Examples of Using Alarms
Presentation
Use EcoStruxure Power Commission software to select:
-
Quantity to be monitored
-
Alarm function settings
Overvalue Condition
Alarms on overvalue condition are dedicated to monitoring:
-
Overvoltages
-
Phase unbalance (MicroLogic 6 E-M)
-
Overcurrents
-
Overfrequencies
-
Current unbalances
-
Power overruns
-
Total harmonic distortion (THD) overruns
The value of the drop-out threshold must always be lower than the pickup threshold.
Undervalue Condition
The value of the drop-out threshold must always be higher than the pickup threshold.
Alarms on undervalue condition are dedicated to supervision of:
-
Undervoltages
-
Underloads (MicroLogic 6 E-M)
-
Underfrequencies
Alarms on Equality Condition
The measurements associated with alarms on an equality condition correspond to a load state:
-
Operating quadrant
-
Leading or lagging reactive power