DOCA0095EN

Vibration

Circuit breakers are designed to withstand vibration. They meet the IEC60068-2-6 standard for vibration:

  • 2 Hz to 25 Hz with an amplitude of +/- 1.6 mm (+/- 0.06 in.)

  • 25 Hz to 100 Hz at a constant acceleration of +/- 4 g

Conformity tests are carried out in accordance with the IEC60068-2-6 standard, at the levels of severity required by the merchant shipping regulatory bodies (mainly IACS, Veritas, and Lloyd’s).

Excessive vibration can cause tripping, breaks in connections, or damage to mechanical parts.

QR code for this page