Separated Distribution and Split Bus NF and NQ Panelboards
Refer to Panelboards
Separated Distribution and Split Bus NF and NQ Panelboards
|
Special lug pad adaptors allow field removal of cables, for easy field installation of solid core or split CTs for electrical energy measurement, by load type. |
|
Split Bus panelboards enable configurations of two or three back fed main circuit breakers, with independent branch distribution sections, in a single enclosure. |
Separated Distribution Interiors (Cabled Between Sections)
Separated Distribution
Interiors |
Max. No. of |
Box Height |
|||||
---|---|---|---|---|---|---|---|
Product Family |
Main Amp- |
Voltage Phases |
Main |
Split |
Split 2 |
Main Lug Only |
Main Circuit Breaker |
NQ |
225 A | 3 Ph |
30 |
18 |
18 |
62 | 74 |
18 |
18 |
18 |
62 | 74 | |||
400 A |
30 |
18 |
18 |
80 | 92 | ||
18 |
18 |
18 |
80 | 92 | |||
NF |
250 A | 3 Ph |
30 |
18 |
18 |
80 | 92 |
18 |
18 |
18 |
74 | 86 |
Bus Bar Interiors
(125 A Max. Split Amps)
Split Bus Bar Interiors |
Max. No. of |
Box Height |
|||||
---|---|---|---|---|---|---|---|
Product Family |
Main Amp- |
Voltage Phases |
Main |
Split |
Split 2 |
Main Lug Only |
Main Circuit Breaker |
NQ |
225 A | 1, 3 Ph |
18 |
30 |
— |
44 | 56 |
1, 3 Ph |
30 |
18 |
— |
44 | 56 | ||
1, 3 Ph |
30 |
30 |
— |
44 | 56 | ||
3 Ph |
30 |
18 |
18 |
50 | 62 | ||
NF |
250 A | 3 Ph |
18 |
30 |
— |
56 | 68 |
1, 3 Ph |
30 |
18 |
— |
56 | 68 | ||
1, 3 Ph |
30 |
30 |
— |
62 | 74 | ||
3 Ph |
30 |
18 |
18 |
74 | 86 |
Square D NF and NQ Separated Distribution and Split Bus Panelboards come Factory Assembled with copper bus, with or without an integral Main Circuit Breaker. A wide variety of configurations may be submitted for quotation via Square D QuoteFAST, and may be quoted or ordered by Authorized Distributors using SE Advantage or E-Way Quote Management.
Features:
-
Multiple branch section configurations (pole spaces per section):
-
Split Bus: 18-30; 30-18; 30-30; 30-18-18
-
Separated Distribution: 30-18-18; 18-18-18
-
-
Up to 400 A Mains rating for NQ; up to 250 A Mains in NF panelboards
Notes:
Enclosure width / depth: 20 in. / 5.75 in. minimum.
Subfeed breaker or lugs, feed through lugs not available at top or bottom ends of panel.
-
Split Bus - feeder breaker (125 A max.) in downstream split section back-fed from feeder breaker in upstream main or split section.
-
Segregated Distribution - cables may be removed in the field. Downstream Split section may have same rating as Main.