |
11 092 |
30 717 |
31 570 |
32 423 |
50% load |
15 358 |
11 945 |
13 652 |
56 314 |
56 314 |
56 314 |
75% load |
17 918 |
17 918 |
17 918 |
89 590 |
89 590 |
89 590 |
100% load |
23 891 |
23 891 |
23 891 |
136 519 |
136 519 |
133 106 |
1125 kW
Normal operation | ECO mode | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
29 757 |
29 757 |
30 717 |
6 719 |
6 719 |
6 719 |
50% load |
51 834 |
49 915 |
49 915 |
11 519 |
11 519 |
11 519 |
75% load |
80 631 |
77 752 |
77 752 |
17 278 |
17 278 |
17 278 |
100% load |
122 867 |
115 188 |
111 348 |
23 038 |
23 038 |
23 038 |
eConversion | Battery operation | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
12 479 |
11 519 |
11 519 |
34 556 |
34 556 |
36 476 |
50% load |
17 278 |
15 358 |
15 358 |
63 353 |
61 433 |
63 353 |
75% load |
20 158 |
20 158 |
20 158 |
103 669 |
97 910 |
100 789 |
100% load |
30 717 |
26 877 |
26 877 |
153 584 |
149 744 |
153 584 |
1250 kW
Normal operation | ECO mode | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
33 063 |
33 063 |
34 130 |
7 466 |
6 399 |
6 399 |
50% load |
57 594 |
57 594 |
55 461 |
10 666 |
10 666 |
10 666 |
75% load |
89 590 |
83 191 |
83 191 |
15 998 |
15 998 |
15 998 |
100% load |
136 519 |
132 253 |
123 720 |
25 597 |
21 331 |
21 331 |
eConversion | Battery operation | |||||
---|---|---|---|---|---|---|
Voltage (V) | 380 | 400 | 415 | 380 | 400 | 415 |
25% load |
11 732 |
13 865 |
12 799 |
36 263 |
39 462 |
38 396 |
50% load |
14 932 |
17 065 |
17 065 |
66 126 |
70 392 |
68 259 |
75% load |
22 398 |
19 198 |
19 198 |
108 788 |
111 988 |
108 788 |
100% load |
29 863 |
25 597 |
25 597 |
170 648 |
170 648 |
166 382 |
Airflow Values
Indicative Airflow Values in m3/Hour Based on a 30 °C Environment in Double Conversion Mode
UPS rating | 500 kW | 600 kW | 625 kW | 750 kW | 875 kW | 1000 kW | 1125 kW | 1250 kW |
---|---|---|---|---|---|---|---|---|
50% load |
3249 |
3693 |
3774 |
4300 |
4826 |
5352 |
5877 |
6403 |
75% load |
4196 |
4800 |
4959 |
5722 |
6484 |
7247 |
8010 |
8772 |
90% load |
4888 |
5605 |
5823 |
6758 |
7694 |
8629 |
9565 |
10 500 |
100% load |
5400 |
6201 |
6463 |
7526 |
8590 |
9653 |
10 717 |
11 780 |
Indicative Airflow Values in m3/Hour Based on a 40 °C Environment in Double Conversion Mode
UPS rating | 500 kW | 600 kW | 625 kW | 750 kW | 875 kW | 1000 kW | 1125 kW | 1250 kW |
---|---|---|---|---|---|---|---|---|
50% load |
3587 |
4037 |
4202 |
4817 |
5432 |
6047 |
6662 |
7277 |
75% load |
4691 |
5244 |
5582 |
6473 |
7364 |
8255 |
9146 |
10 037 |
90% load |
5483 |
6109 |
6572 |
7661 |
8750 |
9839 |
10 928 |
12 017 |
100% load |
6071 |
6745 |
7307 |
8543 |
9779 |
11 015 |
12 251 |
13 487 |