Specifications
Specifications for 50 kW UPS
Voltage (V) | 380 | 400 | 415 | |
---|---|---|---|---|
Input | Connections | L1, L2, L3,
N, PE (single mains) L1, L2, L3, PE (dual mains)* |
||
Input voltage range at full load (V) | 304-456* | 320-460 | 332-477 | |
Frequency (Hz) | 40-70 | |||
Nominal input current (A) |
80 |
76 |
74 |
|
Maximum input current (A) |
100 |
95 |
95 |
|
Total harmonic distortion (THDI) | ≤ 3% for linear load | |||
Input power factor | > 0.99 (full load) | |||
Maximum short circuit rating | Rated conditional
short-circuit current Icc = 35 kA Device: Refer to Required Upstream Protection. |
|||
Ramp-in | Programmable and adaptive 1-40 seconds | |||
Protection | Built-in backfeed protection and fuses | |||
Bypass | Connections |
L1, L2, L3, N, PE |
||
Minimum bypass voltage (V) | 342 | 360 | 374 | |
Maximum bypass voltage (V) | 418 | 440 | 457 | |
Frequency (Hz) | 50 or 60 | |||
Frequency range (Hz) | ±1 Hz, ±3 Hz, ±10 Hz (user selectable) | |||
Nominal bypass current (A) |
78 |
74 |
71 |
|
Maximum short circuit rating | Rated conditional
short-circuit current Icc = 35 kA Device: Refer to Required Upstream Protection. |
|||
Protection | Dry contact signal for backfeed protection | |||
Output | Connections |
L1, L2, L3, N, PE |
||
Output voltage regulation | ±1% (symmetrical
load) ±3% (asymmetrical load) |
|||
Overload capacity | Normal operation:
≤125% for 10 minutes; ≤150% for 1 minute Bypass operation: ≤110% continuous; ≤125% for 10 minutes; ≤150% for 1 minute Battery operation: ≤125% for 1 minute; ≤150% for 1 second |
|||
Output power factor | 1 | |||
Nominal output current (A) |
76 |
73 |
70 |
|
Total harmonic distortion (THDU) | 1% (linear load) 3% (non-linear load) |
|||
Output frequency (Hz) | 50/60 Hz bypass
synchronized 50/60 Hz ± 0.1% free-running |
|||
Slew rate (Hz/sec) | Programmable to 0.25, 0.5, 1, 2, 4, 6 Hz/second | |||
Output performance classification (according to IEC/ EN62040-3) | VFI-SS-11 | |||
Load power factor | 0.7 leading to 0.7 lagging without derating | |||
Output short circuit current (inverter) |
160 A/220 ms |
|||
Battery | Charging power in % of output power | 5% to 60% (selectable) | ||
Maximum charging power (kW) | 30 | |||
Nominal battery voltage (VDC) | 480 to 576 | |||
Nominal float voltage (VDC) | 545 to 654 | |||
End of discharge voltage (full load) (VDC) | 384 to 461 | |||
Temperature compensation (per cell) | -3.3 mV/°C/cell
for T ≥ 25 °C 0 mV/°C/cell for T < 25 °C |
|||
Battery current at full load and nominal battery voltage (A) | 111 | |||
Battery current at full load and minimum battery voltage (A) | 130 | |||
Ripple current | < 5% C20 (5-minute runtime) | |||
Battery test | Manual/automatic (selectable) | |||
Maximum short circuit rating | 25 kA |
Specifications for 100 kW UPS
Voltage (V) | 380 | 400 | 415 | |
---|---|---|---|---|
Input | Connections | L1, L2, L3,
N, PE (single mains) L1, L2, L3, PE (dual mains)* |
||
Input voltage range of full load (V) | 304-456* | 320-460 | 332-477 | |
Frequency (Hz) | 40-70 | |||
Nominal input current (A) |
160 |
152 |
147 |
|
Maximum input current (A) |
200 |
190 |
190 |
|
Total harmonic distortion (THDI) | ≤ 3% for linear load | |||
Input power factor | > 0.99 (full load) | |||
Maximum short circuit rating | Rated conditional
short-circuit current Icc = 35 kA Device: Refer to Required Upstream Protection. |
|||
Ramp-in | Programmable and adaptive 1-40 seconds | |||
Protection | Built-in backfeed protection and fuses | |||
Bypass | Connections |
L1, L2, L3, N, PE |
||
Minimum bypass voltage (V) | 342 | 360 | 374 | |
Maximum bypass voltage (V) | 418 | 440 | 457 | |
Frequency (Hz) | 50 or 60 | |||
Frequency range (Hz) | ±1 Hz, ±3 Hz, ±10 Hz (user selectable) | |||
Nominal bypass current (A) |
155 |
147 |
142 |
|
Maximum short circuit rating | Rated conditional
short-circuit current Icc = 35 kA Device: Refer to Required Upstream Protection. |
|||
Protection | Dry contact signal for backfeed protection | |||
Output | Connections |
L1, L2, L3, N, PE |
||
Output voltage regulation | ±1% (symmetrical
load) ±3% (asymmetrical load) |
|||
Overload capacity | Normal operation:
≤125% for 10 minutes; ≤150% for 1 minute Bypass operation: ≤110% continuous; ≤125% for 10 minutes; ≤150% for 1 minute Battery operation: ≤125% for 1 minute; ≤150% for 1 second |
|||
Output power factor | 1 | |||
Nominal output current (A) |
152 |
145 |
140 |
|
Total harmonic distortion (THDU) | 1% (linear load) 3% (non-linear load) |
|||
Output frequency (Hz) | 50/60 Hz bypass
synchronized 50/60 Hz ± 0.1% free-running |
|||
Slew rate (Hz/sec) | Programmable to 0.25, 0.5, 1, 2, 4, 6 Hz/second | |||
Output performance classification (according to IEC/ EN62040-3) | VFI-SS-11 | |||
Load power factor | 0.7 leading to 0.7 lagging without derating | |||
Load crest factor | 2.5 | |||
Output short circuit current (inverter) |
320 A/220 ms |
|||
Battery | Charging power in % of output power | 5% to 60% (selectable) | ||
Maximum charging power (kW) | 60 | |||
Nominal battery voltage (VDC) | 480 to 576 | |||
Nominal float voltage (VDC) | 545 to 654 | |||
End of discharge voltage (full load) (VDC) | 384 to 461 | |||
Temperature compensation (per cell) | -3.3 mV/°C/cell
for T ≥ 25 °C 0 mV/°C/cell for T < 25 °C |
|||
Battery current at full load and nominal battery voltage (A) | 222 | |||
Battery current at full load and minimum battery voltage (A) | 260 | |||
Ripple current | < 5% C20 (5-minute runtime) | |||
Battery test | Manual/automatic (selectable) | |||
Maximum short circuit rating | 25 kA |
Specifications for 150 kW UPS
Voltage (V) | 380 | 400 | 415 | |
---|---|---|---|---|
Input | Connections | L1, L2, L3,
N, PE (single mains) L1, L2, L3, PE (dual mains)* |
||
Input voltage range at full load (V) | 304-456* | 320-460 | 332-477 | |
Frequency (Hz) | 40-70 | |||
Nominal input current (A) |
240 |
228 |
220 |
|
Maximum input current (A) |
300 |
285 |
285 |
|
Total harmonic distortion (THDI) | ≤ 3% for linear load | |||
Input power factor | > 0.99 (full load) | |||
Maximum short circuit rating | Rated conditional
short-circuit current Icc = 35 kA Device: Refer to Required Upstream Protection. |
|||
Ramp-in | Programmable and adaptive 1-40 seconds | |||
Protection | Built-in backfeed protection and fuses | |||
Bypass | Connections |
L1, L2, L3, N, PE |
||
Minimum bypass voltage (V) | 342 | 360 | 374 | |
Maximum bypass voltage (V) | 418 | 440 | 457 | |
Frequency (Hz) | 50 or 60 | |||
Frequency range (Hz) | ±1 Hz, ±3 Hz, ±10 Hz (user selectable) | |||
Nominal bypass current (A) |
232 |
220 |
212 |
|
Maximum short circuit rating | Rated conditional
short-circuit current Icc = 35 kA Device: Refer to Required Upstream Protection. |
|||
Protection | Dry contact signal for backfeed protection | |||
Output | Connections |
L1, L2, L3, N, PE |
||
Output voltage regulation | ±1% (symmetrical
load) ±3% (asymmetrical load) |
|||
Overload capacity | Normal operation:
≤125% for 10 minutes; ≤150% for 1 minute Bypass operation: ≤110% continuous; ≤125% for 10 minutes; ≤150% for 1 minute Battery operation: ≤125% for 1 minute; ≤150% for 1 second |
|||
Output power factor | 1 | |||
Nominal output current (A) |
228 |
217 |
209 |
|
Total harmonic distortion (THDU) | 1% (linear load) 3% (non-linear load) |
|||
Output frequency (Hz) | 50/60 Hz bypass
synchronized 50/60 Hz ± 0.1% free-running |
|||
Slew rate (Hz/sec) | Programmable to 0.25, 0.5, 1, 2, 4, 6 Hz/second | |||
Output performance classification (according to IEC/ EN62040-3) | VFI-SS-11 | |||
Load power factor | 0.7 leading to 0.7 lagging without derating | |||
Output short circuit current (inverter) |
480 A/220 ms |
|||
Battery | Charging power in % of output power | 5% to 60% (selectable) | ||
Maximum charging power (kW) | 90 | |||
Nominal battery voltage (VDC) | 480 to 576 | |||
Nominal float voltage (VDC) | 545 to 654 | |||
End of discharge voltage (full load) (VDC) | 384 to 461 | |||
Temperature compensation (per cell) | -3.3 mV/°C/cell
for T ≥ 25 °C 0 mV/°C/cell for T < 25 °C |
|||
Battery current at full load and nominal battery voltage (A) | 333 | |||
Battery current at full load and minimum battery voltage (A) | 390 | |||
Ripple current | < 5% C20 (5-minute runtime) | |||
Battery test | Manual/automatic (selectable) | |||
Maximum short circuit rating | 25 kA |
Specifications for 200 kW UPS
Voltage (V) | 380 | 400 | 415 | |
---|---|---|---|---|
Input | Connections | L1, L2, L3,
N, PE (single mains) L1, L2, L3, PE (dual mains)* |
||
Input voltage range at full load (V) | 304-456* | 320-460 | 332-477 | |
Frequency (Hz) | 40-70 | |||
Nominal input current (A) |
320 |
304 |
293 |
|
Maximum input current (A) |
400 |
380 |
380 |
|
Total harmonic distortion (THDI) | ≤ 3% for linear load | |||
Input power factor | > 0.99 (full load) | |||
Maximum short circuit rating | Rated conditional
short-circuit current Icc = 35 kA Device: Refer to Required Upstream Protection. |
|||
Ramp-in | Programmable and adaptive 1-40 seconds | |||
Protection | Built-in backfeed protection and fuses | |||
Bypass | Connections |
L1, L2, L3, N, PE |
||
Minimum bypass voltage (V) | 342 | 360 | 374 | |
Maximum bypass voltage (V) | 418 | 440 | 457 | |
Frequency (Hz) | 50 or 60 | |||
Frequency range (Hz) | ±1 Hz, ±3 Hz, ±10 Hz (user selectable) | |||
Nominal bypass current (A) |
309 |
294 |
283 |
|
Maximum short circuit rating | Rated conditional
short-circuit current Icc = 35 kA Device: Refer to Required Upstream Protection. |
|||
Protection | Dry contact signal for backfeed protection | |||
Output | Connections |
L1, L2, L3, N, PE |
||
Output voltage regulation | ±1% (symmetrical
load) ±3% (asymmetrical load) |
|||
Overload capacity | Normal operation:
≤125% for 10 minutes; ≤150% for 1 minute Bypass operation: ≤110% continuous; ≤125% for 10 minutes; ≤150% for 1 minute Battery operation: ≤125% for 1 minute; ≤150% for 1 second |
|||
Output power factor | 1 | |||
Nominal output current (A) |
304 |
289 |
279 |
|
Total harmonic distortion (THDU) | 1% (linear load) 3% (non-linear load) |
|||
Output frequency (Hz) | 50/60 Hz bypass
synchronized 50/60 Hz ± 0.1% free-running |
|||
Slew rate (Hz/sec) | Programmable to 0.25, 0.5, 1, 2, 4, 6 Hz/second | |||
Output performance classification (according to IEC/ EN62040-3) | VFI-SS-11 | |||
Load power factor | 0.7 leading to 0.7 lagging without derating | |||
Output short circuit current (inverter) |
640 A/220 ms |
|||
Battery | Charging power in % of output power | 5% to 60% (selectable) | ||
Maximum charging power (kW) | 120 | |||
Nominal battery voltage (VDC) | 480 to 576 | |||
Nominal float voltage (VDC) | 545 to 654 | |||
End of discharge voltage (full load) (VDC) | 384 to 461 | |||
Temperature compensation (per cell) | -3.3 mV/°C/cell
for T ≥ 25 °C 0 mV/°C/cell for T < 25 °C |
|||
Battery current at full load and nominal battery voltage (A) | 444 | |||
Battery current at full load and minimum battery voltage (A) | 520 | |||
Ripple current | < 5% C20 (5-minute runtime) | |||
Battery test | Manual/automatic (selectable) | |||
Maximum short circuit rating | 25 kA |
Specifications for 250 kW UPS
Voltage (V) | 380 | 400 | 415 | |
---|---|---|---|---|
Input | Connections | L1, L2, L3,
N, PE (single mains) L1, L2, L3, PE (dual mains)* |
||
Input voltage range at full load (V) | 304-456* | 320-460 | 332-477 | |
Frequency (Hz) | 40-70 | |||
Nominal input current (A) |
400 |
380 |
367 |
|
Maximum input current (A) |
500 |
475 |
475 |
|
Total harmonic distortion (THDI) | ≤ 3% for linear load | |||
Input power factor | > 0.99 (full load) | |||
Maximum short circuit rating | Rated conditional
short-circuit current Icc = 35 kA Device: Refer to Required Upstream Protection. |
|||
Ramp-in | Programmable and adaptive 1-40 seconds | |||
Protection | Built-in backfeed protection and fuses | |||
Bypass | Connections |
L1, L2, L3, N, PE |
||
Minimum bypass voltage (V) | 342 | 360 | 374 | |
Maximum bypass voltage (V) | 418 | 440 | 457 | |
Frequency (Hz) | 50 or 60 | |||
Frequency range (Hz) | ±1 Hz, ±3 Hz, ±10 Hz (user selectable) | |||
Nominal bypass current (A) |
386 |
367 |
354 |
|
Maximum short circuit rating | Rated conditional
short-circuit current Icc = 35 kA Device: Refer to Required Upstream Protection. |
|||
Protection | Dry contact signal for backfeed protection | |||
Output | Connections |
L1, L2, L3, N, PE |
||
Output voltage regulation | ±1% (symmetrical
load) ±3% (asymmetrical load) |
|||
Overload capacity | Normal operation:
≤125% for 10 minutes; ≤150% for 1 minute Bypass operation: ≤110% continuous; ≤125% for 10 minutes; ≤150% for 1 minute Battery operation: ≤125% for 1 minute; ≤150% for 1 second |
|||
Output power factor | 1 | |||
Nominal output current (A) |
380 |
361 |
348 |
|
Total harmonic distortion (THDU) | 1% (linear load) 3% (non-linear load) |
|||
Output frequency (Hz) | 50/60 Hz bypass
synchronized 50/60 Hz ± 0.1% free-running |
|||
Slew rate (Hz/sec) | Programmable to 0.25, 0.5, 1, 2, 4, 6 Hz/second | |||
Output performance classification (according to IEC/ EN62040-3) | VFI-SS-11 | |||
Load power factor | 0.7 leading to 0.7 lagging without derating | |||
Load crest factor | 2.5 | |||
Output short circuit current (inverter) |
800 A/220 ms |
|||
Battery | Charging power in % of output power | 5% to 60% (selectable) | ||
Maximum charging power (kW) | 150 | |||
Nominal battery voltage (VDC) | 480 to 576 | |||
Nominal float voltage (VDC) | 545 to 654 | |||
End of discharge voltage (full load) (VDC) | 384 to 461 | |||
Temperature compensation (per cell) | -3.3 mV/°C/cell
for T ≥ 25 °C 0 mV/°C/cell for T < 25 °C |
|||
Battery current at full load and nominal battery voltage (A) | 555 | |||
Battery current at full load and minimum battery voltage (A) | 650 | |||
Ripple current | < 5% C20 (5-minute runtime) | |||
Battery test | Manual/automatic (selectable) | |||
Maximum short circuit rating | 25 kA |
Required Upstream Protection
![]() |
---|
Hazard of electric shock, explosion, or arc flash
The upstream protection must use the required 3-pole breakers
OR 4-pole breakers listed below. The use of 3-pole breaker or 4-pole
breaker depends on your local and national regulations.
Failure to follow these instructions will result in death or serious injury.
|
Required 3-Pole Upstream Protection
UPS rating | 50 kW | 100 kW | ||
---|---|---|---|---|
Input | Bypass | Input | Bypass | |
Breaker type |
NSX100H TM100D |
NSX100H TM80D |
NSX250H
TM200 (C25H3TM200) |
NSX160H TM160 (C16H3TM160) |
Io | 100 | 80 | 200 | 160 |
Ir | 100 | 80 | 200 | 160 |
Isd | 800 (fixed) | 640 (fixed) | 5 - 10 | 1250 (fixed) |
UPS rating | 150 kW | 200 kW | 250 kW | |||
---|---|---|---|---|---|---|
Input | Bypass | Input | Bypass | Input | Bypass | |
Breaker type | NSX400H
MiC.2.3 (C40H32D400) |
NSX250H
TM250 (C25H3TM250) |
NSX400H
MiC.2.3 (C40H32D400) |
NSX400H
MiC.2.3 (C40H32D400) |
NSX630H
MiC.2.3 (C63H32D630) |
NSX400H MiC.2.3 (C40H32D400) |
Io | 320 | 250 | 400 | 320 | 500 | 400 |
Ir | 0.95 | 250 | 1 | 1 | 1 | 1 |
Isd | 1.5 - 10 | 5 - 10 | 1.5 - 10 | 1.5 - 10 | 1.5 - 10 | 1.5 - 10 |
Required 4-Pole Upstream Protection
UPS rating | 50 kW | 100 kW | ||
---|---|---|---|---|
Input | Bypass | Input | Bypass | |
Breaker type |
NSX100H TM100D |
NSX160H TM160 |
NSX250H TM200 |
NSX400H MiC.2.3 |
Io |
100 |
160 |
200 |
280 |
Ir |
100 |
0.8 |
200 |
0.95 |
Isd |
800 (fixed) |
1250 (fixed) |
1.5 - 10 |
1.5 - 10 |
UPS rating | 150 kW | 200 kW | 250 kW | |||
---|---|---|---|---|---|---|
Input | Bypass | Input | Bypass | Input | Bypass | |
Breaker type |
NSX400H MiC.2.3 |
NSX400H MiC.2.3 |
NSX400H MiC.2.3 |
NSX400H MiC.2.3 |
NSX630H MiC.2.3 |
NSX400H MiC.2.3 |
Io |
320 |
280 |
400 |
320 |
500 |
400 |
Ir |
0.95 |
0.95 |
1 |
1 |
1 |
1 |
Isd |
1.5 - 10 |
1.5 - 10 |
1.5 - 10 |
1.5 - 10 |
1.5 - 10 |
1.5 - 10 |
Recommended Cables Sizes
![]() |
---|
hazard of electric shock, explosion, or arc flash
All wiring must comply with all applicable national and/or
electrical codes. The maximum allowable cable size is 185 mm².
Failure to follow these instructions will result in death or serious injury.
|
Cable sizes in this manual are based on table A.52-5 of IEC 60364-5-52 with the following assertions:
-
90 °C conductors
-
An ambient temperature of 30 °C
-
Use of copper conductors
-
Installation method C
PE size is based on table 54.3 of IEC 60364-5-54.
If the ambient temperature is greater than 30 °C, larger conductors are to be used in accordance with the correction factors of the IEC.
50 kW UPS
Cable size per phase (mm2) | Neutral cable size (mm2) | PE cable size (mm2)) | |
Input | 25 | 35 | 16 |
Bypass | 16 (for 3-pole upstream protection) 35 (for 4-pole upstream protection) |
35 | 16 |
Output | 16 | 35 | 16 |
Battery | 35 | 35* | 16 |
100 kW UPS
Cable size per phase (mm2) | Neutral cable size (mm2) | PE cable size (mm2)) | |
Input | 70 | 2 x 70 | 35 |
Bypass | 70 (for 3-pole upstream protection) 2 x 70 (for 4-pole upstream protection) |
2 x 70 | 35 |
Output | 70 | 2 x 70 | 35 |
Battery | 95 | 95* | 50 |
150 kW UPS
Cable size per phase (mm2) | Neutral cable size (mm2) | PE cable size (mm2)) | |
Input | 120 | 2 x 70 | 70 |
Bypass | 120 (for 3-pole upstream protection) 2 x 70 (for 4-pole upstream protection) |
2 x 70 | 70 |
Output | 120 | 2 x 70 | 70 |
Battery | 2 x 70 | 2 x 70* | 70 |
200 kW UPS
Cable size per phase (mm2) | Neutral cable size (mm2) | PE cable size (mm2)) | |
---|---|---|---|
Input | 2
x 95 |
2 x 95 |
95 |
Bypass | 2
x 70 |
70 | |
Output | 2
x 70 |
2
x 70 |
70 |
Battery | 2 x 120 | 2 x 120* | 120 |
250 kW UPS
Cable size per phase (mm2) | Neutral cable size (mm2) | PE cable size (mm2)) | |
---|---|---|---|
Input | 2 x 120 | 2 x 120 | 120 |
Bypass | 2 x 95 | 95 | |
Output | 2 x 95 | 2 x 95 | 95 |
Battery | 2 x 150 | 2 x 150* | 150 |
Recommended Bolt and Lug Sizes
Copper
Cable size (mm²) | Bolt size | Cable lug type |
---|---|---|
16 | M10x40 mm | TLK 16-10 |
25 | M10x40 mm | TLK 25-10 |
35 | M10x40 mm | TLK 35-10 |
50 | M10x40 mm | TLK 50-10 |
70 | M10x40 mm | TLK 70-10 |
95 | M10x40 mm | TLK 95-10 |
120 | M10x40 mm | TLK 120-10 |
150 | M10x40 mm | TLK 150-10 |
185 | M10x40 mm | TLK 185-10 |
Torque Specifications
Bolt size | Torque |
---|---|
M4 | 1.7 Nm |
M6 | 5 Nm |
M8 | 17.5 Nm |
M10 | 30 Nm |
M12 | 50 Nm |
Requirements for a Third Party Battery Solution
Battery breaker boxes from Schneider Electric are recommended for the battery interface. Please contact Schneider Electric for more information.
Third Party Battery Breaker Requirements
![]() |
---|
Hazard of electric shock, explosion, or arc flash
Failure to follow these instructions will result in death or serious injury.
|
Design Requirements for Battery Breaker
Battery breaker rated DC voltage > Normal battery voltage | The normal voltage of the battery configuration is defined as the highest nominal occurring battery voltage. This can be equivalent to the float voltage which may be defined as number of battery blocks x number of cells x cell float voltage. |
Battery breaker rated DC current > Rated discharge battery current | This current is controlled by the UPS and must include maximum discharge current. This will typically be the current at the end of discharge (minimum operation DC voltage or in overload condition or a combination). |
DC landings | Two DC landings for DC cables (DC+ and DC-) are required. |
AUX switches for monitoring | One AUX switch must be installed in each battery breaker and connected to the UPS. The UPS can monitor up to four battery breakers. |
Short-circuit breaking capability | The short-circuit breaking capability must be higher than the short-circuit DC current of the (largest) battery configuration. |
Minimum trip current | The minimum short-circuit current to trip the battery breaker must match the (smallest) battery configuration, to make the breaker trip in case of a short circuit, up to the end of its life time. |
Common battery solution | Individual battery breaker for each UPS in the parallel system. |
Guidance for Organizing Battery Cables
Environment
Operating | Storage | |
---|---|---|
Temperature | 0 °C to 50 °C with load derating above 40 °C* | -25 °C to 55 °C |
Relative humidity | 0-95% non-condensing | 0-95% non-condensing |
Elevation | Designed for operation in 0-3000 m elevation. Derating required from 1000-3000 m with forced air cooling: Up to 1000 m: 1.000 Up to 1500 m: 0.975 Up to 2000 m: 0.950 Up to 2500 m: 0.925 Up to 3000 m: 0.900 |
|
Audible noise* |
68 dB at 70% load 74 dB at 100% load |
|
Protection class | IP20 | |
Color | Black |
Compliance
Safety | IEC 62040-1:2017,
Edition 2.0, Uninterruptible power systems (UPS) – Part 1:
Safety requirements |
EMC | IEC 62040-2:2016,
Edition 3.0, Uninterruptible power systems (UPS) – Part 2:
Electromagnetic compatibility (EMC) requirements. IEC 62040-2:2005-10, Edition 2.0, Uninterruptible Power Systems (UPS) – Part 2: Electromagnetic compatibility (EMC) requirements |
Performance | IEC 62040-3: 2021-03, Edition 3.0, Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the performance and test requirements |
Transportation | IEC TR 60721-4-2: 2001 Level 2M2 |
Pollution degree | 2 |
Overvoltage category | III |
Earthing system |
TN-S, TN-C, TN-C-S, TT |
Protective class | I |
Arc flash safety | IEC TR 61641: 2014 Edition 3.0 |
UPS Weights and Dimensions
UPS with One Internal Switch
Type | Weight kg | Height mm | Width mm | Depth mm |
---|---|---|---|---|
50 kW |
216 |
1991 |
600 |
850 |
50 kW with N+1 power module |
244 |
1991 |
600 |
850 |
100 kW |
244 |
1991 |
600 |
850 |
100 kW with N+1 power module |
272 |
1991 |
600 |
850 |
150 kW |
272 |
1991 |
600 |
850 |
150 kW with N+1 power module |
300 |
1991 |
600 |
850 |
200 kW |
300 |
1991 |
600 |
850 |
200 kW with N+1 power module |
328 |
1991 |
600 |
850 |
250 kW |
328 |
1991 |
600 |
850 |
250 kW with N+1 power module |
356 |
1991 |
600 |
850 |
UPS with Four Internal Switches
Type | Weight kg | Height mm | Width mm | Depth mm |
---|---|---|---|---|
50 kW |
251 |
1991 |
600 |
850 |
50 kW with N+1 power module |
279 |
1991 |
600 |
850 |
100 kW |
279 |
1991 |
600 |
850 |
100 kW with N+1 power module |
307 |
1991 |
600 |
850 |
150 kW |
307 |
1991 |
600 |
850 |
150 kW with N+1 power module |
335 |
1991 |
600 |
850 |
200 kW |
335 |
1991 |
600 |
850 |
200 kW with N+1 power module |
363 |
1991 |
600 |
850 |
250 kW |
363 |
1991 |
600 |
850 |
250 kW with N+1 power module |
391 |
1991 |
600 |
850 |