Diagnostic codes
|
Diagnostic code * |
Description |
Possible solution |
|---|---|---|
|
— |
LCD display is not visible. |
Check and adjust LCD contrast. |
|
— |
Push buttons do not respond. |
Restart the meter by powering off and powering on again. |
|
101 |
Metering stops due to an EEPROM error. Press OK to display total energy consumption. |
Enter configuration mode and select Reset Config. |
|
102 |
Metering stops due to a lack of a calibration table. Press OK to display total energy consumption. |
Enter configuration mode and select Reset Config. |
|
201 |
Metering continues. Mismatch between frequency settings and frequency measurements. |
Correct the frequency settings according to the nominal frequency of the power system. |
|
202 |
Metering continues. Mismatch between wiring settings and wiring inputs. |
Correct the wiring settings according to wiring inputs. |
|
203 |
Metering continues. Phase sequence reversed. |
Check the wire connections and correct the wiring settings if needed. |
|
204 |
Metering continues. Total active energy is negative due to incorrect voltage and current connections. |
Check the wire connections and correct the wiring settings if needed. |
|
205 |
Metering continues. Date and Time have been reset due to a loss of power. |
Set the Date and Time. |
|
206 |
Metering continues. Pulse is missing due to overload on energy pulse output. |
Check the energy pulse output settings and correct if needed. |
|
207 |
Metering continues. Abnormal internal clock function. |
Restart the meter by powering off and powering on again then reset the date and time. |