I-Line Series Connected Circuit Breaker Ratings

Refer to Catalog 2110CT9701

I-Line Series Connected Circuit Breaker Ratings

I-Line Series Connected Circuit Breaker Ratings (RMS Symmetrical)

Maximum System Voltage AC [1]

Maximum Short Circuit Current Rating

Square D Brand Integral or Remote 2- or 3-Pole Main Circuit Breaker [2]

Square D Brand Branch Circuit Breaker

Catalog Designation

Poles

120

42,000

MG

FY

1

65,000

QG, LH

FA, FD

QG, BG6, HG, JG, LG, MG, PG

BD6 (60 A Max.)

100,000

FJ, QJ

FD

QJ, LC

FA

LJ

FH

QJ, BJ, HJ, JJ, LJ, MJ, PJ

BD6, BG6 (60 A Max.)

125,000

HL, JL, LL

BD6, BG6, BJ (60 A Max.)

200,000

LR

FH, FY

HR, JR

BD6, BG6, BJ (60 A Max.)

208Y/120

65,000

QG, BG6, HG, JG, LG, MG, PG

BD6

2, 3

100,000

QJ

FA, FD

QJ, BJ, HJ, JJ, LJ, MJ, PJ

BD6, BG6

QJ, PH, PJ, RJ

QD, QG

240

35,000

MG

FA

1

42,000

KA

FD

1, 2, 3

LA, MA

HD, JD, QD

2, 3

50,000

MG

FA

MG

FA (25 A Max.)

1

65,000

HG, JG

FA, HD

2, 3

JG

JD, QD

QG

FA, FD, QD

QG, BG6, HG, JG, LG, MG, PG

BD6

LH, MH, PA, PG, RG

HD, JD, QD

FG, FH, MH, MX, PJ

FD

1, 2, 3

FC, KC, KH, LC, LH

FD, FG

LH

FA

LH

LA

2, 3

MG

HD, JD, KA

DG

FH, HD, JD, KA, LA, MA

LG

HD, JD, KA, LA, MA

LG

LD

3

85,000

RL

FH, KH

2, 3

100,000

FC, KC, LC, LX

FD, FG, FJ

1

PH, PJ, RJ

QD, QG

2, 3

QJ

FD

2

FJ

FD

2, 3

LJ

HD, HG, JD, JG, FH, KA, LA, MA, MG

LJ

LD, LG

3

FC, KC

FA, FH, FD, FG, FJ

2, 3

LC, LX

FH, FD, FG, FJ

QJ, BJ, HJ, JJ, LJ, MJ, PJ

BD6, BG6

KC, LC, LX

KA

KC, LC

KH

LC

LA, LH, MG

LC

FA

1, 2, 3

HJ, JJ

FA, FH, HD, HG

2, 3

JJ

JD, JG

LC, LX, MJ, PJ, RJ

HD, HG, JD, JG

MJ

LA, LH

DJ

FH, HD, HG, JD, JG, KA, LA, MA, MG

RL

RG

HL, JL

HD, HG, HJ, FA, FH

125,000

JL

JD, JG, JJ

HL, JL, LL

BD6, BG6, BJ

PC, PH, PL, RL

HD, HG, JD, JG

PC, PL, RL

HJ, JJ

FI, KI, LI, LXI

HD, HG, HJ

KI, LI, LXI

JD, JG, JJ

200,000

FI, KI, LI, LXI

FD, FG, FJ

1

FI, KI

FA, FH, FC, FD, FG, FJ

2, 3

LI, LXI

FH, FD, FG, FJ

LI

FC

HR, JR, LR

BD6, BG6, BJ

KI, LI, LXI

KA, QD, QG, QJ

LI

KC

JR

QD

LR

HJ, HL, JJ, JL, FH, LA, LH, QD, QG, QJ

277

18,000

LD

FY

1

25,000

FH, KA

FD

35,000

FG, KH, LH

FD

DG, LG

FH, FY

FC, KC

FH

BG6, HG, JG, LG, MG, PG

BD6 (60 A Max.)

65,000

FJ

FD

FC, KC

FA, FY, FD, FG

LC, LX (400 A Max.)

FH

LC, LX (600 A Max.)

FY, FD, FG

DJ

FH, FY

LL

FY

LJ

FH, FY

BJ, HJ, JJ, LJ, MJ, PJ

BD6, BG6 (60 A Max.)

FI, KI

FH

100,000

DL, LL

FH, FJ

HL, JL, LL

BD6, BG6, BJ (60 A Max.)

200,000

FI, KI

FA, FY, FD, FG, FJ

LI, LXI, (400 A Max.)

FH

LI, LXI, (600 A Max.)

FY, FD, FG, FJ

HR, JR

BD6, BG6, BJ (60 A Max.)

480

22,000

MG

FA

2, 3

MX, PA, PC, PX

FH

30,000

KH, LA, MA, PJ

FH

LA, MA, PA, PC, PX

KA

LA, MA, PA

HD, JD

MG

FA (25 A Max.), FH, KA

MX, PA

HD, JD

35,000

MH

HD, JD

HG, JG

FA, HD

JG

JD

LH, MG, PG, RG

HD, JD

BG6, HG, JG, LG, MG, PG

BD6

LH

HG, JG

DG

FH, HD, JD, KA, LA, MA

LG

LD

3

LG

HD, JD, FH, KA, LA, MA

2, 3

42,000

MJ

FH (25 A Max.)

2, 3

RL

RG

50,000

MJ

KA, KH

65,000

FC, KC

FA, FH

HJ, JJ

FA, FH, HD, HG

BJ, HJ, JJ, LJ, MJ, PJ

BD6, BG6

JJ

JD, JG

LC, LI, LX, LXI

HD, HG, JD, JG

LC, LX, (400 A Max.)

FH

KC, LC, LX

KA

LC, LX

LA

DJ

FH, HD, HG, JD, JG, KA, LA, MA

LJ

LD, LG

3

LJ

HD, HG, JD, JG, FH, KA, LA, MA

2, 3

100,000

HL, JL

FA, FH, HD, HG, HJ

2, 3

HL, JL, LL

BD6, BG6, BJ

JL

JD, JG, JJ

LI, LXI (600 A Max.)

KA

PC, PH, PL, RL

HJ, JJ

RL

RG

DL

FH, HD, HG, HJ, JD, JG, JJ, KA, LA, MA

LL

LD, LG, LJ

3

LL

HD, HG, HJ, JD, JG, JJ, FH, KA, LA, MA

2, 3

JR

FA

200,000

FI, KI

FA, FH, FC, HD, HG, HJ

HR, JR

BD6, BG6, BJ

KI

JD, JG, JJ, KA

LI

FC, KA, KC, LA, HJ, HL, JJ, JL

LXI

KA, HJ, HL, JJ, JL

HR

FA, HD, HG, HJ, HL

JR

HD, HG, HJ, HL, JD, JG, JJ, JL

LR

HJ, HL, JJ, JL, FH, LA, LH

480Y/277

25,000

FH, KA

FD

35,000

FG, KH, LH

FD

BG6, HG, JG, LG, MG, PG

BD6

65,000

FJ

FD

BJ, HJ, JJ, LJ, MJ, PJ

BD6, BG6

FC, KC

FD, FG

LC, LX (600 A Max.)

FD, FG

100,000

HL, JL, LL

BD6, BG6, BJ

200,000

FI, KI

FD, FG, FJ

HR, JR

BD6, BG6, BJ

LI, LXI (600 A MAX.)

FD, FG, FJ

600

18,000

HG, JG

FA, HD

2, 3

JG

JD

MG, PG, RG

HD, JD

MG

FA

LG

LD

3

LG

HD, JD

2, 3

25,000

HJ, JJ

FA, HD, HG

JJ

JD

PJ, RJ

MG

LJ

LD, LG

3

LJ

JD, JG, HD, HG, MA

2, 3

35,000

LC

FH, HD, HG, HJ, JD, JG, JJ, LA

50,000

HL, JL

FA, HD, HG, HJ

JL

JD, JG, JJ

PK

HJ, JJ, MJ

LL

LD, LG, LJ

3

LL

HD, HG, HJ, JD, JG, JJ, MA

2, 3

100,000

FI, KI

HD, HG, HJ

KI

JD, JG, JJ

HR

FA, HD, HG, HJ, HL

JR

FA, HD, HG, HJ, HL, JD, JG, JJ, JL

KI, LI

FH

LI

LA

347

18,000

BG6, HG, JG, LG, MG, PG

BD6 (60 A Max.)

1

25,000

BJ, HJ, JJ, LJ, MJ, PJ

BD6, BG6 (60 A Max.)

100,000

HR, JR

BD6, BG6, BJ (60 A Max.)

600Y/347

18,000

BG6, HG, JG, LG, MG, PG

BD6

3

MG

FA (25 A Max.)

1

25,000

BJ, HJ, JJ, LJ, MJ, PJ

BD6, BG6

3

MJ

FA (25 A Max.)

1

50,000

HL, JL, LL

BD6, BG6, BJ

3

HL, JL

FJ

1

100,000

HR, JR

BD6, BG6, BJ

3

Fuse/I-Line Circuit Breaker Series Connected Ratings

Maximum System Voltage AC [1]

Maximum Short Circuit Current Rating

Remote Main Fuse

Square D Brand Branch Circuit Breaker Catalog Designation (2- or 3-Pole) Unless Otherwise Stated

Max A

Class

120/240 1Ø 208Y/120

100,000

1200 A

L, T (300 V)

QD, QG

800 A

T (600 V)

600 A

J, RK5

240

65,000

1200 A

L, T (300 V)

QD

800 A

T (600 V)

600 A

J, RK5

100,000

1200 A

L, T (300 V)

QD, QG (2-Pole)

800 A

T (600 V)

600 A

J, RK5

J, T (600 V)

FA, FH, KA, KH, KC, LA, LH, MA, MH, MX, PG

RK5

FH, KA, KH, LA, LH, MA, MH, MX, PG, HD, HG, HJ, HL, JD, JG, JJ, JL

J

HD, HG, HJ, HL, JD, JG, JJ, JL

800 A

T (600 V)

FH, KA, KH, LA, LH, MA, MH, MX, PG

T (300 V)

PG

L

FH, KA, KH, LA, LH, MA, MH, MX, PG

1200 A

L

FH, KH, LA, LH, MA, MH, MX, PG

T (600 V)

HD, HG, HJ, HL, JD, JG, JJ, JL

200,000

600 A

J, T (600 V)

FA (3-pole only) FH, FC, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL

RK5

FH, FC, HD, HG, HJ, HL, JD, JG, JJ, JL, KH, KC, LA, LH, LC, MA, MH, MX, NC, NX, PG,PJ, PL

J

HD, HG, HJ, HL, JD, JG, JJ, JL

800 A

T (600 V)

FH, FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL

T (300 V)

PG, PJ, PL

L

FH, FC, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL

1200 A

L

FC, KH, KC, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL

T (600 V)

HD, HG, HJ, HL, JD, JG, JJ, JL

480

100,000

400 A

J, T(600 V)

HD, HG, HJ, HL, JD, JG, JJ, JL

600 A

J, RK5

HJ, HL, JJ, JL

600 A

J, T (600 V)

FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ

RK5

FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ

800 A

L, T(600V)

FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ

1200 A

L

FC, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ

T (600 V)

HJ, HL, JJ, JL

200,000

200 A

RK5

HJ, HL

400 A

J

FA, FH, FC, HJ, HL, JJ, JL, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL

T (600 V)

FA, FH, FC, HJ, HL, JJ, JL, KA, KH, KC, LA, LH, MA, MH, MX, NA, NC, NX

600 A

J

FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, MG, MJ, NA, NC, NX, PG, PJ, PL

T(600 V)

KA, KH, KC, LA, LH, MA, MH, MX, NA, NC, NX

RK5

KC, LA, LH, LC, MA, MH, MX, MG, MJ, NC, NX, PG, PJ

800 A

T(300 V)

PG, PJ, PL

T(600 V)

KA, KH, KC, LA, LH, MA, MH, MX, MG, MJ, NA, NC, NX, PG, PJ, PL

L

KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG, PJ, PL

1200 A

L

KC, LC, MA, MH, MX, MG, MJ, NA, NC, NX, PG, PJ, PL

600

100,000

30 A

CC

HG, JG (Molded Case Switches)

200 A

J

HD, HG, HJ, HL, JD, JG, JJ, JL

400 A

J, T (600 V)

HJ, HL, JJ, JL

  • The fuse used in this UL test is an envelope (umbrella) fuse. This fuse is designed as a “worst case’’ fuse. Thus, no matter what manufacturer’s fuse is used, the

    Square D
    brand circuit breaker is protected.

  • The line side fused switch may be in a separate enclosure or in the same enclosure as the loadside breaker. A line side fused switch may be a submain, integral main, or remote main. A load side breaker may be a branch, submain, or an integral main used on the load side of a remote main. This series combination short circuit current rating shall not exceed that of the line side fused switch. The charts apply to Square D brand load side breakers only. However, the line side fuse ratings are independent of the fuse manufacturer.

  • Not applicable to Corner Grounded Systems.

  • Limiters used in Square D brand DSL and DSL II fused power circuit breakers are not class L fuses and do not have series ratings.

Footnotes

  1. For indicated circuit breakers rated less than this maximum voltage. The indicated short circuit current rating also applies, but at the voltage rating of the circuit breaker.
  2. LG, LJ, and LL are only available in 3-pole configurations.