DOCA0299EN-01

Indication LEDs

The TS trip system and circuit breaker status are indicated locally by a combination of LEDs:

  • The status bar

  • The service LED

  • The ready LED

  • The trip cause and alarm LEDs

The indication given by the LEDs depends on how the TS trip system is supplied by:

  • The internal current transformers (CT)

  • The internal battery

Indication LEDs with TS Trip System Supplied by Current Transformers

The TS trip system is supplied by the internal current transformers (CT) when the EasyPact MVS circuit breaker is closed. If the load current is more than 0.2 In, the local indication is provided as indicated in following table.

Description

Indication LEDs

No action required

Ready LED: blinking green

Status bar: green on

Service LED: off

All trip cause LEDs: off

Major or minor internal malfunction detected, corrective action to be planned.

Ready LED: blinking green

Status bar: orange on

Service LED: red on

All trip cause LEDs: off

Overload pre-alarm:
90% Ir < Phase current < 105% Ir

Ready LED: blinking green

Status bar: orange on

Service LED: off

L trip cause LED: red on

Other trip cause LEDs: off

Ground-fault alarm:
Ig current ≥ 80 % Ig

Ready LED: blinking green

Status bar: orange on

Service LED: off

G trip cause LED: red on

Other trip cause LEDs: off

Overload alarm:
current ≥ 105 % Ir

Ready LED: blinking green

Status bar: red on

Service LED: off

L trip cause LED: red on

Other trip cause LEDs: off

Trip Indication LEDs After a Trip

When the circuit breaker is tripped, the trip cause is indicated by the trip cause LEDs and the status bar. The trip cause LEDs and the status bar are powered by the internal battery.

When powered by the internal battery, the trip cause and alarm LEDs are turned off after 2 hours.

After 2 hours, use the button to switch on the indication LEDs.

Description

Indication LEDs

Trip on long-time protection (L)

Ready LED: off

Status bar: blinking red

Service LED: off

L trip cause LED: blinking red

Other trip cause LEDs: off

Trip on short-time protection (S)

Ready LED: off

Status bar: blinking red

Service LED: off

S trip cause LED: blinking red

Other trip cause LEDs: off

Trip on instantaneous protection (I)

Ready LED: off

Status bar: blinking red

Service LED: off

I trip cause LED: blinking red

Other trip cause LEDs: off

Trip on ground-fault protection (G)

Ready LED: off

Status bar: blinking red

Service LED: off

G trip cause LED: blinking red

Other trip cause LEDs: off

Major internal malfunction detected

Ready LED: off

Status bar: blinking red

Service LED: blinking red

All trip cause LEDs: off

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.