990-5992E-001

Specifications

Specifications for 400 V Systems

Input Specifications

  60 kVA 80 kVA 100 kVA
Voltage (V) 380 400 415 380 400 415 380 400 415
Connections L1, L2, L3, N, PE
Input voltage range (V) 342–477 at full load*
Frequency range (Hz) 40–70
Nominal input current (A) 96 91 88 128 122 117 160 152 146
Maximum input current (A) 109 104 100 154 146 141 186 177 170
Input current limitation (A) 155 206 258
Total harmonic distortion (THDI) <3% for linear loads
Input power factor > 0.99
Maximum short circuit rating Icc=10 kA
Protection Fuse
Ramp-in 7 seconds

Bypass Specifications

  60 kVA 80 kVA 100 kVA
Voltage (V) 380 400 415 380 400 415 380 400 415
Connections L1, L2, L3, N, PE
Overload capacity 110% for 60 minutes
130% for 10 minutes
130–150% for 1 minute
Minimum bypass voltage (V) 266 280 291 266 280 291 266 280 291
Maximum bypass voltage (V) 475 480 477 475 480 477 475 480 477
Frequency (Hz) 50 or 60

Frequency range (%)

±1, ±2, ±4, ±5, ±10. Default is ±10 (user selectable).
Nominal bypass current (A) 91 87 83 122 115 111 152 144 139
Maximum short circuit rating Icw=10 kA

Output Specifications

  60 kVA 80 kVA 100 kVA
Voltage (V) 380 400 415 380 400 415 380 400 415
Connections L1, L2, L3, N, PE
Overload capacity* 110% for 60 minutes
125% for 10 minutes
150% for 1 minute
Output voltage regulation ± 1%
Dynamic load response 20 milliseconds
Output power factor 1.0
Nominal output current (A) 91 87 83 122 115 111 152 144 139
Total harmonic distortion (THDU) <3% at 100% linear load
<5% at 100% non-linear load
Output frequency (Hz) 50 or 60
Slew rate (Hz/sec) Programmable: 0.5 to 2.0. Default is 0.5
Output performance classification (according to IEC/ EN62040-3) VFI-SS–111
Load power factor 0.5 leading to 0.5 lagging without derating
Output short circuit current 210 A/200 ms 330 A/200 ms 330 A/200 ms

Battery Specifications

  60 kVA 80 kVA 100 kVA
Charging power in % of output power 1–20% 1–30% 1–24%
Maximum charging power (W) 12000 24000 24000
Nominal battery voltage (32–50 blocks*) (VDC) ± 192 to ± 300
Nominal float voltage (32–50 blocks*) (VDC) ± 215.5 to ± 337.5
End of discharge voltage (32–50 blocks) (VDC) ± 153.6 to ± 240
Battery current at full load and nominal battery voltage (36–50 blocks) (A) 147–105 196–140 245–175
Battery current at full load and minimum battery voltage (36–50 blocks) (A) 185–132 246–176 308–221
Temperature compensation (per cell)* Programmable from 0–7 mV. Default is 0 mV
Ripple current < 5% C10

Recommended Upstream Protection

NOTE: For local directives which require 4–pole circuit breakers: If neutral conductor is expected to carry a high current, due to line-neutral non-linear load, the circuit breaker must be rated according to expected neutral current.
  60 kW 80 kW 100 kW
  Input Bypass Input Bypass Input Bypass
Breaker type NSX160F 36kA AC 3P3D 125A TMD C16F3TM125 NSX100F 36kA AC 3P3D 100A TMD C10F3TM100 NSX160F 36kA AC 3P3D 160A TMD C16F3TM160 NSX160F 36kA AC 3P3D 160A TMD C16F3TM160 NSX250F 36kA AC 3P3D 200A TMD C25F3TM200 NSX160F 36kA AC 3P3D 160A TMD C16F3TM160
In setting 125 100 160 160 200 160
Ir setting 125 100 160 144 200 160
Im setting 1250 (fixed) 800 (fixed) 1250 (fixed) 1250 (fixed) 1000 1250 (fixed)

Recommended Cable Sizes

DANGER
hazard of electric shock, explosion, or arc flash
All wiring must comply with all applicable national and/or electrical codes. The maximum allowable cable size is 70 mm².
Failure to follow these instructions will result in death or serious injury.

Cable sizes in this manual are based on table B.52.5 of IEC 60364–5–52 with the following assertions:

  • 90 °C conductors

  • An ambient temperature of 30 °C

  • Use of copper conductors

  • Installation method C

PE size is based on table 54.2 of IEC 60364–4–54.

If the ambient temperature is greater than 30 °C, larger conductors are to be used in accordance with the correction factors of the IEC.

60 kVA UPS

  Cable Size per Phase (mm²) Neutral* Cable Size (mm²) PE Cable Size (mm²)
Input 35 2x25 16
Bypass 25 16
Output 25 2x25 16
Battery 50 50 25

80 kVA UPS

  Cable Size per Phase (mm²) Neutral* Cable Size (mm²) PE Cable Size (mm²)
Input 50 2x50 25
Bypass 50 25
Output 50 2x50 25
Battery 2x50 2x50 50

100 kVA UPS

  Cable Size per Phase (mm²) Neutral* Cable Size (mm²) PE Cable Size (mm²)
Input 70 2x70 35
Bypass 70 35
Output 70 2x70 35
Battery 2x70 2x70 70

Heat Dissipation

  60 kVA 80 kVA 100 kVA
  W BTU/hr W BTU/hr W BTU/hr
Normal mode 3084 10523 4296 14659 5500 18767
Battery mode 2958 10093 4352 14850 5520 18835
ECO mode 540 1843 696 2375 1020 3480

Specifications for 208 V Systems

Input Specifications

  50 kVA
Voltage (V) 200 208 220
Connections L1, L2, L3, N, PE
Input voltage range (V) 180–272 at full load*
Frequency range (Hz) 40–70
Nominal input current (A) 159 152 143
Maximum input current (A) 170 163 154
Input current limitation (A) 254
Total harmonic distortion (THDI) <3% for linear loads
Input power factor > 0.99
Maximum short circuit rating Icc=10 kA
Protection Fuse
Ramp-in 12 seconds

Bypass Specifications

  50 kVA
Voltage (V) 200 208 220
Connections L1, L2, L3, N, PE
Overload capacity 110% for 60 minutes
130% for 10 minutes
130–150% for 1 minute
Minimum bypass voltage (V) 140 146 154
Maximum bypass voltage (V) 250 260 275
Frequency (Hz) 50 or 60

Frequency range (%)

±1, ±2, ±4, ±5, ±10. Default is ±10 (user selectable).
Nominal bypass current (A) 147 141 133
Maximum short circuit rating Icw=10 kA

Output Specifications

  50 kVA
Voltage (V) 200 208 220
Connections L1, L2, L3, N, PE
Overload capacity* 110% for 60 minutes
125% for 10 minutes
150% for 1 minute
Output voltage regulation ± 1%
Dynamic load response 20 milliseconds
Output power factor 1.0
Nominal output current (A) 144 139 131
Total harmonic distortion (THDU) <3% at 100% linear load
<5% at 100% non-linear load
Output frequency (Hz) 50 or 60
Slew rate (Hz/sec) Programmable: 0.5 to 2.0. Default is 0.5
Output performance classification (according to IEC/ EN62040-3) VFI-SS–111
Load power factor 0.5 leading to 0.5 lagging without derating
Output short circuit current 330 A/200 ms

Battery Specifications

  50 kVA
Charging power in % of output power 1-38.4%
Maximum charging power (W) 19200
Nominal battery voltage (32-40 blocks) (VDC) ± 192 to ± 240
Nominal float voltage (32-40 blocks) (VDC) ± 215.5 to ± 270
End of discharge voltage (32-40 blocks) (VDC) ± 153.6 to ± 192
Battery current at full load and nominal battery voltage (32-40 blocks) (A) 140-112
Battery current at full load and minimum battery voltage (32-40 blocks) (A) 175-140
Temperature compensation (per cell)* Programmable from 0-7 mV. Default is 0 mV
Ripple current < 5% C10

Recommended Upstream Protection

NOTE: For local directives which require 4–pole circuit breakers: If neutral conductor is expected to carry a high current, due to line-neutral non-linear load, the circuit breaker must be rated according to expected neutral current.
  50 kW
  Input Bypass
Breaker type NSX250F 36kA AC 3P3D 200A TMD C25F3TM200 NSX160F 36kA AC 3P3D 160A TMD C16F3TM160
In setting 200 160
Ir setting 200 160
Im setting 1000 1250 (fixed)

Recommended Cable Sizes

DANGER
hazard of electric shock, explosion, or arc flash
All wiring must comply with all applicable national and/or electrical codes. The maximum allowable cable size is 70 mm².
Failure to follow these instructions will result in death or serious injury.

Cable sizes in this manual are based on table B.52.5 of IEC 60364–5–52 with the following assertions:

  • 90 °C conductors

  • An ambient temperature of 30 °C

  • Use of copper conductors

  • Installation method C

PE size is based on table 54.2 of IEC 60364–4–54.

If the ambient temperature is greater than 30 °C, larger conductors are to be used in accordance with the correction factors of the IEC.

50 kVA UPS

  Cable Size per Phase (mm²) Neutral* Cable Size (mm²) PE Cable Size (mm²)
Input 70 2x70 35
Bypass 70 35
Output 70 2x70 35
Battery 70 70 35

Heat Dissipation

50 kVA

  W BTU/hr
Normal mode 4648 15859
Battery mode 3528 12038
ECO mode 890 3037

Recommended Bolts and Cable Lugs

Cable Size (mm²) Bolt Size Cable Lug Type
16 M8 KST TLK16-8
25 M8 KST TLK25-8
35 M8 KST TLK35-8
50 M8 KST TLK50-8
70 M8 KST TL70-8

Torque Specifications

Bolt Size Torque
M8 17.5 Nm

Requirements for a Third Party Battery Solution

Battery breaker boxes from Schneider Electric are recommended for the battery interface. Please contact Schneider Electric for more information.

Third Party Battery Breaker Requirements

DANGER
Hazard of electric shock, explosion, or arc flash
All selected battery breakers must be equipped with instantaneous trip functionality with an undervoltage release coil or a shunt trip release coil.
Failure to follow these instructions will result in death or serious injury.
NOTE: There are more factors to consider when selecting a battery breaker than the requirements listed below. Please contact Schneider Electric for more information.

Design Requirements for Battery Breaker

Battery breaker rated DC voltage > Normal battery voltage The normal voltage of the battery configuration is defined as the highest nominal occurring battery voltage. This can be equivalent to the float voltage which may be defined as number of battery blocks x number of cells x cell float voltage.
Battery breaker rated DC current > Rated discharge battery current This current is controlled by the UPS and must include maximum discharge current. This will typically be the current at the end of discharge (minimum operation DC voltage or in overload condition or a combination).
DC landings Three DC landings (+, -, N) for DC cables are required.
AUX switches for monitoring One AUX switch must be installed in each battery breaker and connected to the UPS. The UPS can monitor one battery breaker.
Short-circuit breaking capability The short-circuit breaking capability must be higher than the short-circuit DC current of the (largest) battery configuration.
Minimum trip current The minimum short-circuit current to trip the battery breaker must match the (smallest) battery configuration, to make the breaker trip in case of a short circuit, up to the end of its life time.

Guidance for Organizing Battery Cables

NOTE: For 3rd party batteries, use only high rate batteries for UPS applications.
NOTE: When the battery bank is placed remotely, the organizing of the cables is important to reduce voltage drop and inductance. The distance between the battery bank and the UPS must not exceed 200 m (656 ft). Contact Schneider Electric for installations with a longer distance.
NOTE: To minimize the risk of electromagnetic radiation, it is highly recommended to follow the below guidance and to use grounded metallic tray supports.
Cable Length
<30 m Not recommended Acceptable Recommended Recommended
31–75 m Not recommended Not recommended Acceptable Recommended
76–150 m Not recommended Not recommended Acceptable Recommended
151–200 m Not recommended Not recommended Not recommended Recommended

Clearance

NOTE: Clearance dimensions are published for airflow and service access only. Consult with the local safety codes and standards for additional requirements in your local area.

Option A

NOTE: If the UPS is installed without side access, the length of the cables connected to the UPS must allow for rolling out the UPS.

Option B

Environmental

  Operation Storage
Temperature 0 °C to 40 °C -15 °C to 40 °C for systems with batteries
-25 °C to 55 °C for systems without batteries
Relative humidity 0–95% non-condensing
Elevation derating according to
IEC 62040–3
Power derating factor:
0–1500 m: 1.000
1500–2000 m: 0.975
< 15000 m above sea level (or in an environment with equivalent air pressure)
Audible noise <65 dBA at full load and an ambient temperature of 30 °C*  
Protection class IP20 (dust filter as standard)
Color RAL 9003

UPS Weights and Dimensions

UPS Weight kg Height mm Width mm Depth mm
60 kVA 400 V 109 915 360 850
80 kVA 400 V 140 915 360 850
100 kVA 400 V/50 kVA 208 V 145 915 360 850

UPS Shipping Weights and Dimensions

UPS Weight kg Height mm Width mm Depth mm
60 kVA 400 V 133 1140 475 965
80 kVA 400 V 164 1140 475 965
100 kVA 400 V/50 kVA 208 V 169 1140 475 965

Compliance

Safety

IEC 62040-1:2017, Edition 2.0, Uninterruptible power systems (UPS) – Part 1: Safety requirements

IEC 62040-1: 2008-6, 1st edition, Uninterruptible Power Systems (UPS) – Part 1: General and safety requirements for UPS

IEC 62040-1:2013-01, 1st edition amendment 1

EMC/EMI/RFI

IEC 62040-2:2016, Edition 3.0, Uninterruptible power systems (UPS) – Part 2: Electromagnetic compatibility (EMC) requirements.

IEC 62040-2:2005-10, 2nd edition, Uninterruptible Power Systems (UPS) – Part 2: Electromagnetic compatibility (EMC) requirements

Performance

IEC 62040-3: 2011-03, 2nd edition Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the performance and test requirements

Markings

CE, RCM, EAC, WEEE, UKCA

Transportation

ISTA 2B

Pollution degree

2

Overvoltage category

III

Earthing system

TN, TT, or IT

QR code for this page

Was this helpful?