NQ Factory Assembled Panelboards
NQ Main and Sub-feed Circuit Breakers
Factory Assembled Main Circuit Breakers
400 A and 600 A panelboards, 1Ø or 3Ø
NQ Panelboard Factory Assembled Interiors - 240 Vac / 48 Vdc Max
Single Phase or Three Phase | ||||||
---|---|---|---|---|---|---|
Mains Rating (Amps) | Max. Number of One-Pole Circuit Breakers | Bus Material | Min. Box Depth | |||
Main Lugs Only | Main Circuit Breaker[1] |
Main Switch[1] | Main Lugs Only | Main Circuit Breaker / Switch |
||
100 Max | 15–100 | 70–100 | 18, 30 | Al, Cu | 5.75 in. | 5.75 in. |
225 Max | 15–250 | 110–250 | 30, 42, 54, 72, 84 | Al, Cu | 5.75 in. | 5.75 in. |
400 Max | 125–400 | 300–400 | 30, 42, 54, 72[2], 84[3] | Al, Cu | 5.75 in. | 5.75 in. / 8.75 in.[4] |
600 Max | 125–600 | 450–600 | 30, 42, 54, 72[2], 84 | Cu | 5.75 in. | 8.75 in.[4] |
Main Circuit Breaker (PowerPacT L-frame - see PowerPacT Interrupting Ratings, and Common Catalog Numbering System, in Section 7)
Number of Poles | Trip Unit Options | Frame Sizes | Ampacity |
---|---|---|---|
3 | LI, LSI, Switch | LG, LJ, LL | 125–600 A |
LA/LH PowerPacT H, J, and Q-frame circuit breakers are also available - see PowerPacT Interrupting Ratings and Common Catalog Numbering System and Supplemental Digest Section 3.
PowerPacT L Main Circuit Breaker Cabinet Height (inches)
Max.
No. of Branch Spaces (Does not include sub-feed circuit breaker spaces) |
NEMA 1 Enclosure (20 in. W x 8.75 in. D)[4] |
Vented NEMA
3R Enclosure (26 in. W x 8.75 in. D)[5] |
|
---|---|---|---|
400 or 600 A | 400 A | 600 A | |
30 | 62 | 62 | 68 |
42 | 68 | 68 | 74 |
54 | 74 | 74 | 80 |
72 | 80 | – | – |
84 | 86 | – | – |
Sub-feed Circuit Breakers
Main lugs or main circuit breaker interior—1Ø or 3Ø.
Maximum 1 circuit breaker per 225 A main lug or 250 A main
circuit breaker panelboard, 2 PowerPacT H-, J-, or Q-frame
sub-feed circuit breakers may be installed on a
Panelboards in MHxxWP NEMA Type 3R/5/12 enclosures are limited to one 150 A maximum sub-feed breaker.
-
Panelboards in vented MHxxD9VWP NEMA 3R enclosures may have two 225 A maximum sub-feed circuit breakers. A single 600 A maximum sub-feed circuit breaker may be factory installed in these new enclosures.
Sub-feed Circuit Breakers for NQ Panelboards[6]
Interior Rating |
Sub Feed Circuit Breakers[6] |
Space Factor |
||
---|---|---|---|---|
Ampacity |
Poles |
MCCB Frame |
||
225 A | 70–225 | 2 or 3 | QB, QD, QG, QJ | 18 in. |
110–150 | 2 or 3 | HD, HG, HJ, HL, HR[7] | ||
150–225 | 2 or 3 | JD, JG, JJ, JL, JR[8] | ||
400 A / 600 A | 70–225 | 2 or 3 | QB, QD, QG, QJ[9] | 24 in. |
110–150 | 2 or 3 | HD, HG, HJ, HL, HR[7], [9] | ||
150–225 | 2 or 3 | JD, JG, JJ, JL, JR[8], [9] | ||
125–400 | 2 or 3 | LA / LH | 18 in.[10] | |
125–600 | 3 | LG, LJ, LL | 18 in.[11] | |
PowerPacT H, J, & L frame circuit breakers are also available - see Tables PowerPacT Interrupting Ratings, and Common Catalog Numbering System, Section 7. |
PowerPacT H, J, or Q-frame Sub-feed Circuit Breaker Cabinet Height (inches)[12]
Max. No. of Branch Circuit Spaces (not including sub-feed circuit breaker) |
Mains Type and Maximum Current Rating |
||||
---|---|---|---|---|---|
225 A Main Lugs[13] |
250 A Main Circuit Breaker[14] |
400 / 600 A Main Lugs[15] |
400 A LA/LH Main Circuit Breaker[16] |
400 / 600 A LG/LJ/LL Main Circuit Breaker[17] |
|
30 |
50 |
62 |
74 |
86 |
86 |
42 |
56 |
68 |
74 |
86 |
86 |
54 |
62 |
74 |
80 |
92 |
– |
72 |
68 |
80 |
86 |
– |
– |
84 |
74 |
86 |
92 |
– |
– |
PowerPacT LG, LJ, or LL Sub-feed Circuit Breaker Cabinet Height (inches)[18]
Max. No. of Branch Spaces (Does not include sub-feed circuit breaker spaces) | NEMA 1 D9 Enclosure (8.75-in. D)[19] |
Vented NEMA
3R Enclosure Height (26-in. W x 8.75-in. D) |
|||||
---|---|---|---|---|---|---|---|
20-in. Wide | 26-in. Wide | Main Lugs | Main Circuit Breaker[19] | ||||
Main Lugs | LA / LH Main Circuit Breaker | LG / LJ / LL[19] | |||||
Main Breaker | LA / LH | 400A PP-L | 600A PP-L | ||||
30 | 68 | 80 | 80 | 74 | 74 | 86 | 92 |
42 | 68 | 80 | 86 | 74 | 80 | 86 | 92 |
54 | 74 | 86 | 92 | 80 | 86 | 92 | — |
72 | 80 | 92 | — | — | — | — | — |
84 | 86 | — | — | — | — | — | — |
Weather and Dust Resistant Enclosures—Type 3R, 4, 4X, 5, 12
Weatherproof or Dusttight Cabinets |
---|
noteNQ panelboards with PowerPacT L circuit
breakers are not available with a NEMA Type 4, 4X, 5, or 12 enclosure.
(Use I-Line).
|
NQ panelboards with PowerPacT L circuit breakers are available with vented 26 in. wide NEMA 3R enclosures. These vented NEMA 3R enclosures also enable selection of subfeed circuit breakers up to 600 A.
400 A maximum NQ panelboards in NEMA 4, 4X, 5, or 12 enclosures are available with one subfeed breaker up to 150 A.