Cross References to Modbus Registers for MasterPact NT/NW and PowerPact M-, P-, and R- Frame Circuit Breakers
General Description
The following table gives cross references to the Modbus registers used by the communication modules. The registers are listed in ascending order.
Cross References Table
|
Address |
Register |
Module |
Description |
Page |
|---|---|---|---|---|
|
0x0095–0x009B |
150–156 |
BCM ULP module |
Trip history |
|
|
0x0202 |
515 |
BCM ULP module |
Product identification |
|
|
0x0215–0x021E |
534–543 |
BCM ULP module |
BCM ULP module identifier |
|
|
0x0229–0x022A |
554–555 |
BCM ULP module |
BCM ULP module counters |
|
|
0x0240 |
577 |
BCM ULP module |
Firmware version |
|
|
0x0243–0x0244 |
580–581 |
BCM ULP module |
Counter thresholds |
|
|
0x0289–0x028A |
650–651 |
BCM ULP module |
Tripping cause |
|
|
0x0291–0x0292 |
658–659 |
BCM ULP module |
Inhibit close order |
|
|
0x0293 |
660 |
BCM ULP module |
Local/remote mode |
|
|
0x0294 |
661 |
BCM ULP module |
Circuit breaker status |
|
|
0x0295–0x0298 |
662–665 |
BCM ULP module |
Circuit breaker operation counters |
|
|
0x029D |
670 |
BCM ULP module |
Auto/Manu mode |
|
|
0x029E–0x02A0 |
671–673 |
BCM ULP module |
Date of last actuation of MX auxiliary |
|
|
0x02A1 |
674 |
BCM ULP module |
MX actuation counter |
|
|
0x02A2 |
675 |
BCM ULP module |
Date of last actuation of XF auxiliary |
|
|
0x02A5 |
678 |
BCM ULP module |
XF actuation counter |
|
|
0x02A6–0x02A9 |
679–682 |
BCM ULP module |
Current date of BCM ULP module |
|
|
0x02AB–0x02BD |
684–702 |
BCM ULP module |
Date of last event |
|
|
0x031F |
800 |
BCM ULP module |
Legacy dataset activation |
|
|
0x0325 |
806 |
BCM ULP module |
Communication parameter |
|
|
0x0326–0x032B |
807–812 |
BCM ULP module |
Energy Reduction Maintenance Switch (ERMS) |
|
|
0x032C |
813 |
BCM ULP module |
Contact wear |
|
|
0x03E7–0x03F6 |
1000–1015 |
MicroLogic trip unit |
Voltage and voltage unbalance (real time-measurements) |
|
|
0x03F7–0x0407 |
1016–1032 |
MicroLogic trip unit |
Current and current unbalance (real time-measurements) |
|
|
0x0409–0x0414 |
1034–1045 |
MicroLogic trip unit |
Active, reactive, and apparent power (real time-measurements) |
|
|
0x0415–0x041C |
1046–1053 |
MicroLogic trip unit |
Power factor and fundamental power factor (real time-measurements) |
|
|
0x041D |
1054 |
MicroLogic trip unit |
Frequency (real time-measurements) |
|
|
0x041F–0x0424 |
1056–1061 |
MicroLogic trip unit |
Fundamental voltage (real time-measurements) |
|
|
0x042B–0x042E |
1068–1071 |
MicroLogic trip unit |
Fundamental current (real time-measurements) |
|
|
0x0433–0x0436 |
1076–1079 |
MicroLogic trip unit |
Fundamental active power (real time-measurements) |
|
|
0x0437–0x043A |
1080–1083 |
MicroLogic trip unit |
Fundamental reactive power (real time-measurements) |
|
|
0x043B–0x043E |
1084–1087 |
MicroLogic trip unit |
Fundamental apparent power (real time-measurements) |
|
|
0x043F–0x0442 |
1088–1091 |
MicroLogic trip unit |
Distortion power (real time-measurements) |
|
|
0x0443–0x044C |
1092–1101 |
MicroLogic trip unit |
Total harmonic distortion in relation to the fundamental (THD) (real time-measurements) |
Total Harmonic Distortion in Relation to the Fundamental (THD) |
|
0x044D–0x0456 |
1102–1111 |
MicroLogic trip unit |
Total harmonic distortion in relation to the RMS Value (thd) (real time-measurements) |
Total Harmonic Distortion in Relation to the RMS Value (thd) |
|
0x0457–0x0459 |
1112–1114 |
MicroLogic trip unit |
Voltage to current phase shift (real time-measurements) |
|
|
0x045A–0x045D |
1115–1118 |
MicroLogic trip unit |
K-Factor (real time-measurements) |
|
|
0x045E–0x0467 |
1119–1128 |
MicroLogic trip unit |
Peak factor (real time-measurements) |
|
|
0x046C–0x046E |
1133–1135 |
MicroLogic trip unit |
Voltage-to-voltage phase shift (real time-measurements) |
|
|
0x0513–0x0522 |
1300–1315 |
MicroLogic trip unit |
Voltage (minimum of real-time measurement) |
|
|
0x0523–0x0533 |
1316–1332 |
MicroLogic trip unit |
Current (minimum of real-time measurement) |
|
|
0x0535–0x0540 |
1334–1345 |
MicroLogic trip unit |
Active, reactive, and apparent power (minimum of real-time measurement) |
|
|
0x0541–0x0548 |
1346–1353 |
MicroLogic trip unit |
Power factor (minimum of real-time measurement) |
|
|
0x0549–0x054A |
1354–1355 |
MicroLogic trip unit |
Frequency (minimum of real-time measurement) |
|
|
0x054B–0x0551 |
1356–1362 |
MicroLogic trip unit |
Fundamental voltage (minimum of real-time measurement) |
|
|
0x0557–0x055B |
1368–1372 |
MicroLogic trip unit |
Fundamental current (minimum of real-time measurement) |
|
|
0x055F–0x0562 |
1376–1379 |
MicroLogic trip unit |
Fundamental active power (minimum of real-time measurement) |
|
|
0x0563–0x0566 |
1380–1383 |
MicroLogic trip unit |
Fundamental reactive power (minimum of real-time measurement) |
|
|
0x0567–0x056A |
1384–1387 |
MicroLogic trip unit |
Fundamental apparent power (minimum of real-time measurement) |
|
|
0x056B–0x056E |
1388–1391 |
MicroLogic trip unit |
Distortion power (minimum of real-time measurement) |
|
|
0x056–0x0578 |
1392–1401 |
MicroLogic trip unit |
Total harmonic distortion in relation to the fundamental (THD) (minimum of real-time measurement) |
|
|
0x0579–0x0582 |
1402–1411 |
MicroLogic trip unit |
Total harmonic distortion in relation to the RMS Value (thd) (minimum of real-time measurement) |
|
|
0x0583–0x0585 |
1412–1414 |
MicroLogic trip unit |
Voltage to current phase shift (minimum of real-time measurement) |
|
|
0x0586–0x0589 |
1415–1418 |
MicroLogic trip unit |
K-Factor (minimum of real-time measurement) |
|
|
0x058A–0x0593 |
1419–1428 |
MicroLogic trip unit |
Peak factor (minimum of real-time measurement) |
|
|
0x0598–0x059A |
1433–1435 |
MicroLogic trip unit |
Voltage-to-voltage phase shift (minimum of real-time measurement) |
|
|
0x063F–0x064E |
1600–1615 |
MicroLogic trip unit |
Voltage (maximum of real-time measurement) |
|
|
0x064F–0x065F |
1616–1632 |
MicroLogic trip unit |
Current (maximum of real-time measurement) |
|
|
0x0661–0x066C |
1634–1645 |
MicroLogic trip unit |
Active, reactive, and apparent power (maximum of real-time measurement) |
|
|
0x066D–0x0674 |
1646–1653 |
MicroLogic trip unit |
Power factor (maximum of real-time measurement) |
|
|
0x0675–0x0676 |
1654–1655 |
MicroLogic trip unit |
Frequency (maximum of real-time measurement) |
|
|
0x0677–0x067D |
1656–1662 |
MicroLogic trip unit |
Fundamental voltage (maximum of real-time measurement) |
|
|
0x0683–0x0687 |
1668–1672 |
MicroLogic trip unit |
Fundamental current (maximum of real-time measurement) |
|
|
0x068B–0x068E |
1676–1679 |
MicroLogic trip unit |
Fundamental active power (maximum of real-time measurement) |
|
|
0x068F–0x0692 |
1680–1683 |
MicroLogic trip unit |
Fundamental reactive power (maximum of real-time measurement) |
|
|
0x0693–0x0696 |
1684–1687 |
MicroLogic trip unit |
Fundamental apparent power (maximum of real-time measurement) |
|
|
0x0697–0x069A |
1688–1691 |
MicroLogic trip unit |
Distortion power (maximum of real-time measurement) |
|
|
0x069B–0x06A4 |
1692–1701 |
MicroLogic trip unit |
Total harmonic distortion in relation to the fundamental (THD) (maximum of real-time measurement) |
|
|
0x06A5–0x06AE |
1702–1711 |
MicroLogic trip unit |
Total harmonic distortion in relation to the RMS Value (thd) (maximum of real-time measurement) |
|
|
0x06AF–0x06B1 |
1712–1714 |
MicroLogic trip unit |
Voltage to current phase shift (maximum of real-time measurement) |
|
|
0x06B2–0x06B5 |
1715–1718 |
MicroLogic trip unit |
K-Factor (maximum of real-time measurement) |
|
|
0x06B6–0x06BF |
1719–1728 |
MicroLogic trip unit |
Peak factor (maximum of real-time measurement) |
|
|
0x06C4–0x06C6 |
1733–1735 |
MicroLogic trip unit |
Voltage-to-voltage phase shift (maximum of real-time measurement) |
|
|
0x07CF–0x07EA |
2000–2027 |
MicroLogic trip unit |
Energy measurements |
|
|
0x0897–0x08C0 |
2200–2241 |
MicroLogic trip unit |
Demand measurements |
|
|
0x0BB7–0x0BF7 |
3000–3064 |
MicroLogic trip unit |
Time-stamped information |
|
|
0x0CE6–0x0CEF |
3303–3312 |
MicroLogic trip unit |
Identification of the metering manager |
|
|
0x0CF1 |
3314 |
MicroLogic trip unit |
System type |
|
|
0x0CF3 |
3316 |
MicroLogic trip unit |
Power flow sign |
|
|
0x0CF4 |
3317 |
MicroLogic trip unit |
Power reactive sign |
|
|
0x0CF5 |
3318 |
MicroLogic trip unit |
Power factor sign |
|
|
0x0CF6 |
3319 |
MicroLogic trip unit |
Reactive power calculation convention |
|
|
0x0CFB |
3324 |
MicroLogic trip unit |
Energy accumulation mode |
|
|
0x0D16–0x0D1A |
3351–3355 |
MicroLogic trip unit |
Demand time |
|
|
0x0EE7 |
3816 |
MicroLogic trip unit |
Product identification (with metering manager) |
|
|
0x1003–0x105C |
4100–4189 |
MicroLogic trip unit |
Amplitude of voltage harmonic (odd rank) |
|
|
0x105D–0x1098 |
4190–4249 |
MicroLogic trip unit |
Amplitude of current harmonic (odd rank) |
|
|
0x1099–0x10AA |
4250–4267 |
MicroLogic trip unit |
Phase of voltage harmonic (odd rank) |
|
|
0x10F3–0x1102 |
4340–4355 |
MicroLogic trip unit |
Phase of current harmonic (odd rank) |
|
|
0x112F–0x1188 |
4400–4489 |
MicroLogic trip unit |
Amplitude of voltage harmonic (even rank) |
|
|
0x1189–0x11C4 |
4490–4549 |
MicroLogic trip unit |
Amplitude of current harmonic (even rank) |
|
|
0x11C5–0x11D6 |
4550–4567 |
MicroLogic trip unit |
Phase of voltage harmonic (even rank) |
|
|
0x121F–0x122E |
4640–4655 |
MicroLogic trip unit |
Phase of current harmonic (even rank) |
|
|
0x1643–0x1646 |
5700–5703 |
MicroLogic trip unit |
Predefined alarms status |
|
|
0x176F–0x19EA |
6000–6635 |
MicroLogic trip unit |
Analog predefined alarms |
|
|
0x1F3F–0x1FD4 |
8000–8149 |
MicroLogic trip unit |
Command interface |
|
|
0x21FB–0x21FE |
8700–8703 |
MicroLogic trip unit |
Serial number |
|
|
0x2204 |
8709 |
MicroLogic trip unit |
Hardware version |
|
|
0x2205 |
8710 |
MicroLogic trip unit |
Firmware version |
|
|
0x220B |
8716 |
MicroLogic trip unit |
Product identification (with protection manager) |
|
|
0x2223 |
8740 |
MicroLogic trip unit |
Protection type |
|
|
0x2224 |
8741 |
MicroLogic trip unit |
Metering type (A, E, P, H) |
|
|
0x2225 |
8742 |
MicroLogic trip unit |
Long-time rating plug |
|
|
0x222D |
8750 |
MicroLogic trip unit |
Nominal current |
|
|
0x2230 |
8753 |
MicroLogic trip unit |
Neutral protection parameters |
|
|
0x2231–0x223A |
8754–8763 |
MicroLogic trip unit |
Long-time protection |
|
|
0x223B–0x2244 |
8764–8773 |
MicroLogic trip unit |
Short-time protection |
|
|
0x2245–0x224E |
8774–8783 |
MicroLogic trip unit |
Instantaneous protection |
|
|
0x224F–0x2258 |
8784–8793 |
MicroLogic trip unit |
Ground-fault protection |
|
|
0x2259–0x2262 |
8794–8803 |
MicroLogic trip unit |
Earth-leakage (Vigi) protection |
|
|
0x2263–0x2289 |
8804–8842 |
MicroLogic trip unit |
Protection manager measurements |
|
|
0x228A |
8843 |
MicroLogic trip unit |
Battery status |
|
|
0x2298 |
8857 |
MicroLogic trip unit |
M2C/M6C programmable contacts status |
|
|
0x229D–0x229F |
8862–8864 |
MicroLogic trip unit |
Protection status |
|
|
0x22A0–0x22A1 |
8865–8866 |
MicroLogic trip unit |
Time remaining until long-time tripping |
|
|
0x22A7 |
8872 |
MicroLogic trip unit |
Phase rotation |
|
|
0x2327–0x2372 |
9000–9075 |
MicroLogic trip unit |
Time-stamped information |
|
|
0x238B–0x2452 |
9100–9299 |
MicroLogic trip unit |
Trip history |
|
|
0x2583–0x258C |
9604–9613 |
MicroLogic trip unit |
Identification (of the protection manager) |
|
|
0x258D |
9614 |
MicroLogic trip unit |
Language |
|
|
0x258E |
9615 |
MicroLogic trip unit |
Nominal frequency |
|
|
0x258F–0x2590 |
9616–9617 |
MicroLogic trip unit |
Nominal voltage Vn |
|
|
0x2591 |
9618 |
MicroLogic trip unit |
Circuit breaker type |
|
|
0x259C–0x25A5 |
9629–9638 |
MicroLogic trip unit |
Ground-fault alarm |
|
|
0x25A6–0x25AF |
9639–9648 |
MicroLogic trip unit |
Earth-leakage alarm |
|
|
0x25B0–0x25B9 |
9649–9658 |
MicroLogic trip unit |
Current unbalance protection |
|
|
0x25BA–0x25C3 |
9659–9668 |
MicroLogic trip unit |
Maximum current protection on phase A |
|
|
0x25C4–0x25CD |
9669–9678 |
MicroLogic trip unit |
Maximum current protection on phase B |
|
|
0x25CE–0x25D7 |
9679–9688 |
MicroLogic trip unit |
Maximum current protection on phase C |
|
|
0x25D8–0x25E1 |
9689–9698 |
MicroLogic trip unit |
Maximum current protection on neutral |
|
|
0x25E2–0x25EB |
9699–9708 |
MicroLogic trip unit |
Minimum voltage protection |
|
|
0x25EC–0x25F5 |
9709–9718 |
MicroLogic trip unit |
Maximum voltage protection |
|
|
0x25F6–0x25FF |
9719–9728 |
MicroLogic trip unit |
Voltage unbalance protection |
|
|
0x260A–0x2613 |
9739–9748 |
MicroLogic trip unit |
Reverse power protection |
|
|
0x2614–0x261D |
9749–9758 |
MicroLogic trip unit |
Minimum frequency protection |
|
|
0x261E–0x2627 |
9759–9768 |
MicroLogic trip unit |
Maximum frequency protection |
|
|
0x2628–0x2631 |
9769–9778 |
MicroLogic trip unit |
Phase rotation alarm |
|
|
0x2632–0x263B |
9779–9788 |
MicroLogic trip unit |
Load shedding and reconnection based on current |
|
|
0x263C–0x2645 |
9789–9798 |
MicroLogic trip unit |
Load shedding and reconnection based on power |
|
|
0x2647 |
9800 |
MicroLogic trip unit |
Remote configuration status |
|
|
0x2648–0x2671 |
9801–9842 |
MicroLogic trip unit |
Configuration of the M2C/M6C programmable contacts |
|
|
0x2672 |
9843 |
MicroLogic trip unit |
Type of M2C/M6C programmable contacts |
|
|
0x2675–0x267C |
9846–9853 |
MicroLogic trip unit |
Circuit breaker characteristics |
|
|
0x27FF–0x2826 |
10240–10279 |
IFE interface |
IP network parameters |
|
|
0x2DFF–0x2E06 |
11776–11783 |
IFM interface |
Firmware version |
|
|
0x2DFF–0x2E06 |
11776–11783 |
IFE interface |
Firmware version |
|
|
0x2E07–0x2E0C |
11784–11789 |
IFM interface |
Serial number |
|
|
0x2E07–0x2E0C |
11784–11789 |
IFE interface |
Hardware version |
|
|
0x2E18–0x2E2E |
11801–11823 |
IFM interface |
IMU name |
|
|
0x2E18–0x2E2E |
11801–11823 |
IFE interface |
IMU name |
|
|
0x2E45–0x2E5B |
11846–11868 |
IFM interface |
IMU location |
|
|
0x2E45–0x2E5B |
11846–11868 |
IFE interface |
IMU location |
|
|
0x2E72 |
11891 |
IFM interface |
Modbus locking pad position |
|
|
0x2E72 |
11891 |
IFE interface |
Locking pad position |
|
|
0x2E73–0x2E7A |
11892–11899 |
IFE interface |
Current date and time |
|
|
0x2E7C |
11901 |
IFM interface |
Product identification |
|
|
0x2E7C |
11901 |
IFE interface |
Product identification |
|
|
0x2E7D–0x02E7F |
11902–11904 |
IFE interface |
IFE interface MAC address |
|
|
0x2E89–0x2E8C |
11914–11917 |
IFE interface |
Manufacturing date and time |
|
|
0x2E91–0x02E96 |
11922–11931 |
IFE interface |
Serial number |
|
|
0x2EDF–0x2F84 |
12000–12165 |
IFM interface |
Legacy dataset |
|
|
0x2EDF–0x2F84 |
12000–12165 |
IFE interface |
Legacy dataset |
|
|
0x306E |
12399 |
IFM interface |
Auto-Speed sensing state |
|
|
0x306F |
12400 |
IFM interface |
IFM interface Modbus address |
|
|
0x306F–0x3072 |
12400–12403 |
IFE interface |
IFE interface Modbus parameters |
|
|
0x3070 |
12401 |
IFM interface |
Modbus parity |
|
|
0x3071 |
12402 |
IFM interface |
Modbus Baud rate |
|
|
0x3072 |
12403 |
IFM interface |
Number of stop bits |
|
|
0x35FF–0x3668 |
13824–13929 |
IO module |
Analog input of IO 1 |
|
|
0x3669–0x3848 |
13930–14409 |
IO module |
Digital input of IO 1 |
|
|
0x3849–0x38FC |
14410–14589 |
IO module |
Digital output of IO 1 |
|
|
0x38FD–0x3902 |
14590–14595 |
IO module |
Hardware setting of IO 1 |
|
|
0x3905–0x3908 |
14598–14601 |
IO module |
Digital input and output status of IO 1 |
|
|
0x392F–0x3982 |
14640–14723 |
IO module |
IO 1 identification |
|
|
0x3989–0x39A4 |
14730–14759 |
IO module |
Alarm status of IO 1 |
|
|
0x3BC3–0x3BE0 |
15300–15329 |
IO module |
Cradle management of IO 1 |
|
|
0x3BE1–0x3BFE |
15330–15359 |
IO module |
Drawer management of IO 1 |
|
|
0x3C27–3C30 |
15400–15409 |
IO module |
Light control of IO 1 |
|
|
0x3C31–3EEC |
15410–16109 |
IO module |
Load control of IO 1 |
|
|
0x41B8–0x4220 |
16824–16929 |
IO module |
Analog input of IO 2 |
|
|
0x4221–0x4400 |
16930–17409 |
IO module |
Digital input of IO 2 |
|
|
0x4401–0x44B4 |
17410–17589 |
IO module |
Digital output of IO 2 |
|
|
0x44B5–0x44BA |
17590–17595 |
IO module |
Hardware setting of IO 2 |
|
|
0x44BD–0x44C0 |
17598–17601 |
IO module |
Digital input and output status of IO 2 |
|
|
0x44E7–0x453A |
17640–17723 |
IO module |
IO 2 identification |
|
|
0x4541–0x455E |
17730–17759 |
IO module |
Alarm status of IO 2 |
|
|
0x477B–0x4798 |
18300–18329 |
IO module |
Cradle management of IO 2 |
|
|
0x4799–0x47B6 |
18330–18359 |
IO module |
Drawer management of IO 2 |
|
|
0x749C |
29853 |
MicroLogic trip unit |
Rate of wear counter |
|
|
0x74B7–0x74BE |
29880–29887 |
MicroLogic trip unit |
Load profile counters |
|
|
0x7CFF–0x7E4E |
32000–32341 |
IFE interface |
Standard dataset |