History and Time-Stamped Information
History
MicroLogic trip units generate the following types of history:
-
History of alarms associated with measurements (the last 10 alarms are recorded)
-
History of trips (the last 18 trips are recorded)
-
History of maintenance operations (the last 10 operations are recorded)
-
History of earth-leakage protection settings (present and previous settings recorded)
-
History of earth-leakage protection tests. Tests with trip and tests without trip are recorded in the same history (the last 10 operations are recorded)
Availability
Consult the history:
-
With EcoStruxure Power Commission software
-
On a remote controller using the communication network
Time-Stamped Information
Time-stamped information displays dates for important information such as previous protection settings and minimum/maximum current, voltage, and network frequency values.
The table of time-stamped information describes:
-
The previous protection configurations and corresponding dates
-
The minimum and maximum voltage measurement values and corresponding dates
-
The maximum current measurement values and corresponding dates
-
The minimum and maximum network frequencies and corresponding dates
The time when the minimum and maximum values were reset is also available.