Protection Function Screens
MicroLogic 5 LSI: Protection Function Readout Screens
Mode |
Screen description |
Unit |
Arrows |
---|---|---|---|
Ir: Long-time protection pickup value setting for the phases |
A |
The up arrow indicates the Ir function. |
|
Ir(IN): Long-time protection pickup value setting for the neutral (4-pole or 3-pole trip unit with ENCT option and neutral protection active) |
A |
The up arrow indicates the Ir function. |
|
tr: Long-time protection time delay value (at 6 Ir) |
s |
The up arrow indicates the tr function. |
|
Isd: Short-time protection pickup value setting for the phases |
A |
The up arrow indicates the Isd function. |
|
Isd(IN): Short-time protection pickup value for the neutral (4-pole or 3-pole trip unit with ENCT option and neutral protection active) |
A |
The up arrow indicates the Isd function. |
|
tsd: Short-time protection time delay value The time delay is associated with the I2t inverse time curve protection function:
|
s |
The up arrow indicates the tsd function. |
|
Ii: Instantaneous protection pickup value setting for the phases and for the neutral (4-pole or 3-pole trip unit with ENCT option and neutral protection active) |
A |
The up arrow indicates the Ii function. |
|
Neutral status (3-pole trip unit with ENCT option):
|
– |
– |
MicroLogic 5 LSI: Protection Function Setting Screens
Mode |
Screen description |
Unit |
Arrows |
---|---|---|---|
Ir: Long-time protection pickup setting for the phases Preset by a dial |
A |
The up arrow indicates the Ir function. |
|
tr: Long-time protection time delay setting |
s |
The up arrow indicates the tr function. |
|
Isd: Short-time protection pickup setting for the phases Preset by a dial |
Isd/Ir |
The up arrow indicates the Isd function. |
|
tsd: Short-time protection time delay setting Activation of the I2t inverse time curve short-time protection
|
s |
The up arrow indicates the tsd function. |
|
IN: Protection pickup setting for the neutral (4-pole or 3-pole trip unit with ENCT option and neutral protection active) |
IN/Ir |
The down arrow indicates the neutral. |
|
Ii: Instantaneous protection pickup value setting for the phases and for the neutral (4-pole or 3-pole trip unit with ENCT option and active neutral protection) |
Ii/In |
The up arrow indicates the Ii function. |
|
Activation of neutral status (3-pole trip unit with ENCT option)
|
– |
– |
MicroLogic 6 LSIG: Protection Function Readout Screens
Mode |
Screen description |
Unit |
Arrows |
---|---|---|---|
Ir: Long-time protection pickup value for the phases |
A |
The up arrow indicates the Ir function. |
|
Ir(IN): Long-time protection pickup value for the neutral (4-pole or 3-pole trip unit with ENCT option and neutral protection active) |
A |
The up arrow indicates the Ir function. |
|
tr: Long-time protection time delay value (at 6 Ir) |
s |
The up arrow indicates the tr function. |
|
Isd: Short-time protection pickup value for the phases |
A |
The up arrow indicates the Isd function. |
|
Isd(IN): Short-time protection pickup value for the neutral (4-pole or 3-pole trip unit with ENCT option and neutral protection active) |
A |
The up arrow indicates the Isd function. |
|
tsd: Short-time protection time delay value The time delay is associated with the I2t inverse time curve protection function:
|
s |
The up arrow indicates the tsd function. |
|
Ii: Instantaneous protection pickup value setting for the phases and the neutral (4-pole or 3-pole trip unit with ENCT option and neutral protection active) |
A |
The up arrow indicates the Ii function. |
|
Ig: Ground-fault protection pickup value |
A |
The up arrow indicates the Ig function. |
|
tg: Ground-fault protection time delay value The time delay is associated with the I2t inverse time curve protection function:
|
s |
The up arrow indicates the tg function. |
|
Neutral status (3-pole trip unit with ENCT option):
|
– |
– |
MicroLogic 6 LSIG: Protection Function Setting Screens
Mode |
Screen description |
Unit |
Arrows |
---|---|---|---|
Ir: Long-time protection pickup setting for the phases Preset by a dial |
A |
The up arrow indicates the Ir function. |
|
tr: Long-time protection time delay setting |
s |
The up arrow indicates the tr function. |
|
Isd: Short-time protection pickup setting for the phases |
Isd/Ir |
The up arrow indicates the Isd
function. |
|
tsd: Short-time protection time delay setting Activation of the I2t inverse time curve short-time protection
|
s |
The up arrow indicates the tsd function. |
|
IN: Protection pickup setting for the neutral (4-pole or 3-pole trip unit with ENCT option and neutral protection active) |
IN/Ir |
The down arrow indicates the neutral. |
|
Ii: Instantaneous protection pickup value for the phases and for the neutral (4-pole or 3-pole trip unit with ENCT option and neutral protection active) |
Ii/In |
The up arrow indicates the Ii function. |
|
Ig: Ground-fault protection pickup setting Preset by a dial |
Ig/In |
The up arrow indicates the Ig function. |
|
tg: Ground-fault protection time delay setting Activation of the I2t inverse time curve ground-fault protection
|
s |
The up arrow indicates the tg function. |
|
Activation of neutral status (3-pole trip unit with ENCT option)
|
– |
– |
MicroLogic 6 E-M LSIG: Protection Function Readout Screens
Mode |
Screen description |
Unit |
Arrows |
---|---|---|---|
Ir: Long-time protection pickup value for the phases |
A |
The up arrow indicates the Ir function. |
|
Cl: Long-time protection trip class (value at 7.2 Ir) |
s |
The up arrow indicates the Cl function. |
|
Y: Type of ventilation
|
– |
The up arrow indicates the Y function. |
|
Isd: Short-time protection pickup value for the phases |
A |
The up arrow indicates the Isd function. |
|
Iunbal: Phase unbalance protection pickup value (expressed as a percentage of the average motor current) |
% |
The up arrow indicates the Iunbal
function. |
|
tunbal: Phase unbalance protection time delay value |
s |
The up arrow indicates the tunbal function. |
|
Ijam: Jam motor protection pickup value (if OFF is indicated, jam motor protection is not active) |
A |
The up arrow indicates the Ijam
function. |
|
tjam: Jam motor protection time delay value |
s |
The up arrow indicates the tjam function. |
|
Ig: Ground-fault protection pickup value |
A |
The up arrow indicates the Ig function. |
|
tg: Ground-fault protection time delay value OFF is always indicated: the I2t inverse time curve protection function is not available on MicroLogic 6 E-M trip units. |
s |
The up arrow indicates the tg function. |
MicroLogic 6 E-M LSIG: Protection Function Setting Screens
Mode |
Screen description |
Unit |
Arrows |
---|---|---|---|
Ir: Long-time protection pickup setting for the 3 phases Preset by a dial |
A |
The up arrow indicates the Ir function. |
|
Cl: Selection of the long-time protection trip class |
s |
The up arrow indicates the Cl function. |
|
Y: Choice of type of ventilation
|
– |
The up arrow indicates the Y function. |
|
Isd: Short-time protection pickup setting for the 3 phases |
Isd/Ir |
The up arrow indicates the Isd function. |
|
Iunbal: Phase unbalance protection pickup setting (expressed as a percentage of the average motor current) |
% |
The up arrow indicates the Iunbal
function. |
|
tunbal: Phase unbalance protection time delay setting |
s |
The up arrow indicates the tunbal function. |
|
Ijam: Jam motor protection pickup setting (if OFF is indicated, jam motor protection is not active) |
Ijam/Ir |
The up arrow indicates the Ijam
function. |
|
tjam: Jam motor protection time delay setting |
s |
The up arrow indicates the tjam function. |
|
Ig: Ground-fault protection pickup setting Preset by a dial |
Ig/In |
The up arrow indicates the Ig function. |
|
tg: Ground-fault protection time delay setting |
s |
The up arrow indicates the tg function. |
MicroLogic 7 LSIV: Protection Function Readout Screens
Mode |
Screen description |
Unit |
Arrows |
---|---|---|---|
Ir: Long-time protection pickup value for the phases |
A |
The up arrow indicates the Ir function. |
|
Ir(IN): Long-time protection pickup value for the neutral (4-pole and neutral protection active) |
A |
The up arrow indicates the Ir function. |
|
tr: Long-time protection time delay value (at 6 Ir) |
s |
The up arrow indicates the tr function. |
|
Isd: Short-time protection pickup value for the phases |
A |
The up arrow indicates the Isd function. |
|
Isd(IN): Short-time protection pickup value for the neutral (4-pole and neutral protection active) |
A |
The up arrow indicates the Isd function. |
|
tsd: Short-time protection time delay value The time delay is associated with the I2t inverse time curve protection function:
|
s |
The up arrow indicates the tsd function. |
|
Ii: Instantaneous protection pickup value setting for the phases and the neutral (4-pole and neutral protection active) |
A |
The up arrow indicates the Ii function. |
|
IΔn: Earth-leakage protection pickup value |
A |
The up arrow indicates the IΔn function. |
|
Δt: Earth-leakage protection time delay value |
s |
The up arrow indicates the Δt function. |
|
Neutral status:
|
– |
– |
MicroLogic 7 LSIV: Protection Function Setting Screens
Mode |
Screen description |
Unit |
Arrows |
---|---|---|---|
Ir: Long-time protection pickup setting for the phases Preset by a dial |
A |
The up arrow indicates the Ir function. |
|
tr: Long-time protection time delay setting |
s |
The up arrow indicates the tr function. |
|
Isd: Short-time protection pickup setting for the phases |
Isd/Ir |
The up arrow indicates the Isd function. |
|
tsd: Short-time protection time delay setting Activation of the I2t inverse time curve short-time protection
|
s |
The up arrow indicates the tsd function. |
|
IN: Protection pickup setting for the neutral (4-pole and neutral protection active) |
IN/Ir |
The down arrow indicates the neutral. |
|
Ii: Instantaneous protection pickup value for the phases and for the neutral (4-pole and neutral protection active) |
Ii/In |
The up arrow indicates the Ii function. |
|
IΔn: Earth-leakage protection pickup setting Preset by a dial NOTE: The present and previous earth-leakage protection
settings are recorded in a history
|
A |
The up arrow indicates the IΔn function. |
|
Δt: Earth-leakage protection time delay setting |
s |
The up arrow indicates the Δt function. |
|
Activation of neutral status
|
– |
– |