Molded Case Circuit Breakers for I-Line Panelboards
Refer to I-Line Power Distribution Panelboards
PowerPacT™ B-frame, Thermal Magnetic
Accessories are located in Section 7 PowerPacT Accessories.
B-frame Interrupting Ratings
Interrupting Rating |
||||
D |
G |
J |
K |
|
240 Vac | 25 kA | 65 kA | 100 kA | 100 kA |
480/277 Vac | 18 kA | 35 kA | 65 kA | 65 kA |
480 Vac | 18 kA | 35 kA | 65 kA | 65 kA |
600Y/347 Vac | 14 kA | 18 kA | 25 kA | 65 kA |
1P 125 Vdc | 10 kA | 20 kA | 50 kA | — |
2–3P 250 Vdc | 10 kA | 20 kA | 50 kA | — |
PowerPacT B-frame, 125 A max, Thermal Magnetic UL Circuit Breaker
(PowerPacT B-frame 1–pole
branch circuit breakers utilize 1.5 in. of I-Line mounting space,
2–pole branch circuit breakers utilize 3 in. of I-Line mounting
space and 3–pole B-frame circuit breakers utilize 4.5 in. of
I-Line mounting space.) Refer to Phase Options Suffix Numbers for B/Q-frame Circuit Breakers Example for phase options and suffix information.
D - SCCR |
|||||
1-pole |
2-pole |
3-pole |
Fixed AC Magnetic Trip |
||
Amps |
277 Vac |
480/277 Vac |
480/277 Vac |
Hold |
Trip |
15 | BDA14015 | BDA24015Y | BDA34015Y | 400 A | 600 A |
20 | BDA14020 | BDA24020Y | BDA34020Y | 400 A | 600 A |
25 | BDA14025 | BDA24025Y | BDA34025Y | 400 A | 600 A |
30 | BDA14030 | BDA24030Y | BDA34030Y | 400 A | 600 A |
35 | BDA14035 | BDA24035Y | BDA34035Y | 400 A | 600 A |
40 | BDA14040 | BDA24040Y | BDA34040Y | 400 A | 600 A |
45 | BDA14045 | BDA24045Y | BDA34045Y | 400 A | 600 A |
50 | BDA14050 | BDA24050Y | BDA34050Y | 480 A | 720 A |
60 | BDA14060 | BDA24060Y | BDA34060Y | 640 A | 960 A |
70 | BDA14070 | BDA24070Y | BDA34070Y | 640 A | 960 A |
80 | BDA14080 | BDA24080Y | BDA34080Y | 800 A | 1200 A |
90 | BDA14090 | BDA24090Y | BDA34090Y | 1000 A | 1500 A |
100 | BDA14100 | BDA24100Y | BDA34100Y | 1000 A | 1500 A |
110 | BDA14110 | BDA24110Y | BDA34110Y | 1000 A | 1500 A |
125 | BDA14125 | BDA24125Y | BDA34125Y | 1000 A | 1500 A |
G - SCCR |
|||||
1-pole |
2-pole |
3-pole |
Fixed AC Magnetic Trip |
||
Amps |
277 Vac |
480/277 Vac |
480/277 Vac |
Hold |
Trip |
15 | BGA14015 | BGA24015Y | BGA34015Y | 400 A | 600 A |
20 | BGA14020 | BGA24020Y | BGA34020Y | 400 A | 600 A |
25 | BGA14025 | BGA24025Y | BGA34025Y | 400 A | 600 A |
30 | BGA14030 | BGA24030Y | BGA34030Y | 400 A | 600 A |
35 | BGA14035 | BGA24035Y | BGA34035Y | 400 A | 600 A |
40 | BGA14040 | BGA24040Y | BGA34040Y | 400 A | 600 A |
45 | BGA14045 | BGA24045Y | BGA34045Y | 400 A | 600 A |
50 | BGA14050 | BGA24050Y | BGA34050Y | 480 A | 720 A |
60 | BGA14060 | BGA24060Y | BGA34060Y | 640 A | 960 A |
70 | BGA14070 | BGA24070Y | BGA34070Y | 640 A | 960 A |
80 | BGA14080 | BGA24080Y | BGA34080Y | 800 A | 1200 A |
90 | BGA14090 | BGA24090Y | BGA34090Y | 1000 A | 1500 A |
100 | BGA14100 | BGA24100Y | BGA34100Y | 1000 A | 1500 A |
110 | BGA14110 | BGA24110Y | BGA34110Y | 1000 A | 1500 A |
125 | BGA14125 | BGA24125Y | BGA34125Y | 1000 A | 1500 A |
J - SCCR |
|||||
1-pole |
2-pole |
3-pole |
Fixed AC Magnetic Trip |
||
Amps |
347 Vac |
600Y/347 Vac |
600Y/347 Vac |
Hold |
Trip |
15 | BJA16015 | BJA26015 | BJA36015 | 400 A | 600 A |
20 | BJA16020 | BJA26020 | BJA36020 | 400 A | 600 A |
25 | BJA16025 | BJA26025 | BJA36025 | 400 A | 600 A |
30 | BJA16030 | BJA26030 | BJA36030 | 400 A | 600 A |
35 | BJA16035 | BJA26035 | BJA36035 | 400 A | 600 A |
40 | BJA16040 | BJA26040 | BJA36040 | 400 A | 600 A |
45 | BJA16045 | BJA26045 | BJA36045 | 400 A | 600 A |
50 | BJA16050 | BJA26050 | BJA36050 | 480 A | 720 A |
60 | BJA16060 | BJA26060 | BJA36060 | 640 A | 960 A |
70 | BJA16070 | BJA26070 | BJA36070 | 640 A | 960 A |
80 | BJA16080 | BJA26080 | BJA36080 | 800 A | 1200 A |
90 | BJA16090 | BJA26090 | BJA36090 | 1000 A | 1500 A |
100 | BJA16100 | BJA26100 | BJA36100 | 1000 A | 1500 A |
110 | BJA16110 | BJA26110 | BJA36110 | 1000 A | 1500 A |
125 | BJA16125 | BJA26125 | BJA36125 | 1000 A | 1500 A |
Refer to I-Line Power Distribution Panelboards
I-Line HQO Accessory
For phase option information see Phase Options Suffix Numbers for B/Q-frame Circuit Breakers.
QO™ Distribution Panel—240 Vac Max. Only Mounts in Type HCJ, HCP, HCP-SU, or HCR-U I-Line panelboards, 30 A max. branch circuit breaker.
Maximum No. 1-pole QO Circuit Breakers |
Phase Connection |
Mounting Height |
2-pole Catalog Number |
3-pole Catalog Number |
|
---|---|---|---|---|---|
In. |
mm |
||||
6 |
AB |
4.5 |
114 |
— |
|
6 |
BC |
4.5 |
114 |
— |
|
6 |
AC |
4.5 |
114 |
— |
|
6 |
ABC |
4.5 |
114 |
— |
|
6 |
CBA |
4.5 |
114 |
— |
Phase Options Suffix Numbers for B/Q-frame Circuit Breakers
Phase |
Phase Connection |
1-pole |
2-pole |
3-pole |
---|---|---|---|---|
1 |
A |
BDA140151 |
— |
— |
3 |
B |
BDA140153 |
— |
— |
5 |
C |
BDA140155 |
— |
— |
1 |
AB |
— |
QBA220701 |
— |
2 |
AC |
— |
QBA220702 |
— |
3 |
BA |
— |
QBA220703 |
— |
4 |
BC |
— |
QBA220704 |
— |
5 |
CA |
— |
QBA220705 |
— |
6 |
CB |
— |
QBA220706 |
— |
Standard [1] |
ABC |
— |
— |
QBA32070 |
6 |
CBA |
— |
— |
QBA320706 |
Refer to I-Line Power Distribution Panelboards
PowerPacT Q-frame for I-Line™ Panelboards and Switchboards
PowerPacT™ Q-frame— 225 A, Thermal-magnetic
(240 Vac)
(PowerPacT
Q-frame 2–pole branch circuit breakers utilize 3 in. of I-Line
mounting space and 3–pole Q-frame circuit breakers utilize
4.5 in. of I-Line mounting space.)
Ampere |
AC Magnetic |
"B" Interrupting |
"D" Interrupting |
"G" Interrupting |
"J" Interrupting[2] |
|
---|---|---|---|---|---|---|
Hold |
Trip |
Catalog Number |
Catalog Number |
Catalog Number |
Catalog Number |
|
2-pole, 240 Vac [3]. |
||||||
70 A |
1000 |
1800 |
QBA22070( ) |
QDA22070( ) |
QGA22070( ) |
QJA22070( ) |
80 A |
QBA22080( ) |
QDA22080( ) |
QGA22080( ) |
QJA22080( ) |
||
90 A |
QBA22090( ) |
QDA22090( ) |
QGA22090( ) |
QJA22090( ) |
||
100 A |
1200 |
2400 |
QBA22100( ) |
QDA22100( ) |
QGA22100( ) |
QJA22100( ) |
110 A |
QBA22110( ) |
QDA22110( ) |
QGA22110( ) |
QJA22110( ) |
||
125 A |
QBA22125( ) |
QDA22125( ) |
QGA22125( ) |
QJA22125( ) |
||
150 A |
QBA22150( ) |
QDA22150( ) |
QGA22150( ) |
QJA22150( ) |
||
175 A |
QBA22175( ) |
QDA22175( ) |
QGA22175( ) |
QJA22175( ) |
||
200 A |
QBA22200( ) |
QDA22200( ) |
QGA22200( ) |
QJA22200( ) |
||
225 A |
QBA22225( ) |
QDA22225( ) |
QGA22225( ) |
QJA22225( ) |
||
3-pole, 240 Vac [4] |
||||||
70 A |
1000 |
1800 |
QBA32070( ) |
QDA32070( ) |
QGA32070( ) |
QJA32070( ) |
80 A |
QBA32080( ) |
QDA32080( ) |
QGA32080( ) |
QJA32080( ) |
||
90 A |
QBA32090( ) |
QDA32090( ) |
QGA32090( ) |
QJA32090( ) |
||
100 A |
1200 |
2400 |
QBA32100( ) |
QDA32100( ) |
QGA32100( ) |
QJA32100( ) |
110 A |
QBA32110( ) |
QDA32110( ) |
QGA32110( ) |
QJA32110( ) |
||
125 A |
QBA32125( ) |
QDA32125( ) |
QGA32125( ) |
QJA32125( ) |
||
150 A |
QBA32150( ) |
QDA32150( ) |
QGA32150( ) |
QJA32150( ) |
||
175 A |
QBA32175( ) |
QDA32175( ) |
QGA32175( ) |
QJA32175( ) |
||
200 A |
QBA32200( ) |
QDA32200( ) |
QGA32200( ) |
QJA32200( ) |
||
225 A |
QBA32225( ) |
QDA32225( ) |
QGA32225( ) |
QJA32225( ) |
||
See [5] below. |
Interrupt Ratings (kA)
QB |
QD |
QG |
QJ [2] |
|
---|---|---|---|---|
240 V |
10 |
25 |
65 |
100 |
480 V |
— |
— |
— |
— |
600 V |
— |
— |
— |
— |
Padlock attachments for Q-frame are available.
Refer to I-Line Power Distribution Panelboards
H- and J-frame for I-Line™ Panelboards and Switchboards
HD/HG/HJ/HL/HR |
JD/JG/JJ/JL/JR 2- and 3-pole Thermal-Magnetic Trip Unit |
H-frame 150 A Thermal-Magnetic UL Current-Limiting[6] Circuit Breakers (600 Vac, 250 Vdc) With
Factory Sealed Trip Unit[7] Suitable
for Reverse Connection[7]
(PowerPacT HD and
HG 2–pole circuit breakers utilize 3 in. of I-Line mounting
space, HJ and HL 2–pole circuit breakers utilize 4.5 in. of
I-Line mounting space, all 3–pole H and J-frame circuit breakers
utilize 4.5 in. of I-Line mounting space.)
Current |
Fixed AC Magnetic |
Cat. No. [8] |
Terminal |
|
---|---|---|---|---|
Hold |
Trip |
|||
H-frame, 150A 2P, 600 Vac 50/60 Hz, 250 Vdc[9] |
||||
15 A |
350 A |
750 A |
H( )A26015( ) |
AL150HD 14–3/0 AWG Al or Cu |
20 A |
350 A |
750 A |
H( )A26020( ) |
|
25 A |
350 A |
750 A |
H( )A26025( ) |
|
30 A |
350 A |
750 A |
H( )A26030( ) |
|
35 A |
400 A |
850 A |
H( )A26035( ) |
|
40 A |
400 A |
850 A |
H( )A26040( ) |
|
45 A |
400 A |
850 A |
H( )A26045( ) |
|
50 A |
400 A |
850 A |
H( )A26050( ) |
|
60 A |
800 A |
1450 A |
H( )A26060( ) |
|
70 A |
800 A |
1450 A |
H( )A26070( ) |
|
80 A |
800 A |
1450 A |
H( )A26080( ) |
|
90 A |
800 A |
1450 A |
H( )A26090( ) |
|
100 A |
800 A |
1700 A |
H( )A26100( ) |
|
110 A |
900 A |
1700 A |
H( )A26110( ) |
|
125 A |
900 A |
1700 A |
H( )A26125( ) |
|
150 A |
900 A |
1700 A |
H( )A26150( ) |
|
H-frame 150A 3P, 600 Vac 50/60 Hz, 250 Vdc |
||||
15 A |
350 A |
750 A |
H( )A36015 |
AL150HD 14–3/0 AWG Al or Cu |
20 A |
350 A |
750 A |
H( )A36020 |
|
25 A |
350 A |
750 A |
H( )A36025 |
|
30 A |
350 A |
750 A |
H( )A36030 |
|
35 A |
400 A |
850 A |
H( )A36035 |
|
40 A |
400 A |
850 A |
H( )A36040 |
|
45 A |
400 A |
850 A |
H( )A36045 |
|
50 A |
400 A |
850 A |
H( )A36050 |
|
60 A |
800 A |
1450 A |
H( )A36060 |
|
70 A |
800 A |
1450 A |
H( )A36070 |
|
80 A |
800 A |
1450 A |
H( )A36080 |
|
90 A |
800 A |
1450 A |
H( )A36090 |
|
100 A |
800 A |
1700 A |
H( )A36100 |
|
110 A |
900 A |
1700 A |
H( )A36110 |
|
125 A |
900 A |
1700 A |
H( )A36125 |
|
150 A |
900 A |
1700 A |
H( )A36150 |
Interrupting Ratings Codes (kA)
Voltage |
D |
G |
J |
L |
R |
---|---|---|---|---|---|
240 V |
25 |
65 |
100 |
125 |
200 |
480Y/277 |
18 |
35 |
65 |
100 |
200 |
480 V |
18 |
35 |
65 |
100 |
200 |
600Y/347 |
14 |
18 |
25 |
50 |
100 |
600 V |
14 |
18 |
25 |
50 |
100 |
J-frame 250 A Thermal-Magnetic UL Current-Limiting[10]Circuit Breakers (600 Vac, 250 Vdc) With
Factory Sealed Trip Unit[7] Suitable for Reverse Connection[7]
(All PowerPacT J-frame circuit breakers, both 2–
and 3–pole, utilize 4.5 in. of I-Line mounting space.)
Current |
Adjustable AC Magnetic |
Cat. No.[8] |
Terminal |
|
Low |
High |
|||
J-frame 250A 2P, 600 Vac 50/60 Hz, 250 Vdc[11]. |
||||
150 A |
750 A |
1500 A |
J( )A26150( ) |
AL175JD |
175 A |
875 A |
1750 A |
J( )A26175( ) |
|
200 A |
1000 A |
2000 A |
J( )A26200( ) |
AL250JD 3/0 AWG–350 kcmil |
225 A |
1125 A |
2250 A |
J( )A26225( ) |
|
250 A |
1250 A |
2500 A |
J( )A26250( ) |
|
J-frame 250A 3P, 600 Vac 50/60 Hz, 250 Vdc |
||||
150 A |
750 A |
1500 A |
J( )A36150 |
AL175JD 4–4/0 AWG Al or Cu |
175 A |
875 A |
1750 A |
J( )A36175 |
|
200 A |
1000 A |
2000 A |
J( )A36200 |
AL250JD 3/0 AWG–350 kcmil |
225 A |
1125 A |
2250 A |
J( )A36225 |
|
250 A |
1250 A |
2500 A |
J( )A36250 |
HDA36250U33X 2- and 3-pole MicroLogic Electronic Trip Unit |
JDA36250U44X 2- and 3-pole MicroLogic Electronic Trip Unit |
H-frame 150 A and J-frame 250 A MicroLogic Electronic Trip
UL Current-Limiting[10]Circuit Breakers
(600 Vac)
With Factory Sealed Trip Unit[7] Suitable for Reverse Connection [12]
(PowerPacT Electronic Trip H- and J-frame circuit
breakers utilize 4.5 in. of I-Line mounting space.)
Electronic Trip Unit |
Sensor Rating |
Cat. No.[8] |
Terminal |
||
---|---|---|---|---|---|
Type |
Function |
Trip Unit |
|||
600 Vac, 50/60 Hz, 3P |
|||||
MicroLogic |
LI |
3.2[13] |
60 A |
H( )A36060U31X |
AL150HD[14] |
100 A |
H( )A36100U31X |
||||
150 A |
H( )A36150U31X |
||||
250 A |
J( )A36250U31X |
AL250JD[15] |
|||
LSI |
3.2S[13] |
60 A |
H( )A36060U33X |
AL150HD[14] |
|
100 A |
H( )A36100U33X |
||||
150 A |
H( )A36150U33X |
||||
250 A |
J( )A36250U33X |
AL250JD[15] |
|||
MicroLogic Ammeter |
LSI |
5.2A |
60 A |
H( )A36060U43X |
AL150HD[14] |
100 A |
H( )A36100U43X |
||||
150 A |
H( )A36150U43X |
||||
250 A |
J( )A36250U43X |
AL250JD[15] |
|||
MicroLogic Energy |
LSI |
5.2E |
60 A |
H( )A36060U53X |
AL150HD[14] |
100 A |
H( )A36100U53X |
||||
150 A |
H( )A36150U53X |
||||
250 A |
J( )A36250U53X |
AL250JD[15] |
|||
MicroLogic |
LSIG |
6.2A |
60 A |
H( )A36060U44X |
AL150HD[14] |
100 A |
H( )A36100U44X |
||||
150 A |
H( )A36150U44X |
||||
250 A |
J( )A36250U44X |
AL250JD[15] |
|||
MicroLogic |
LSIG |
6.2E |
60 A |
H( )A36060U54X |
AL150HD[14] |
100 A |
H( )A36100U54X |
||||
150 A |
H( )A36150U54X |
||||
250 A |
J( )A36250U54X |
AL250JD[15] |
Interrupting Ratings Codes (kA)
Voltage |
D |
G |
J |
L |
R |
---|---|---|---|---|---|
240 V |
25 |
65 |
100 |
125 |
200 |
480 V |
18 |
35 |
65 |
100 |
200 |
600 V |
14 |
18 |
25 |
50 |
100 |
Refer to I-Line Power Distribution Panelboards
J-frame Mission Critical Circuit Breaker
J-frame 250 A MicroLogic Electronic Trip Mission Critical Circuit Breakers (480/277 Vac) With Factory Sealted Trip Units Suitable for Reverse Connection[16]
Electronic Trip |
Trip Function |
Trip Unit |
Continuous Current |
D Interrupting |
G Interrupting |
J Interrupting |
L Interrupting |
Terminal |
---|---|---|---|---|---|---|---|---|
Cat. No. |
Cat. No. |
Cat. No. |
Cat. No. |
|||||
Standard |
LI |
3.2 W |
250 |
|||||
Standard |
LSI |
3.2S-W |
250 |
|||||
High Perf. Ammerter |
LSI |
5.2A-W |
250 |
|||||
High Perf. Energy |
LSI |
5.2E-W |
250 |
|||||
High perf. Ammerter |
LSIG |
6.2A-W |
250 |
|||||
High Perf. Energy |
LSIG |
6.2E-W |
250 |
L-frame Mission Critical Circuit Breaker
L-frame 600 A MicroLogic Electronic Trip Mission Critical Circuit Breakers (480/277 Vac) With Factory Sealed Trip Units Suitable for Reverse Connection[16]
Electronic Trip |
Trip Function |
Trip Unit |
Continuous Current |
G Interrupting |
J Interrupting |
L Interrupting |
Terminal |
Cat. No. |
Cat. No. |
Cat. No. |
|||||
Standard |
LI |
3.3 W |
250 |
||||
400 |
|||||||
600 |
|||||||
Standard |
LSI |
3.3S-W |
250 |
||||
400 |
|||||||
600 |
|||||||
High Perf. Ammeter |
LSI |
5.3A-W |
400 |
||||
600 |
|||||||
High Perf. Energy |
LSI |
5.3E-W |
400 |
||||
600 |
|||||||
High Perf. Ammeter |
LSIG |
6.3A-W |
400 |
||||
600 |
|||||||
High Perf. Energy |
LSIG |
6.3E-W |
400 |
||||
600 |
PowerPacT™ H-, J-, and L-frame Automatic Molded Case Switches, 600 Vac
Circuit Breaker |
Poles |
Ampere Rating |
G Withstand |
L Withstand |
R Withstand |
Terminal |
Wire Range |
|||
---|---|---|---|---|---|---|---|---|---|---|
Cat. No. |
Trip Point |
Cat. No. |
Trip Point |
Cat. No. |
Trip Point |
|||||
H-frame J-frame |
2[20] |
150 A |
HGA26000S15( ) |
2250 A |
2250 A |
— |
— |
— |
— |
|
175 A |
JGA26000S17( ) |
3125 A |
3125 A |
— |
— |
— |
— |
|||
250 A |
JGA26000S25( ) |
3125 A |
3125 A |
— |
— |
— |
— |
|||
3 |
150 A |
2250 A |
2250 A |
2250 A |
AL150HD |
14 AWG–3/0 AWG Al/Cu |
||||
175 A |
3125 A |
3125 A |
3125 A |
AL175JD |
4–4/0 AWG Al/Cu |
|||||
250 A |
3125 A |
3125 A |
3125 A |
AL250JD |
3/0 AWG–350 kcmil Al/Cu |
|||||
L-frame |
3 |
400 A |
4800 A |
4800 A |
4800 A |
AL150HD |
AL600LS52K3 (2) 2/0 AWG–500 kcmil Al/Cu |
|||
600 A |
6600 A |
6600 A |
6600 A |
AL250JD |
||||||
H-,
J-, and L-frame accessories starting on PowerPacT Accessories. |
Interrupting Ratings Codes (kA)
Voltage |
D |
G |
J |
L |
R |
---|---|---|---|---|---|
240 V |
25 |
65 |
100 |
125 |
200 |
480Y/277 |
18 |
35 |
65 |
100 |
200 |
480 V |
18 |
35 |
65 |
100 |
200 |
600Y/347 |
14 |
18 |
25 |
50 |
100 |
600 V |
14 |
18 |
25 |
50 |
100 |
H/J/L-Frame Circuit Breaker/Switch Phase Options—Example HDA26150( )
Phase Option |
Phase |
2-pole |
3-pole |
---|---|---|---|
1 |
AB |
HDA261501 |
— |
2 |
AC |
HDA261502 |
— |
3 |
BA |
HDA261503 |
— |
4 |
BC |
HDA261504 |
— |
5 |
CA |
HDA261505 |
— |
6 |
CB |
HDA261506 |
— |
Standard |
ABC |
— |
JDA34250WU31X |
6 |
CBA |
— |
JDA34250WU31X6 |
Refer to I-Line Power Distribution Panelboards
LA/LH-frame Thermal Magnetic Circuit Breakers
L-frame circuit breaker utilizes 6 in. of available I-Line bus
L-frame—400 A, Thermal-magnetic (600 Vac)
Ampere |
AC Magnetic |
Standard Interrupting |
High Interrupting |
Terminal |
|
---|---|---|---|---|---|
Low |
High |
Catalog Number |
Catalog Number |
||
2-pole, 600 Vac, 250 Vdc [21] |
|||||
125 A |
625 |
1250 |
LA26125( ) |
LH26125( ) |
AL400LA |
150 A |
750 |
1500 |
LA26150( ) |
LH26150( ) |
|
175 A |
875 |
1750 |
LA26175( ) |
LH26175( ) |
|
200 A |
1000 |
2000 |
LA26200( ) |
LH26200( ) |
|
225 A |
1125 |
2250 |
LA26225( ) |
LH26225( ) |
|
250 A |
1250 |
2500 |
LA26250( ) |
LH26250( ) |
|
300 A |
1500 |
3000 |
LA26300( ) |
LH26300( ) |
|
350 A |
1750 |
3500 |
LA26350( ) |
LH26350( ) |
|
400 A |
2000 |
4000 |
LA26400( ) |
LH26400( ) |
|
3-pole, 600 Vac, 250 Vdc |
|||||
125 A |
625 |
1250 |
AL400LA |
||
150 A |
750 |
1500 |
|||
175 A |
875 |
1750 |
|||
200 A |
1000 |
2000 |
|||
225 A |
1125 |
2250 |
|||
250 A |
1250 |
2500 |
|||
300 A |
1500 |
3000 |
|||
350 A |
1750 |
3500 |
|||
400 A |
2000 |
4000 |
LA circuit breaker accessories can be found in Supplemental Digest Section 3.
LA circuit breaker dimensions can be found in Digest Section 7.
Mechanical lug kits for LA, LH, and Q4 circuit breakers can be found in Supplemental Digest Section 3.
Interrupt Ratings (kA)
LA |
LH |
|
---|---|---|
240 V |
42 |
65 |
480 V |
30 |
35 |
600 V |
22 |
25 |
Refer to I-Line Power Distribution Panelboards
PowerPacT L- and M-frame for I-Line™ Panelboards and Switchboards
L-frame 600 A Circuit Breakers with Lugs and Factory-Sealed
Electronic Trip Units Suitable for Reverse Connection[22]
(L-frame circuit breaker utilizes 6
in. of available I-Line bus)
Electronic Trip Unit |
Sensor |
Catalog |
Terminal |
||
---|---|---|---|---|---|
Type |
Function |
Trip Unit |
|||
600 Vac, 53/60 Hz, 3P |
|||||
MicroLogic |
LI |
3.3[13] |
250 A |
L( )A36250U31X |
AL400L61K3[24] |
400 A 600 A |
L( )A36400U31X L( )A36600U31X |
AL600LF52K3[25] (2) 3/0–500 kcmil Al or Cu. |
|||
MicroLogic |
LSI |
3.3S[13] |
250 A |
L( )A36250U33X |
AL400L61K3[24] |
400 A 600 A |
L( )A36400U33X L( )A36600U33X |
AL600LF52K3 Al or Cu. |
|||
MicroLogic |
LSI |
5.3A |
400 A 600 A |
L( )A36400U43X L( )A36600U43X |
|
MicroLogic |
LSI |
5.3E |
400 A 600 A |
L( )A36400U53X L( )A36600U53X |
|
MicroLogic |
LSIG |
6.3A |
400 A 600 A |
L( )A36400U44X L( )A36600U44X |
|
MicroLogic |
LSIG |
6.3E |
400 A 600 A |
L( )A36400U54X L( )A36600U54X |
Interrupt Ratings Codes (kA) for PowerPacT L and M Frames
G |
J |
L [26] |
R |
|
---|---|---|---|---|
240 V |
65 |
100 |
125 |
200 |
480 V |
35 |
65 |
100 |
200 |
600 V |
18 |
25 |
50 |
100 |
M-Frame 800 A, Basic Electronic Trip System Type ET 1.0[27] Factory-Sealed Trip Unit
(PowerPacT M-frame circuit breakers utilize 9 in.
of the available I-Line bussing.)
Electronic Trip Unit |
Ampere |
Adjustable Instantaneous Trip Range |
Interrupting Rating |
Terminal Wire Range |
|||
---|---|---|---|---|---|---|---|
Type |
Function |
Low |
High |
G |
J |
||
2P, 600 Vac 50/60 Hz[28] |
|||||||
Basic |
Fixed Long-time, Adjustable Instantaneous Trip |
400 A |
800 |
4000 |
(3) 3/0 through 500 kcmil Al or Cu |
||
600 A | 1200 | 6000 |
(3) 3/0 through 500 kcmil Al or Cu |
||||
3P, 600 Vac 50/60 Hz |
|||||||
Basic | Fixed Long-time, Adjustable Instantaneous Trip | 400 A | 800 | 4000 |
(3) 3/0 through 500 kcmil Al or Cu |
||
600 A | 1200 | 6000 |
(3) 3/0 through 500 kcmil Al or Cu |
M-Frame 800 A, Adjustable Amperage Electronic Trip Unit
Electronic Trip Unit |
Adjustable Long-Time Settings |
Adjustable Instantaneous |
Interrupting Rating |
Terminal Wire Range |
|||
---|---|---|---|---|---|---|---|
Type |
Function |
Low |
High |
G |
J |
||
2P, 600 Vac 50/60 Hz[28] |
|||||||
Basic |
Adjustable Long-time, Adjustable Instantaneous Trip |
300–800 |
2x |
10x |
(3) 3/0 through 500 kcmil Al or Cu |
||
3P, 600 Vac 50/60 Hz |
|||||||
Basic |
Adjustable Long-time, Adjustable Instantaneous Trip |
300–800 | 2x | 10x |
(3) 3/0 through 500 kcmil Al or Cu |
L-frame accessories, see PowerPact Accessories in Section 7 of the Digest. L-frame dimensions, see Molded Case Circuit Breaker Dimensions in Section 7 of the Digest. L-frame optional lugs, see Mechanical Lugs in Section 7 of the Digest. |
M-frame accessories, see PowerPact Accessories in Section 7 of the Digest. M-frame dimensions, see Molded Case Circuit Breaker Dimensions in Section 7 of the Digest. M-frame optional lugs, see Mechanical Lugs in Section 7 of the Digest. |
Automatic Molded Case Switches—600 Vac, 50/60 Hz
Ampere |
2-pole |
3-pole |
Withstand Rating [29] |
Trip Point Amperes |
Terminal |
||
---|---|---|---|---|---|---|---|
Catalog Number [28] |
Catalog Number |
240 Vac |
480 Vac |
600 Vac |
AC |
||
600 A |
PJA26000S60( ) |
100 |
65 |
25 |
10000 |
(3) 3/0 through 500 kcmil Al or Cu |
|
800 A |
PJA26000S80( ) |
100 |
65 |
25 |
10000 |
||
1000 A |
PJA26000S10( ) |
100 |
65 |
25 |
10000 |
(4) 3/0 through 500 kcmil Al or Cu |
|
1200 A |
PJA26000S12( ) |
100 |
65 |
25 |
10000 |
PowerPacT P- and R-frame Interrupt Ratings Codes
Voltage |
P-frame Interrupt Rating |
R-frame Interrupt Rating |
||||||
---|---|---|---|---|---|---|---|---|
G |
J |
K |
L |
G |
J |
K |
L |
|
240 Vac |
65 kA |
100 kA |
65 kA |
125 kA |
65 kA |
100 kA |
65 kA |
125 kA |
480 Vac |
35 kA |
65 kA |
50 kA |
100 kA |
35 kA |
65 kA |
65 kA |
100 kA |
600 Vac |
18 kA |
25 kA |
50 kA |
25 kA |
18 kA |
25 kA |
65 kA |
50 kA |
Refer to Catalog 0612CT0101
PowerPacT P- and R-frame for I-Line™ Panelboards and Switchboards
PowerPacT P-frame 1200 A (600 Vac, 50/60 Hz) 3P Circuit Breaker
with Electronic Trip Unit
(PowerPacT P-frame circuit breakers utilize 9 in. of the available
I-Line bussing.)
Electronic Trip Unit |
Sensor Rating |
Terminal Wire Range |
|||
---|---|---|---|---|---|
Type |
Function |
Code |
|||
Basic Electronic Trip Unit (Not Interchangeable) |
Fixed long-time, |
ET1.0I |
600 A |
P( )A36060 |
(3) 3/0
AWG–500 kcmil Al or Cu |
800 A |
P( )A36080 |
||||
1000 A |
P( )A36100 |
(4) 3/0
AWG–500 kcmil Al or Cu |
|||
1200 A |
P( )A36120 |
||||
MicroLogic Trip Unit |
LI |
3.0 |
250 A |
P( )A36025(C)U31A |
(3) 3/0
AWG–500 kcmil Al or Cu |
400 A |
P( )A36040(C)U31A |
||||
600 A |
P( )A36060(C)U31A |
||||
800 A |
P( )A36080(C)U31A |
||||
1000 A |
P( )A36100U31A |
(4) 3/0
AWG–500 kcmil Al or Cu |
|||
1200 A |
P( )A36120U31A |
||||
LSI |
5.0 |
250 A |
P( )A36025(C)U33A |
(3) 3/0
AWG–500 kcmil Al or Cu |
|
400 A |
P( )A36040(C)U33A |
||||
600 A |
P( )A36060(C)U33A |
||||
800 A |
P( )A36080(C)U33A |
||||
1000 A |
P( )A36100U33A |
(4) 3/0
AWG–500 kcmil Al or Cu |
|||
1200 A |
P( )A36120U33A |
||||
MicroLogic Trip Unit |
LI |
3.0A |
250 A |
P( )A36025(C)U41A |
(3) 3/0
AWG–500 kcmil Al or Cu |
400 A |
P( )A36040(C)U41A |
||||
600 A |
P( )A36060(C)U41A |
||||
800 A |
P( )A36080(C)U41A |
||||
1000 A |
P( )A36100U41A |
(4) 3/0
AWG–500 kcmil Al or Cu |
|||
1200 A |
P( )A36120U41A |
||||
LSI |
5.0A |
250 A |
P( )A36025(C)U43A |
(3) 3/0
AWG–500 kcmil Al or Cu |
|
400 A |
P( )A36040(C)U43A |
||||
600 A |
P( )A36060(C)U43A |
||||
800 A |
P( )A36080(C)U43A |
||||
1000 A |
P( )A36100U43A |
(4) 3/0
AWG–500 kcmil Al or Cu |
|||
1200 A |
P( )A36120U43A |
||||
LSIG |
6.0A |
250 A |
P( )A36025(C)U44A |
(3) 3/0
AWG–500 kcmil Al or Cu |
|
400 A |
P( )A36040(C)U44A |
||||
600 A |
P( )A36060(C)U44A |
||||
800 A |
P( )A36080(C)U44A |
||||
1000 A |
P( )A36100U44A |
(4) 3/0
AWG–500 kcmil Al or Cu |
|||
1200 A |
P( )A36120U44A |
||||
MicroLogic Trip Unit |
LSI |
5.0P |
250 A |
P( )A36025(C)U63AE1 |
(3) 3/0
AWG–500 kcmil Al or Cu |
400 A |
P( )A36040(C)U63AE1 |
||||
600 A |
P( )A36060(C)U63AE1 |
||||
800 A |
P( )A36080(C)U63AE1 |
||||
1000 A |
P( )A36100U63AE1 |
(4) 3/0
AWG–500 kcmil Al or Cu |
|||
1200 A |
P( )A36120U63AE1 |
||||
LSIG |
6.0P |
250 A |
P( )A36025(C)U64AE1 |
(3) 3/0
AWG–500 kcmil Al or Cu |
|
400 A |
P( )A36040(C)U64AE1 |
||||
600 A |
P( )A36060(C)U64AE1 |
||||
800 A |
P( )A36080(C)U64AE1 |
||||
1000 A |
P( )A36100U64AE1 |
(4) 3/0
AWG–500 kcmil Al or Cu |
|||
1200 A |
P( )A36120U64AE1 |
||||
MicroLogic Trip Unit |
LSI |
5.0H |
250 A |
P( )A36025(C)U73AE1 |
(3) 3/0
AWG–500 kcmil Al or Cu |
400 A |
P( )A36040(C)U73AE1 |
||||
600 A |
P( )A36060(C)U73AE1 |
||||
800 A |
P( )A36080(C)U73AE1 |
||||
1000 A |
P( )A36100U73AE1 |
(4) 3/0
AWG–500 kcmil Al or Cu |
|||
1200 A |
P( )A36120U73AE1 |
||||
LSIG |
6.0H |
250 A |
P( )A36025(C)U74AE1 |
(3) 3/0
AWG–500 kcmil Al or Cu |
|
400 A |
P( )A36040(C)U74AE1 |
||||
600 A |
P( )A36060(C)U74AE1 |
||||
800 A |
P( )A36080(C)U74AE1 |
||||
1000 A |
P( )A36100U74AE1 |
(4) 3/0 AWG–500 kcmil Al or Cu |
|||
1200 A |
P( )A36120U74AE1 |
PowerPacT R-frame 1200 A (600 Vac, 50/60 Hz) 3P Circuit Breaker with Electronic Trip Unit
Electronic Trip Unit |
Sensor Rating |
Terminal |
|||
---|---|---|---|---|---|
Type |
Function |
Code |
|||
Basic Electronic Trip Unit |
Fixed Long-Time, Adjustable Instantaneous |
ET1.01 |
1200 A |
R( )A36120 |
AL1200R53K |
MicroLogic Trip Unit |
LI |
3.0 |
1000 A |
R( )A36100CU31A |
|
1200 A |
R( )A36120CU31A |
||||
LSI |
5.0 |
1000 A |
R( )A36100CU33A |
||
1200 A |
R( )A36120CU33A |
||||
MicroLogic Trip Unit |
LI |
3.0A |
1000 A |
R( )A36100CU41A |
|
1200 A |
R( )A36120CU41A |
||||
LSI |
5.0A |
1000 A |
R( )A36100CU43A |
||
1200 A |
R( )A36120CU43A |
||||
LSI |
6.0A |
1000 A |
R( )A36100CU44A |
||
1200 A |
R( )A36120CU44A |
||||
MicroLogic Trip Unit |
LSI |
5.0P |
1000 A |
R( )A36100CU63AE1 |
|
1200 A |
R( )A36120CU63AE1 |
||||
LSIG |
6.0P |
1000 A |
R( )A36100CU64AE1 |
||
1200 A |
R( )A36120CU64AE1 |
||||
MicroLogic Trip Unit |
LSI |
5.0H |
1000 A |
R( )A36100CU73AE1 |
|
1200 A |
R( )A36120CU73AE1 |
||||
LSIG |
6.0H |
1000 A |
R( )A36100CU74AE1 |
||
1200 A |
R( )A36120CU74AE1 |
P- and R-frame accessories, see PowerPact Accessories in Section 7 of the Digest.
P- and R-frame dimensions, see Molded Case Circuit Breaker Dimensions in Section 7 of the Digest.
P- and R-frame trip unit options, see MicroLogic Electronic Trip Units in Section 7 of the Digest.
P- and R-frame optional lugs, see Mechanical Lugs in Section 7 of the Digest.
P- and R-frame alternate rating plugs, see MicroLogic Electronic Trip Units in Section 7 of the Digest.