Indication LEDs
The TS trip system and circuit breaker status are indicated locally by a combination of LEDs:
-
The status bar
-
The service LED
-
The ready LED
-
The trip cause and alarm LEDs
The indication given by the LEDs depends on how the TS trip system is supplied by:
-
The internal current transformers (CT)
-
The internal battery
Indication LEDs with TS Trip System Supplied by Current Transformers
The TS trip system is supplied by the internal current transformers (CT) when the EasyPact MVS circuit breaker is closed. If the load current is more than 0.2 In, the local indication is provided as indicated in following table.
Description |
Indication LEDs |
|
---|---|---|
No action required |
Ready LED: blinking green Status bar: green on Service LED: off All trip cause LEDs: off |
|
Major or minor internal malfunction detected, corrective action to be planned. |
Ready LED: blinking green Status bar: orange on Service LED: red on All trip cause LEDs: off |
|
Overload pre-alarm: |
Ready LED: blinking green Status bar: orange on Service LED: off L trip cause LED: red on Other trip cause LEDs: off |
|
Ground-fault alarm: |
Ready LED: blinking green Status bar: orange on Service LED: off G trip cause LED: red on Other trip cause LEDs: off |
|
Overload alarm: |
Ready LED: blinking green Status bar: red on Service LED: off L trip cause LED: red on Other trip cause LEDs: off |
Trip Indication LEDs After a Trip
When the circuit breaker is tripped, the trip cause is indicated by the trip cause LEDs and the status bar. The trip cause LEDs and the status bar are powered by the internal battery.
When powered by the internal battery, the trip cause and alarm LEDs are turned off after 2 hours.
After 2 hours, use the button to switch on the indication LEDs.
Description |
Indication LEDs |
|
---|---|---|
Trip on long-time protection (L) |
Ready LED: off Status bar: blinking red Service LED: off L trip cause LED: blinking red Other trip cause LEDs: off |
|
Trip on short-time protection (S) |
Ready LED: off Status bar: blinking red Service LED: off S trip cause LED: blinking red Other trip cause LEDs: off |
|
Trip on instantaneous protection (I) |
Ready LED: off Status bar: blinking red Service LED: off I trip cause LED: blinking red Other trip cause LEDs: off |
|
Trip on ground-fault protection (G) |
Ready LED: off Status bar: blinking red Service LED: off G trip cause LED: blinking red Other trip cause LEDs: off |
|
Major internal malfunction detected |
Ready LED: off Status bar: blinking red Service LED: blinking red All trip cause LEDs: off |