Minimum PowerPact B Clearance with Interphase Barriers

The minimum clearance distances required around circuit breakers equipped with interphase barriers are shown below.

2P

3P/4P

With painted sheet metal:

  • A1: 0 mm (0 in.)

  • A2: 0 mm (0 in.)

  • B: 0 mm (0 in.)

With bare sheet metal:

  • A1: 0 mm (0 in.)

  • A2: 0 mm (0 in.)

  • B: 5 mm (0.19 in.)

With painted sheet metal:

  • A1: 0 mm (0 in.)

  • A2: 0 mm (0 in.)

  • B: 0 mm (0 in.)

With bare sheet metal:

  • A1: 0 mm (0 in.)

  • A2: 0 mm (0 in.)

  • B: 5 mm (0.19 in.)