I-Line Merchandised Panelboard Accessories

Refer to Catalog 2110CT9701

I-Line Merchandised Panelboard Accessories

Blank Fillers

Equipment Ground Bar

Solid Neutral

I-Line Merchandised Panelboard Accessories

 

Description

Catalog No.

Blank Filler Kit—1.5 in.[1] (One kit contains quantity of 3 blank fillers.)

HNM1BL

Blank Filler Kit—4.5 in.[1] (One kit contains quantity of 5 blank fillers.)

HNM4BL

Solid Neutral Assemblies

 

225 A

HC2SN

400 A

HC4SN  [2], HCW4SN  [3]

600 A

HC6SN  [2], HCW6SN  [3]

800 A

HC8SN  [2], HCW8SN  [3]

HCPSU8SN [4]

HCPSU8SNCW[4]

1200 A

HCW12SN [3]

1200 A, for use with HCR-U universal panel only

HCWM12SN [5]

1200 A, including neutral Current Transformer (CT) for 3Ø4W systems

HCR12SNCTW [5]

Equipment Ground Bar Kits—HCJ, HCP, HCP-SU (single row), HCR-U

PK32DGTA

Blank Extensions (For replacement purposes)

1.5 in. for mounting on wide side of I-Line panelboard used with HNM1BL and HNM4BL as a filler plate on the wide side of the panel (HCP, HCP-SU and HCRU). Do not use with MicroLogic trip unit as this filler will cover the trip unit. [1]

HLW1BL
(Kit contains quantity of 3.)

4.5 in. for mounting on wide side of I-Line panelboard used with HNM1BL and HNM4BL as a filler plate on the wide side of the panel (HCP, HCP-SU and HCRU). Do not use with MicroLogic trip unit as this filler will cover the trip unit. [1]

HLW4BL
(Kit contains quantity of 5.)

1.5 in. for mounting on narrow side of I-Line panelboard used with HNM1BL and HNM4BL as a filler plate on the narrow side of the panel. Do not use with MicroLogic trip unit as this filler will cover the trip unit. [1]

HLN1BL
(Kit contains quantity of 3.)

4.5 in. for mounting on narrow side of I-Line panelboard used with HNM1BL and HNM4BL as a filler plate on the narrow side of the panel. Do not use with MicroLogic trip unit as this filler will cover the trip unit. [1]

HLN4BL
(Kit contains quantity of 5.)

4.5 in. for mounting on wide side of I-Line panelboard. For use with PowerPacT H and J circuit breakers mounted on the wide side of the panel so that electronic trip unit can be accessed. [1]

HLW4EBL
(Kit contains quantity of 5.)

4.5 in. for mounting on narrow side of I-Line panelboard. For use with PowerPacT H and J circuit breakers mounted on the narrow side of the panel so that electronic trip unit can be accessed. [1]

HLN4EBL
(Kit contains quantity of 5.)

Blank Extensions

Application

Circuit Breaker Mounting Ht.

Branch Circuit Side

Catalog Number

All applications, except PowerPacT H/J with MicroLogic trip unit 3, 5 and 6

1.5 in.

Wide Side

HLW1BL

4.5 in.

HLW4BL

All applications, except PowerPacT H/J with MicroLogic trip unit 3, 5 and 6

1.5 in.

Narrow Side

HLN1BL

4.5 in.

HLN4BL

Only PowerPacT H/J circuit breakers with MicroLogic trip unit 3, 5 and 6

4.5 in.

Narrow Side

HLN4EBL

Only PowerPacT H/J circuit breakers with MicroLogic trip unit 3, 5 and 6

4.5 in.

Wide Side

HLW4EBL

UL Service Entrance Barriers for I-Line Panelboards with Backfeed Main Circuit Breaker [6]

I-Line Panelboard Type

Backfeed Main Circuit Breaker

Catalog Number [7]

HCJ H, J ILBFMHCJHULC
HCP H, J ILBFMHCPHJULC
LA, LH, PowerPacT L ILBFMHCPLULC
M, P ILBFMHCPMPULC
HCR LA, LH, PowerPacT L ILBFMHCRLULC
M ILBFMHCRMULC
P ILBFMHCRPULC
R ILBFMHCRRULC
(NOTE: Barriers are required by 2017 version of NFPA70—National Electric Code. Both the 2017 UL67 and 2017 NFPA70 allow an exception for service entrance panelboards with more than one disconnect.)

UL Service Entrance Barrier Kits for I-Line Vertical Mounted Mains [6]

Main Circuit Breaker

Determining Factors

Catalog Number [7]

MG, MJ 4 wires per phase
(for breakers with AL1200P24K or CU1200P24K lug kit)
ILMLC4W
3 wires per phase
(for breakers with AL80023K or CU80023K lug kit)
ILMLC3W
2 wires per phase
(for breakers with AL800P6K or AL800P7K lug kit)
ILMLC2W
PowerPacT L All instances PPLLC
LA/LH All instances LALLC
(NOTE: Barriers are required by 2017 version of NFPA70—National Electric Code)

Solid Neutral Lug Quantities and Sizes

Solid Neutral Assembly Terminal Wire Range
HC2SN (1) 6 - 300, (9) #1/0 - 14, (45) #4 - 14
HC4SN (7) 6 - 350, (45) #4 - 14
HC6SN (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HC8SN (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCPSU8SN (4) 3/0 - 600, (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14,
HCW4SN (2) 4 - 600, (7) 6 - 350, (45) #4 - 14
HCW6SN (4) 3/0 - 750, (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCW8SN (4) 3/0 - 750, (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCW12SN (4) 3/0 - 750, (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCWM12SN (4) 3/0 - 750, (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HC6SNALCU (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HC8SNALCU (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCPSU8SNALCU (4) 3/0 - 600, (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCP4SNALCU (2) 4 - 600, (7) 6 - 350, (45) #4 - 14
HCP6SNALCU (4) 3/0 - 750, (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCP8SNALCU (4) 3/0 - 750, (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCP12SNALCU (4) 3/0 - 750, (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCR12SNALCU (4) 3/0 - 750, (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HC6SNCU (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HC8SNCU (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCPSU8SNCU (4) 3/0 - 600, (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14,
HCW4SNCU (2) 2 - 600, (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCW6SNCU (2) 2 - 600, (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCW8SNCU (4) 3/0 - 750, (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCP12SNCU (4) 3/0 - 750, (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCW12SNCU (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCR12SNCU (4) 3/0 - 750, (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCR2SNCTW (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCR2SNCTWALCU (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCR2SNCTWCU (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCR12SNCTW (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCR12SNCTWALCU (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCR12SNCTWCU (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCPSU2SNCTW (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCPSU2SNCTWALCU (7) 6 - 350, (9) #1/0 - 14, (34) #4 - 14
HCPSU2SNCTWCU (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCPSU8SNCW (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCPSU12SNCTWALCU (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCPSU12SNCTWCU (7) 6 - 350, (9) #1/0 - 14, (28) #4 - 14
HCP16NALCU (35) 350, (9) #1/0 - 14, (17) #4 - 14
HCR24NALCU (8) 750, (21) 350, (9) #1/0 - 14, (17) #4 - 14
HCPSU16NALCU (8) 750, (21) 350, (9) #1/0 - 14, (17) #4 - 14

Panelboard Adapter Kits

Crimp Lug Adapter Kits [8]

I-Line Panelboard Type

HCJ

HCP, HCR-U [9]

400 A

HCM400VCA

HCW400VCA

600 A

HCM600VCA

HCW600VCA

800 A

HCM800VCA

HCW800VCA

1200 A

HCW1200VCA

Type 3R/5/12 Enclosures

Catalog Number

Interior Type

Dimensions (In.)

H

W

D

HC4250WP

HCP

50

42

12.95

HC4259WP 

HCP

59

42

12.95

HC4268WP

HCP

68

42

12.95

HC4286WP

HCP

86

42

12.95

HC4486WP

HCR-U

86

44

14.50

Box Extensions

 

Catalog Number

Interior Type

Extension

HC2609DEX (F or S)

HCP-SU

 9 in.

HC3209EX (F or S)

HCJ

 9 in.

HC4212DEX (F or S)

HCP

12 in.

HC4406DEX (F or S)

HCR-U

 6 in.

HC4412DEX (F or S)

HCR-U

12 in.

I-Line/QMB PanelBoard Drip Hood Kits
The Drip Hoods listed below are intended for use on surface mounted HC and QMB boxes only. Select the appropriate Drip Hood based on Interior Type, Width, and Depth from the following table. The Drip Hoods are designed to fit on the outside of the boxes. The Drip Hood will increase the enclosure rating of the box from Type 1 to Type 2. Reference Instruction Bulletin 80043-401-03.

Catalog Number Interior Type Dimensions (In.)
Width Depth
HCT2DH32D9 HCJ 32 9.5
HCT2DH42 HCP 42 9.5
HCT2DH26D9 HCP-SU 26 9.5
HCT2DH47 HCP (L5) 47 9.5
HCT2DH56 HCP (PL) 56 9.5
HCT2DH42D12 HCP (DB) 42 12.5
HCT2DH44 HCR-U 44 9.5
HCT2DH49 HCR-U (L5) 49 9.5
HCT2DH58 HCR-U (PL) 58 9.5
HCT2DH44D12 HCR-U (DB) 44 12.5
QMT2DH38 QMB 38 11.5
  1. Box Types noted with (PL) are standard width boxes with an additional 14 in. PowerLogic extension.

  2. Box Types noted with (L5) are standard width boxes with an additional 5 in. side extension.

  3. Box Types noted with (DB) have additional box depth.

Sub-feed Lug Kits

Sub-feed Lug Kits  [10] [11] [12]

Ampere

Rating

Height

Catalog

Number

Max. Short Circuit System Ratings

RMS Symmetrical Amperes

Protected by

Circuit Breaker

For Use in I-Line

Panelboard Types

In.

(mm)

240 Vac

480 Vac

600 Vac

 250 A

4.5

114

SL250

200,000

200,000

100,000

FA, FD, FG, FH, FJ, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, KI

HCJ, HCP, HCP-SU, HCR-U

 400 A

6

152

SL400  [12]

200,000

200,000

100,000

HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, LA, LH,, DG, DJ, DL, LG, LJ, LL, LR (“L” & “D” FRAME
400 A MAX.)

HCP, HCP-SU, HCR-U (wide side only)

 800 A

9

229

SL800M5

125,000

100,000

25,000

FA, FD, FG, FH, FJ, KA, KH, KC, KI, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, MA, MH, MX, MG, PG, MJ, PJ, PK, PL, DG, DJ, DL, LG, LJ, LL, LR

HCJ, HCP, HCP-SU, HCR-U

1200 A

15

381

S33930

125,000

100,000

50,000

FA, FD, FG, FH, FJ, KA, KH, KC, KI, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, LA, LH, LC, LI, MA, MH, MX, NA, NC, NX, MG, PG, MJ, PJ, PK, PL, RG, RJ, RL, RK, DG, DJ, DL, LG, LJ, LL, LR

HCR-U

1200 A

9

229

SL1200P5, SL1200P6, SL1200P7

125,000

100,000

50,000

FA, FD, FG, FH, FJ, KA, KH, KC, KI, HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, MG, PG, MJ, PJ, PK, PL, RG, RJ, RL, RK, DG, DJ, DL, LG, LJ, LL, LR

HCP, HCP-SU, HCR-U


note

S33930, S33931, SL1200P5, SL1200P6, SL1200P7, SL Kits are rated 1200 A and may be applied to 1200 ampere loads when installed into HCRU panelboards. However, when installed into HCP and HCPSU panelboards they are only rated 800 amperes maximum due to restricted wire bending space.

Sub-feed Lug kit terminal data

Catalog No. (Prefix)

No. Poles

Ampere Rating

Standard Lug Wire Size  [13]

SL100

3

 100

#14–1/0 AWG Cu or #12–1/0 AWG Al

SL250

3

 250

(1) #4 AWG–300 kcmil

SL400

3

 400

(1) #1 AWG–600 kcmil or 2– #1 AWG–250 kcmil

SL800M5

3

 800

(3) #3/0 AWG–500 kcmil

S33930

3

1200

(4) #3/0 AWG–600 kcmil

SL1200P5

3

1200

(4) #3/0 AWG–500 kcmil

SL1200P6

3

1200

(3) 350–600 kcmil

SL1200P7

3

1200

(3) #3/0 AWG–750 kcmil

Footnotes

  1. Blank extension and blank filler pricing is per kit. See note on kit number for number included in each kit.
  2. Used on Type HCJ.
  3. Used on 400 A, 600 A, 800 A, and 1200 A HCP (main lugs), and 600 A and 800 A (main circuit breaker).
  4. Used on Type HCP-SU (single row).
  5. Used on Type HCR-U.
  6. For US only.
  7. For panelboards manufactured after 1 January 2017.
  8. For use with MLO panel, order VCEL lugs seperately.
  9. Not for use with P- or R-frame circuit breakers or sub-feed kits S33930 or S33931.
  10. Plug-on in same manner as a branch circuit breaker
  11. For other ratings, see the latest edition of I-Line Information Manual, #80043-309-xx.
  12. SL400 cannot be used in HCJ panelboards due to inadequate wire bending space.
  13. Unless otherwise specified, wire sizes apply to both aluminum and copper conductors.

Was this helpful?