990-55333B-001

Environment

  Operating Storage
Temperature 0 °C to 40 °C without load derating.
40 °C to 50 °C when derated to 75% power.
-25 °C to 55 °C for systems without batteries.
Relative humidity 5-90% non-condensing 0-95% non-condensing
Elevation Designed for operation in 0-3000 m elevation.
Derating required from 1000-3000 m with forced air cooling:
0 to 1000 m: 1.000
1000 to 1500 m: 0.975
1500 to 2000 m: 0.950
2000 to 2500 m: 0.925
2500 to 3000 m: 0.900
 
Audible noise one meter from unit 69 dB at 70% load
78 dB at 100% load
NOTE: The noise level can be higher during charging/battery operation. Use appropriate hearing protection per local regulations.
Protection class IP20
Color RAL 9003, gloss level 85%

Heat Dissipation in BTU/hr

500 kW

  Normal operation ECO mode
Voltage (V) 380 400 415 380 400 415
25% load

12 799

13 225

13 652

3 413

2 986

3 413

50% load

22 184

22 184

22 184

5 119

4 266

4 266

75% load

34 556

33 276

33 276

6 399

5 119

6 399

100% load

51 195

47 782

47 782

8 532

6 826

8 532

  eConversion Battery operation
Voltage (V) 380 400 415 380 400 415
25% load

5 973

5 546

6 399

15 785

15 785

16 212

50% load

7 679

6 826

6 826

28 157

28 157

28 157

75% load

8 959

7 679

8 959

44 795

44 795

44 795

100% load

10 239

10 239

10 239

68 259

66 553

66 553

600 kW

  Normal operation ECO mode
Voltage (V) 380 400 415 380 400 415
25% load

15 870

16 382

16 894

4 096

4 096

4 096

50% load

25 597

26 621

26 621

6 143

6 143

6 143

75% load

39 932

41 468

39 932

9 215

7 679

7 679

100% load

59 386

59 386

57 338

12 287

10 239

10 239

  eConversion Battery operation
Voltage (V) 380 400 415 380 400 415
25% load

7 167

6 143

9 727

18 430

18 430

19 454

50% load

9 215

8 191

10 239

32 765

31 741

33 788

75% load

10 751

10 751

12 287

53 754

50 683

53 754

100% load

14 334

12 287

14 334

81 911

77 816

79 863

625 kW

  Normal operation ECO mode
Voltage (V) 380 400 415 380 400 415
25% load

15 998

16 532

17 065

4 266

3 733

3 733

50% load

26 664

27 730

26 664

6 399

6 399

5 333

75% load

43 195

43 195

39 996

9 599

7 999

7 999

100% load

63 993

61 860

59 727

12 799

10 666

10 666

  eConversion Battery operation
Voltage (V) 380 400 415 380 400 415
25% load

6 933

5 866

8 532

19 731

19 731

21 331

50% load

9 599

8 532

9 599

35 196

35 196

36 263

75% load

11 199

11 199

11 199

55 994

55 994

57 594

100% load

14 932

14 932

14 932

85 324

85 324

87 457

750 kW

  Normal operation ECO mode
Voltage (V) 380 400 415 380 400 415
25% load

19 198

20 478

19 838

4 480

4 480

4 480

50% load

31 997

33 276

33 276

7 679

7 679

7 679

75% load

51 834

51 834

49 915

11 519

9 599

9 599

100% load

79 352

74 232

71 672

15 358

12 799

12 799

  eConversion Battery operation
Voltage (V) 380 400 415 380 400 415
25% load

8 319

8 319

8 319

23 677

23 677

24 317

50% load

11 519

11 519

12 799

42 235

42 235

42 235

75% load

13 439

13 439

13 439

67 193

69 113

65 273

100% load

17 918

17 918

17 918

102 389

102 389

99 829

875 kW

  Normal operation ECO mode
Voltage (V) 380 400 415 380 400 415
25% load

22 398

23 891

23 144

5 226

5 226

5 226

50% load

38 823

38 823

38 823

8 959

8 959

8 959

75% load

60 474

58 234

58 234

13 439

11 199

11 199

100% load

92 577

86 604

83 618

17 918

14 932

14 932

  eConversion Battery operation
Voltage (V) 380 400 415 380 400 415
25% load

9 706

9 706

9 706

29 117

27 624

29 117

50% load

13 439

11 945

13 439

52 261

49 275

50 768

75% load

15 678

15 678

15 678

82 871

78 392

80 631

100% load

20 904

20 904

20 904

125 427

116 468

119 454

1000 kW

  Normal operation ECO mode
Voltage (V) 380 400 415 380 400 415
25% load

26 451

27 304

27 304

5 973

5 973

5 973

50% load

44 369

44 369

44 369

10 239

10 239

10 239

75% load

71 672

69 113

66 553

15 358

12 799

15 358

100% load

105 802

102 389

95 563

20 478

17 065

20 478

  eConversion Battery operation
Voltage (V) 380 400 415 380 400 415
25% load

11 092

9 386

11 092

30 717

31 570

32 423

50% load

15 358

11 945

13 652

56 314

56 314

56 314

75% load

17 918

17 918

17 918

89 590

89 590

89 590

100% load

23 891

23 891

23 891

136 519

136 519

133 106

1125 kW

  Normal operation ECO mode
Voltage (V) 380 400 415 380 400 415
25% load

29 757

29 757

30 717

6 719

6 719

6 719

50% load

51 834

49 915

49 915

11 519

11 519

11 519

75% load

80 631

77 752

77 752

17 278

17 278

17 278

100% load

122 867

115 188

111 348

23 038

23 038

23 038

  eConversion Battery operation
Voltage (V) 380 400 415 380 400 415
25% load

12 479

11 519

11 519

34 556

34 556

36 476

50% load

17 278

15 358

15 358

63 353

61 433

63 353

75% load

20 158

20 158

20 158

103 669

97 910

100 789

100% load

30 717

26 877

26 877

153 584

149 744

153 584

1250 kW

  Normal operation ECO mode
Voltage (V) 380 400 415 380 400 415
25% load

33 063

33 063

34 130

7 466

6 399

6 399

50% load

57 594

57 594

55 461

10 666

10 666

10 666

75% load

89 590

83 191

83 191

15 998

15 998

15 998

100% load

136 519

132 253

123 720

25 597

21 331

21 331

  eConversion Battery operation
Voltage (V) 380 400 415 380 400 415
25% load

11 732

13 865

12 799

36 263

39 462

38 396

50% load

14 932

17 065

17 065

66 126

70 392

68 259

75% load

22 398

19 198

19 198

108 788

111 988

108 788

100% load

29 863

25 597

25 597

170 648

170 648

166 382

Airflow Values

Indicative Airflow Values in m3/Hour Based on a 30 °C Environment in Double Conversion Mode

UPS rating 500 kW 600 kW 625 kW 750 kW 875 kW 1000 kW 1125 kW 1250 kW
50% load

3249

3693

3774

4300

4826

5352

5877

6403

75% load

4196

4800

4959

5722

6484

7247

8010

8772

90% load

4888

5605

5823

6758

7694

8629

9565

10 500

100% load

5400

6201

6463

7526

8590

9653

10 717

11 780

Indicative Airflow Values in m3/Hour Based on a 40 °C Environment in Double Conversion Mode

UPS rating 500 kW 600 kW 625 kW 750 kW 875 kW 1000 kW 1125 kW 1250 kW
50% load

3587

4037

4202

4817

5432

6047

6662

7277

75% load

4691

5244

5582

6473

7364

8255

9146

10 037

90% load

5483

6109

6572

7661

8750

9839

10 928

12 017

100% load

6071

6745

7307

8543

9779

11 015

12 251

13 487